**Answer (R14):** For CN→EU corridor fire-detector shipments, pre-shipment sensitivity verification on a typical Hochiki ESP Intelligent point-type smoke detector (e.g. *ALN-EN(WHT)*, firmware ≥ v3.4) or a Hochiki *ACB-EW* heat detector requires (i) the OEM datasheet and commissioning manual pull, (ii) drift-compensation sampling per the OEM FPC AQL, (iii) EN 54-7:2018 / EN 54-5:2017+A1:2018 stimulus testing, and (iv) a consignment file with DoP + CE evidence retained for 10 years under CPR (EU 305/2011). Equipment: Hochiki ALN-EN series optical smoke detector (EN 54-7) and ACB-EW heat detector (EN 54-5). Location: CN production line → EU port. Horizon: pre-shipment (D-7 to D0) plus ≥10-year importer archive. Evidence date: 2026-09-22. Limitation: HS code for these detectors is pending verification — use the TARIC lookup path below before customs filing; rate not asserted.

| Topic | Decision / value | Source |
| --- | --- | --- |
| Equipment family (illustrative) | Hochiki ALN-EN(WHT) / ALN-EN(VAD) optical smoke detector; Hochiki ACB-EW heat detector (Class A2S) | Hochiki product pages (see §3) |
| Applicable harmonised standards | EN 54-7:2018 (smoke); EN 54-5:2017+A1:2018 (heat) | BSI catalogue (see §2) |
| Regulatory regime | CPR (EU) No 305/2011 — DoP + CE marking mandatory | EUR-Lex CELEX 32011R0305 |
| HS / customs code | PENDING — verify via EU TARIC consultation | ec.europa.eu TARIC lookup |
| Documentation retention | ≥10 years (importer of record) | Regulation (EU) No 305/2011, Art. 7(3) & 11(2) |
| Archive horizon | Pre-shipment (D-7 to D0) + 10 years post-EU receipt | CPR + OEM warranty |

[Request a tailored RFQ (R14)](https://tradvolt.com/rfq/?topic=fire-detector-sensitivity-r14) [Download the R14 PDF checklist](https://tradvolt.com/assets/guides/cn-eu-fire-detector-sensitivity-r14-checklist.pdf)

**Indicative content.** This guide consolidates manufacturer and standards-body references; it is not a substitute for the OEM commissioning manual or the EN 54 series text held by your Notified Body. Always cross-check the latest revision of cited documents against the detector model and firmware on the actual shipment manifest.

## 1. Scope & applicability

This guide applies to point-type smoke and heat detectors carrying a Declaration of Performance (DoP) under the EU Construction Products Regulation (CPR, EU 305/2011) and destined for fixed installation in EU/EEA buildings via the CN→EU corridor. It does not cover aspirating detectors, flame detectors, or addressable system design — those follow separate OEM and EN 54-20 / EN 54-10 procedures. The workflow assumes batch-level sampling on the production line in China, followed by pre-shipment document compilation for EU customs and the importer of record.

The maintenance lens is deliberate: detector sensitivity drifts over time as chamber optics foul and as analogue sensor elements age. OEM commissioning tools typically expose a "drift compensation" or "analogue value" reading that should be captured at the pre-shipment gate so the EU installer has a clean baseline. Where this reading sits outside the OEM's declared band, the unit should be quarantined, not shipped.

## 2. Standards & documentary anchors

- **EN 54-5:2017+A1:2018** — Heat detectors, point-type. Defines classes A1, A2, B, C, D, E, F, G and the maximum application temperatures and static response temperatures. See BSI catalogue entry for EN 54-5:2017+A1:2018 (Fire detection and fire alarm systems. Part 5: Heat detectors. Point detectors): [BSI Standards Development](https://standardsdevelopment.bsigroup.com/) (catalogue — search "BS EN 54-5:2017+A1:2018").

- **EN 54-7:2018** — Smoke detectors, point-type using scattered light, transmitted light, or ionisation. Specifies response thresholds and test methods. See BSI catalogue entry for BS EN 54-7:2018 (Fire detection and fire alarm systems. Part 7: Smoke detectors. Point detectors using scattered light, transmitted light or ionisation): [BSI Standards Development](https://standardsdevelopment.bsigroup.com/) (catalogue — search "BS EN 54-7:2018").

- **EU Regulation No 305/2011 (CPR)** — Establishes the DoP and CE marking framework for construction products, including fire safety products. Consolidated text: [EUR-Lex CELEX 32011R0305 — Regulation (EU) No 305/2011](https://eur-lex.europa.eu/legal-content/EN/TXT/?uri=CELEX:32011R0305).

- **HS classification** — **PENDING verification.** Use the EU TARIC consultation tool at [EU TARIC consultation](https://ec.europa.eu/taxation_customs/dds2/taric/taric_consultation.jsp?Lang=en) to confirm the code and applicable third-country duty rate for this consignment before customs filing. Do not assert a rate until the TARIC query is complete.

- **OEM commissioning manual** — computed for the specific detector model; supersedes generic guidance whenever they diverge. For the illustrative Hochiki ALN-EN(WHT) and ACB-EW references used in this guide, see the Hochiki ESP product literature at [Hochiki Europe product pages](https://www.hochikieurope.com/) (model-specific datasheet and commissioning manual revisions must be confirmed at RFQ time — treated as a model assumption).

## 3. Step-by-step maintenance process

Each step has a single named owner. The "Done-when" cell is the gate — do not advance until the criterion is satisfied and recorded. Equipment references below assume the illustrative Hochiki ALN-EN(WHT) optical smoke detector (EN 54-7) and Hochiki ACB-EW heat detector (EN 54-5, Class A2S); substitute the actual OEM model, firmware revision, and sensitivity class from your shipment manifest before production.

| Step # | Action | Owner | Input document | Output document | Done-when |
| --- | --- | --- | --- | --- | --- |
| 1 | Confirm applicable harmonised standard and DoP availability for the model on the shipment manifest (e.g. Hochiki ALN-EN(WHT) → EN 54-7:2018; ACB-EW → EN 54-5:2017+A1:2018). | QA Lead (CN site) | Shipment manifest (CSV/XLSX) | Standards-mapping note (MD, internal) | EN 54 part number recorded against each line item and the DoP is retrievable from the manufacturer's CE database. |
| 2 | Pull OEM datasheet and commissioning manual for the specific detector model and firmware revision (illustrative: Hochiki ALN-EN datasheet rev. 2024-04 and ESP commissioning manual rev. ≥ 3.4 — model assumption, confirm at RFQ). | QA Lead (CN site) | OEM product code | Datasheet pack (PDF) | Nominal analogue value, alarm threshold, and drift band are extracted to the worksheet and quoted in the OEM manual's terms. |
| 3 | Pre-batch sampling: read drift compensation / analogue value from a defined AQL sample using the OEM protocol (e.g. Hochiki ESP loop explorer reading on ALN-EN: analogue value window per datasheet rev. 2024-04). | Line Technician (CN) | Datasheet pack (PDF) | Sampling log (CSV) | Sample size meets the OEM's AQL rule; raw values fall within declared band. |
| 4 | Functional response test with stimulus matching EN 54-7:2018 (smoke aerosol into measuring chamber for ALN-EN(WHT)) or EN 54-5:2017+A1:2018 (heat stimulus at Class A2S for ACB-EW) at declared class temperature. | Test Bench Operator (CN) | Sampling log (CSV) | Functional test record (CSV/PDF) | Each sampled unit reaches alarm state within declared response time; failures are tagged. |
| 5 | Quarantine non-conforming units and open a Non-Conformance Report (NCR) per supplier procedure. | QA Lead (CN site) | Functional test record (CSV/PDF) | NCR entry (internal DB) | Failing serial numbers are physically segregated and the NCR has an owner and a closure date. |
| 6 | Compile EU customs documentation set: DoP, CE/UKCA evidence, invoice, packing list, HS code reference (HS code PENDING — verify via EU TARIC before filing). | Export Coordinator (CN) | Standards-mapping note (MD); Invoices (PDF) | Consignment file (ZIP/PDF) | Every required document is present, named per the checklist below, and the file is hashed. |
| 7 | Pre-shipment review and archival for traceability (CPR + OEM warranty horizon). | QA Manager (CN site) | Consignment file (ZIP/PDF) | Signed release note (PDF) | QA Manager signs; digital copies archived for ≥10 years per CPR Art. 7(3) and Art. 11(2). |

## 4. Document checklist (literal filenames)

Save the consignment file using these exact filenames. The convention keeps the corridor audit trail searchable across shipments and across Notified Body reviewers. Where the filename embeds a model placeholder, replace `<model>` with the actual OEM model and `RevX` with the datasheet or commissioning manual revision actually pulled from the manufacturer.

| # | Literal filename | Source | Purpose |
| --- | --- | --- | --- |
| 1 | `01_Manifest_CN-EU_R14.csv` | Internal | Line-item reference with OEM product code, quantity, batch, serial range. |
| 2 | `02_DoP_<model>_EN54-7.pdf` or `02_DoP_<model>_EN54-5.pdf` | OEM | Declaration of Performance under CPR (EU) No 305/2011 — see EUR-Lex CELEX 32011R0305. |
| 3 | `03_CE_Marking_Image_<model>.png` | OEM | Photograph of the physical CE mark + notified body number on the product label. |
| 4 | `04_Datasheet_<model>_RevX.pdf` | OEM | Rated sensitivity, response thresholds, drift band, dimensions (e.g. Hochiki ALN-EN datasheet rev. 2024-04 — model assumption). |
| 5 | `05_Commissioning_Manual_<model>_RevX.pdf` | OEM | computed test procedure and analogue-value interpretation (e.g. Hochiki ESP commissioning manual rev. ≥ 3.4 — model assumption, confirm revision at RFQ). |
| 6 | `06_Sampling_Log_<batch>.csv` | Internal | Raw analogue / drift-compensation readings per serial number. |
| 7 | `07_Functional_Test_<batch>.pdf` | Internal | Pass/fail of EN 54-7:2018 aerosol or EN 54-5:2017+A1:2018 heat stimulus per unit. |
| 8 | `08_NCR_Log_<period>.xlsx` | Internal | Non-conformance register covering any quarantined units. |
| 9 | `09_Commercial_Invoice_<invoice#>.pdf` | Internal | Value, currency, Incoterms (per ICC Incoterms® 2020), HS code field marked PENDING pending EU TARIC verification. |
| 10 | `10_Packing_List_<shipment#>.pdf` | Internal | Carton count, gross/net weight, dimensions. |
| 11 | `11_Consignment_File_Hash.txt` | Internal | SHA-256 of the consignment ZIP for tamper evidence. |

## 5. Timeline & responsibilities

| Phase | Indicative day | Activity | Owner |
| --- | --- | --- | --- |
| Pre-production | D-7 | Confirm DoP, datasheet (e.g. Hochiki ALN-EN rev. 2024-04), commissioning manual (rev. ≥ 3.4), and standards mapping are current. | QA Lead (CN) |
| Sampling | D-3 | Pre-batch sampling and analogue-value logging. | Line Technician (CN) |
| Functional test | D-2 | EN 54-7:2018 aerosol or EN 54-5:2017+A1:2018 heat response test. | Test Bench Operator (CN) |
| NCR handling | D-1 | Quarantine, NCR, root-cause tagging. | QA Lead (CN) |
| Document pack | D-1 → D0 | Compile consignment file with literal filenames (HS code PENDING until TARIC verified). | Export Coordinator (CN) |
| Release | D0 | Pre-shipment review and signed release note. | QA Manager (CN) |
| EU receipt | D+port | Importer retains copies with CE/DoP for ≥10 years per CPR Art. 7(3). | EU Importer |

## 6. Indicative cost slots

These are **indicative** slots only. Pricing varies materially by detector type, OEM, batch size, Notified Body selection, and Incoterms (see [ICC Incoterms® 2020](https://iccwbo.org/business-solutions/incoterms-rules/incoterms-2020/)). Treat any number below as **UNCERTAIN / model assumption** unless you have a current OEM quote.

| Slot | Indicative range (EUR) | Confidence | Driver |
| --- | --- | --- | --- |
| Pre-batch sampling labour (per shift) | Indicative — varies by site | UNCERTAIN | Technician hours, AQL rate |
| Functional test consumables (aerosol / heat source) | Indicative — per OEM spec | UNCERTAIN | Stimulus type (EN 54-7:2018 aerosol; EN 54-5:2017+A1:2018 heat) and units tested |
| Notified Body testing (if re-tested) | Indicative — per quotation | UNCERTAIN | Whether the existing EN 54-7:2018 / EN 54-5:2017+A1:2018 report is accepted |
| Document compilation & archival | Indicative — internal cost | UNCERTAIN | Internal hours + storage |
| EU customs handling | Indicative — broker fee | UNCERTAIN | Broker model, port of entry (HS code and duty rate pending via EU TARIC) |

## 7. Request a tailored RFQ

[Request a tailored RFQ (R14)](https://tradvolt.com/rfq/?topic=fire-detector-sensitivity-r14)

Need a detector-specific version (model, firmware, sensitivity class)? Tradvolt can mirror this maintenance workflow against your OEM part numbers and target Notified Body evidence. Equipment references used in this guide (Hochiki ALN-EN(WHT) optical smoke detector under EN 54-7:2018 and Hochiki ACB-EW heat detector under EN 54-5:2017+A1:2018) are illustrative; the actual model, firmware, and commissioning manual revision will be confirmed at RFQ time.

## 8. FAQ

**1. Is sensitivity calibration mandatory for every detector before export?**

Pre-shipment verification of the analogue / drift-compensation value and a functional stimulus test is the practical gate. EN 54-5:2017+A1:2018 and EN 54-7:2018 do not prescribe a sampling rate per shipment — that is set by the manufacturer's FPC plan and the importer's quality agreement.

**2. What is the AQL I should use?**

Use the figure named in your supplier's FPC plan or quality agreement. There is no EN 54-mandated AQL; OEM datasheets (e.g. the Hochiki ALN-EN datasheet rev. 2024-04) usually state one for batch release.

**3. Does the EU importer need the originals?**

Yes. The DoP and CE marking must be supplied with the product (paper or PDF per [CPR (EU) No 305/2011](https://eur-lex.europa.eu/legal-content/EN/TXT/?uri=CELEX:32011R0305) Article 7), and the importer must keep copies on file for at least 10 years (Article 7(3) and Article 11(2)).

**4. What about UKCA / Great Britain?**

Separate regime. If the consignment also lands in GB, a UKCA mark and UK Declaration of Conformity are required in addition to the CE / DoP for the EU27 — see [GOV.UK — placing construction products on the GB market](https://www.gov.uk/guidance/placing-construction-products-on-the-gb-market).

**5. What if a unit fails after install?**

The serial number, batch ID and OEM firmware revision (e.g. Hochiki ESP firmware ≥ v3.4 on ALN-EN(WHT)) in this consignment file make the failure traceable back to the production date and the FPC records the OEM is required to retain.

**6. What HS code should I declare?**

PENDING — confirm via the [EU TARIC consultation](https://ec.europa.eu/taxation_customs/dds2/taric/taric_consultation.jsp?Lang=en) tool before customs filing. Do not assert a duty rate until the TARIC query is complete for the specific consignment.

## 9. Claim-row register

| Claim | Specific source URL | File / section |
| --- | --- | --- |
| EN 54-5:2017+A1:2018 defines classes A1–G with maximum application and static response temperatures. | BSI Standards Development catalogue — search "BS EN 54-5:2017+A1:2018" | EN 54-5 (cited in §2) |
| EN 54-7:2018 specifies point-type smoke detector test methods and response thresholds. | BSI Standards Development catalogue — search "BS EN 54-7:2018" | EN 54-7 (cited in §2, §3) |
| EU 305/2011 (CPR) requires a Declaration of Performance and CE marking for construction products. | EUR-Lex CELEX 32011R0305 — Regulation (EU) No 305/2011 | CPR (cited in §2, §3 step 6, §8 FAQ 3) |
| HS classification for fire detectors is to be verified via EU TARIC; duty rate not asserted. | EU TARIC consultation (lookup tool — PENDING) | §3 step 6; §4 item 9; §8 FAQ 6 |
| Importer must retain DoP and technical documentation for ≥10 years. | EUR-Lex CELEX 32011R0305 — Article 7(3) and Article 11(2) | §3 step 7; §8 FAQ 3 |
| Sensitivity drift and drift-compensation values are exposed via the OEM commissioning protocol. | Hochiki Europe product pages — Hochiki ESP commissioning manual rev. ≥ 3.4 (model assumption; confirm revision at RFQ) | §1, §3 step 2, §3 step 3 |
| UKCA marking is required for Great Britain in addition to CE for the EU27. | GOV.UK — placing construction products on the GB market | §8 FAQ 4 |
| Illustrative equipment family — Hochiki ALN-EN(WHT) optical smoke detector and Hochiki ACB-EW heat detector. | Hochiki Europe product pages (model assumption; actual OEM model to be confirmed at RFQ) | §1, §3 step 2, §8 FAQ 5 |
| Incoterms reference for trade-term allocation in commercial documents. | ICC Incoterms® 2020 official rules page | §4 item 9; §6 |