Standard Operating Procedure · Equipment: Sungrow SG125HT three-phase string inverter · Document ID: TVT-SOP-CN-AU-INV-014 · Revision: A · Effective: 2026-09-21
Verdict: ~6 hours on-site. This SOP executes the volt-var / volt-watt acceptance test of the Sungrow SG125HT three-phase string inverter per AS/NZS 4777.2:2020. Proceed only after firmware, LOTO, and AC source readiness are confirmed.
Equipment: Sungrow SG125HT (1500 V DC, C&I three-phase string inverter) [Src: Sungrow product range | URL: https://www.sungrowpower.com/en/products/string-inverter | accessed 2026-09-21]. Location: CN → AU export corridor, on-site at AU PCC. Horizon: Single visit, Day 1. Evidence date: 2026-09-21.
| Item | Value | Source |
|---|---|---|
| Equipment model | Sungrow SG125HT (3-phase string inverter) | https://www.sungrowpower.com/en/products/string-inverter |
| Standard | AS/NZS 4777.2:2020 (clause on grid-support volt-var/volt-watt) | https://www.standards.org.au |
| Duration | ~6 hours on-site (model assumption pending site survey) | Internal estimate |
| HS code candidate | 8504.40 (static converters — to be confirmed by licensed broker) | https://www.abf.gov.au/importing-exporting-and-manufacturing/tariff-classification/current-tariff |
| Incoterm default | CIF Australian port per Incoterms 2020 | https://iccwbo.org/business-solutions/incoterms-rules/incoterms-2020/ |
| Limitation | Specific SG125HT service-manual revision confirmed at RFQ; SOP parameters derived from public datasheet envelope only | Model assumption |
This SOP governs the on-site acceptance test of the reactive-power (volt-var / volt-watt / Q(V)) grid-support functions of the Sungrow SG125HT three-phase string inverter before hand-over on the China-to-Australia export corridor. It applies to SG125HT units shipped under Tradvolt job numbers prefixed TVT-CAU-. The SG125HT is a 1500 V DC, C&I-rated three-phase string inverter; exact firmware parameter set, clearing time, and tolerance values must be reconfirmed against the current Sungrow SG125HT service manual revision at the time of commissioning.
| Step # | Action | Owner | Input doc | Output doc | Done-when |
|---|---|---|---|---|---|
| 1 | Confirm single-line diagram, PCC, and AS/NZS 4777.2:2020 region setting (A/B/C) | Commissioning Engineer | TVT-PRJ-CAU-001 SLD | Pre-test checklist | Region code recorded and signed |
| 2 | Lock-out / tag-out DC and AC isolators per Sungrow SG125HT service manual (current AU revision) | Site Safety Officer | LOTO register; Sungrow SG125HT service manual | LOTO permit | Zero-energy verified on calibrated meter |
| 3 | Verify SG125HT firmware version matches AU parameter set (region code, volt-var / volt-watt curves) | Commissioning Engineer | Firmware manifest; SG125HT service manual | Firmware sign-off sheet | Hash match logged in commissioning folder |
| 4 | Connect programmable AC source ≥110% of SG125HT nominal apparent power | Test Technician | AC source calibration cert | Source connection log | Three-phase voltages balanced ±2% |
| 5 | Run volt-var curve through V1–V4 per AS/NZS 4777.2:2020 Table 4 | Commissioning Engineer | Volt-var test sheet | Reactive-power CSV | Q output within ±5% of setpoint at each step |
| 6 | Run volt-watt curve through Vw1–Vw4 per AS/NZS 4777.2:2020 Table 5 | Commissioning Engineer | Volt-watt test sheet | Active-power CSV | P curtailment within ±5% of setpoint at each step |
| 7 | Repeat Q(V) three times; compute mean reactive error against SG125HT datasheet tolerance | Test Technician | CSV set; SG125HT datasheet | Repeatability report | Mean error ≤ SG125HT datasheet tolerance band |
| 8 | Spot-check anti-islanding: open AC contactor, record clearing time against SG125HT service-manual limit | Commissioning Engineer | Anti-island log; SG125HT service manual | Anti-island record | Trip ≤ SG125HT service-manual clearing time |
| 9 | Visual AQL inspection per ISO 2859-1:1999 General Level II, AQL 1.0 | QC Inspector | ISO 2859-1 General Level II / AQL 1.0 sampling table | AQL inspection form | Sample defects ≤ accept number |
| 10 | Compile evidence pack: PDF report, screenshots, raw CSVs | Documentation Lead | All prior outputs | Final commissioning dossier | Dossier uploaded to job folder, link issued |
TVT-CAU-PRE-CHECK-001.pdf — pre-test safety checklistTVT-CAU-LOTO-PERMIT-001.pdf — lock-out / tag-out permit (cites Sungrow SG125HT service-manual revision)TVT-CAU-FW-SIGNOFF-001.pdf — SG125HT firmware hash and parameter-set sign-offTVT-CAU-VOLTVAR-CSV.zip — volt-var raw measurement archiveTVT-CAU-VOLTWATT-CSV.zip — volt-watt raw measurement archiveTVT-CAU-REPEAT-REP-001.pdf — repeatability reportTVT-CAU-ANTIISLAND-001.pdf — anti-islanding recordTVT-CAU-AQL-FORM-001.pdf — ISO 2859-1:1999 AQL inspection form (General Level II, AQL 1.0)TVT-CAU-FINAL-DOSSIER-001.pdf — final commissioning dossier| Phase | Activity | Dependency | Indicative duration |
|---|---|---|---|
| Pre-arrival | Documentation review and SG125HT firmware staging | Job number issued; Sungrow SG125HT service-manual revision on file | 2 working days — UNCERTAIN pending AU customs hold |
| On-site Day 1 AM | LOTO, AC source connection | PCC energised, safety permits | 2 h |
| On-site Day 1 PM | Volt-var + volt-watt curves | Steps 1–4 closed | 2 h |
| On-site Day 1 PM | Repeatability and anti-islanding | Curve tests signed off | 1 h |
| On-site Day 1 PM | AQL visual + dossier upload | All measurements captured | 1 h |
All figures below are indicative and UNCERTAIN; final quotation is issued only after RFQ intake and current carrier/authority tariff lookup on 2026-09-21.
Equipment / parts: Sungrow SG125HT three-phase string inverter (1500 V DC, C&I class) with grid-support functions.
Recommended HS code candidate (must be confirmed by a licensed customs broker at booking):
8504.40 — Static converters — typical heading for power inverters on the AU Working Tariff [Src: Australian Border Force — current tariff-classification page for HS 8504.40 | URL: https://www.abf.gov.au/importing-exporting-and-manufacturing/tariff-classification/current-tariff | accessed 2026-09-21].8504.40.00 sub-line — to be confirmed against the AU Working Tariff and CN Customs Export Tariff at the time of shipment.Duty rate: PENDING — lookup against the ABF Working Tariff current-tariff section and any applicable Free Trade Agreement (e.g., ChAFTA) preference at the time of entry.
GST / VAT: PENDING — lookup.
Official portals consulted: Australian Border Force current tariff-classification page (https://www.abf.gov.au/importing-exporting-and-manufacturing/tariff-classification/current-tariff) and GACC (http://english.customs.gov.cn).
Disclaimer: HS classification and duty rates are jurisdiction-specific and time-sensitive. Tradvolt does not issue binding tariff rulings; the buyer is responsible for engaging a licensed customs broker and confirming the classification, preferential origin, and applicable rate at the date of export and import.
Default quotation basis for this corridor is CIF Australian port per Incoterms 2020 (rule CIF, ICC publication 723E); alternative terms (FOB, DAP, DDP) available on RFQ. Risk transfer and cost allocation follow the official ICC Incoterms 2020 rules page [Src: ICC — Incoterms 2020 | URL: https://iccwbo.org/business-solutions/incoterms-rules/incoterms-2020/ | accessed 2026-09-21].
Request Quote — replies in 48h