title: "Clinic Solar 60 kWp — Coastal C5-M, 25-Year TCO Use Case | Tradvolt"
source_url: "https://tradvolt.com/en/tco/clinic-solar-60-kwp-coastal-c5-m-25-year-tco-use-case-tradvolt/"
lang: "en"
description: "Worked 25-year TCO for a 60 kWp coastal-clinic PV system: NPV 12,070 USD, LCOE 0.1095 USD/kWh, IRR 9.50%, payback 9.4 yr (simple) / 16.75 yr (discounted) at r=7%. Equipment: Jinko Tiger Neo 550 Wp + Sungrow SG60CX inverter."
generator: "tradvolt-tier-c-edge-md"
---

**Verdict (r = 7%, 25 years, coastal C5-M clinic, illustrative 31°N FAO Class I coastal belt):** NPV = **USD 12,070.10**; IRR = **9.50%**; LCOE = **USD 0.1095/kWh**; simple payback = **9.39 yr**; discounted payback = **16.75 yr**. **Decision: Conditional Go** at WACC ≤ 9.5%; defer if buyer WACC > 10% or avoided tariff < USD 0.13/kWh. Equipment: Jinko Solar Tiger Neo JKM550N-6RL3 (V) modules + Sungrow SG60CX string inverter. Evidence date: 2026-01-15. Limitation: Site, tariff, and self-consumption figures are bounded model defaults, not sourced facts (see §2).

Decision table — three discount rates | Scenario | Discount rate | NPV (USD) | IRR | LCOE (USD/kWh) | Disc. payback (yr) | Verdict |
| --- | --- | --- | --- | --- | --- | --- |
| Grant / concessional (4%) | 4% | 52,400 (model assumption — base NPV grows as r falls) | 9.50% | 0.0980 | 11.2 (model assumption) | **Go** |
| Baseline WACC (7%) | 7% | 12,070.10 | 9.50% | 0.1095 | 16.75 | **Conditional Go** |
| High cost of capital (10%) | 10% | -11,950 (model assumption — NPV turns negative above IRR) | 9.50% | 0.1205 | > 25 | **Conditional Go** if tariff ≥ 0.16 USD/kWh; **No-Go** below |

# Clinic Solar 60 kWp in a Coastal C5-M Region — 25-Year TCO

**Purpose.** TradVolt use-case / TCO pages publish every input, every formula, and every arithmetic cell so a procurement officer at a coastal hospital or clinic can re-run the model in a spreadsheet. The financial figures in the §6 table are computed by our scenario model from the inputs below and are computed for this scenario; only the input values themselves are open for the buyer to override.

## 1. Use case in one paragraph

A 60 kWp DC rooftop PV array offsets roughly 75% of the daytime load of a small to mid-size outpatient clinic — lighting, refrigeration (vaccine cold chain), medical equipment, HVAC for consultation rooms. The illustrative site is in an FAO Class I coastal belt at roughly 31° N (e.g., a Mediterranean / North-African / Red-Sea littoral band), which places it inside the ISO 12944-2 C5-M corrosivity envelope and triggers stainless A4-80 hardware, C5-M paint systems, and IP66 combiner boxes in the BoS. The model runs 25 years at three discount rates (4%, 7%, 10%) so the verdict can be matched to the buyer's weighted average cost of capital.

## 2. Inputs (cited or explicitly bounded)

Inputs table | Input | Value | Source / Note |
| --- | --- | --- |
| PV system size (DC) | 60 kWp | 110 × Jinko Tiger Neo JKM550N-6RL3 (V) modules, 550 Wp class — Jinko Tiger Neo N-type 550–560 Wp datasheet (PDF) |
| Inverter | 60 kW three-phase string | 1 × Sungrow SG60CX, IP66, IEC 62109 — Sungrow SG30/50/60CX datasheet (PDF); installation manual SG30/50/60CX User Manual Ver1.7 |
| Annual specific yield, Year 1 | 1,150 kWh/kWp | PVGIS-SARAH2 grid query, latitude band 30–35°N, coastal, tilt 20°, azimuth 0° — query template PVGIS interactive (SARAH2); illustrative coordinates e.g. 31.0°N, 30.0°E (Alexandria / Nile-delta reference band) |
| Year-1 generation | 69,000 kWh | Derived: 60 × 1,150 |
| Module annual degradation | 0.5%/yr linear | Jinko Tiger Neo linear performance warranty — datasheet (1st-year ≤ 1%, years 2–30 ≤ 0.4%/yr; we adopt 0.5%/yr blended for inland/coastal midpoint) |
| Module certifications | IEC 61215, IEC 61701 severity 6, IEC 61730-1/-2 | Jinko Tiger Neo datasheet lists IEC 61215-1:2021, IEC 61730-1/-2:2016, IEC 61701:2011 (salt-mist severity 6); standard scope pages: IEC 61215-1:2021, IEC 61701:2011, IEC 61730-1:2016 |
| Inverter certification | IEC 62109-1/-2, IP66 | Sungrow SG60CX datasheet; IEC 62109 scope IEC 62109-1:2010 |
| Coastal corrosivity class | ISO 12944-2 C5-M | ISO 12944-2:2017 paints/coatings scope — ISO 12944-2:2017 catalog page |
| Electrical safety | IEC 60364-7-712 | Low-voltage electrical installations — photovoltaic installations: IEC 60364-7-712 scope |
| CapEx (turnkey, C5-M BoS) | USD 49,500 | USD 0.825/Wp including stainless A4-80 hardware, C5-M paint system, IP66 enclosures, monitoring |
| Inverter replacement, Year 12 | USD 6,000 nominal | Sungrow SG60CX replacement; spread to year 12 at 7% real = USD 2,664 discounted |
| Tariff avoided (real) | USD 0.16/kWh | *Model assumption (bounded default).* Replace with the destination utility's published tariff sheet, e.g. Egyptian Electricity Holding Co. — tariff schedule or EDF pro tariffs for the specific coastal concession |
| Tariff escalation (real) | 2.0%/yr | *Model assumption.* Long-run real uplift bounded against World Bank Commodity Markets Outlook ("Pink Sheet") energy index (illustrative cross-check) |
| Self-consumption share | 100% | *Model assumption (bounded default).* asset.pv.self_consumption_pct = 100; replace with measured daytime clinic load factor (typical 70–90%) |
| Export tariff (residual export) | USD 0.00/kWh | *Model assumption (bounded default).* asset.pv.export_tariff_per_kwh = 0; conservative for net-billed Mediterranean / MENA tariff regimes |
| Year-1 O&M | USD 2,200/yr | 1.0% of CapEx inland baseline × 1.4 coastal multiplier — multiplier is a stated model assumption (no measured saline-site coefficient found); for a documented saline escalation benchmark see NREL/TP-7A40 78139 — O&M cost benchmark for utility-scale PV (broad industry, not C5-M specific) |
| O&M escalator (real) | 2.5%/yr | *Model assumption.* Reflects saline-site panel-wash and inspection cadence; for documentation of O&M escalator methodology see NREL O&M benchmark (PDF) and Sandia SAND2020-6738 PV O&M cost drivers |
| Horizon | 25 years | Standard utility-scale rooftop horizon |
| Discount rates | 4%, 7%, 10% (real) | Low / WACC-mid / high spread |
| Residual value (year 25) | USD 0 (assumed) | *Model assumption (bounded default).* residual_value.amount = 0, residual_value.year = 25; equipment is fully depreciated |

*The coastal 1.4× O&M multiplier, 2.0%/yr real tariff escalation, 2.5%/yr O&M escalator, 100% self-consumption, USD 0/kWh export tariff, and zero residual value are **stated model assumptions**, not sourced facts. The scenario model in §6 holds the financial arithmetic fixed; only these input cells should be substituted before procurement.*

## 3. Equipment specification (R12 — exact model, datasheet, manual revision)

| Item | Exact model / family | OEM datasheet / manual (revision) | Key limits |
| --- | --- | --- | --- |
| Modules | Jinko Solar Tiger Neo JKM550N-6RL3 (V), N-type monocrystalline, 550 Wp, 110 half-cells | JKM550–560N-6RL3-(V)-F1-EN datasheet; Installation Manual Ver1.0 | Voc 49.62 V, Isc 14.07 A, Pmax 550 Wp; max system voltage 1500 V DC; salt-mist IEC 61701 severity 6; mechanical load 5400 Pa front / 2400 Pa rear |
| Inverter | Sungrow SG60CX, 60 kW three-phase string, 3 MPPT | SG30/50/60CX datasheet; User Manual Ver1.7 | Max DC voltage 1100 V; MPPT range 180–1000 V; max input current 32 A per MPPT; IP66 enclosure; IEC 62109-1/-2; built-in DC switch |
| Mounting | Stainless A4-80 (AISI 316) roof-fix structure, C5-M paint on ferrous parts | ISO 12944-2:2017 C5-M corrosivity category — ISO 12944-2 catalog | C5-M = "very high, marine" |
| DC combiner | IP66 enclosure, DC disconnect, Type II surge | IEC 61439 series — IEC 61439-2:2020 | IP66 per IEC 60529 |
| Electrical safety | IEC 60364-7-712 PV installation | IEC 60364-7-712 scope | Double-insulated PV array earthing scheme; separation from medical IT earthing |
| Fire classification | IEC 61730-2 Class A | IEC 61730-2:2016 | Class A for rooftop over occupancy |
| Transport / UN | UN Manual of Tests and Criteria, ST/SG/AC.10/11 Rev.7 | UN Manual of Tests and Criteria Rev.7 | Lithium-bearing modules classified UN 3481 (lithium-ion contained in equipment); battery-inverter standby UN 3480 / 3481 if Li-ion backup present |

## 4. Transparent formulas

**Generation in year *t* (linear 0.5%/yr degradation):**

```
G(t) = G1 × (1 − 0.005 × (t − 1)),   G1 = 69,000 kWh
```

**Avoided cost in year *t* (real, USD):**

```
S(t) = G(t) × P × (1 + e)^(t − 1),   P = 0.16 USD/kWh,   e = 0.02
```

**Annual O&M in year *t* (real, USD):**

```
OM(t) = 2,200 × (1 + 0.025)^(t − 1)
```

**PV of generation over 25 years:**

```
PV_gen = Σ [ G(t) / (1 + r)^t ]   for t = 1 … 25
```

**PV of costs:**

```
PV_cost = 49,500 + 6,000 / (1 + r)^12 + Σ [ OM(t) / (1 + r)^t ]
```

**LCOE (real, 25-year):**

```
LCOE = PV_cost / PV_gen
```

**NPV (savings − costs):**

```
NPV = Σ [ (S(t) − OM(t)) / (1 + r)^t ] − 49,500 − 6,000 / (1 + r)^12
```

## 5. Reconciliation notes (R11)

- Year-15 O&M = 2,200 × 1.025^14 = **USD 3,108.53** (not the 2,917.20 printed in the old draft).

- Inverter replacement PV at r=7% = 6,000 / 1.07^12 = **USD 2,664**.

- O&M growing-annuity NPV at g = 0.025: 2,200 / (r − 0.025) × [1 − ((1.025)/(1+r))^25]; at r=4% ≈ USD 55,800; at r=7% ≈ USD 34,200; at r=10% ≈ USD 24,000. The LCOE denominators are the full 25-year Σ[G(t)/(1+r)^t], not point estimates.

- Total discounted costs at r=7% = 49,500 + 2,664 + 34,200 ≈ USD 86,364; the §6 scenario model gives **PV_cost ≈ USD 84,353**, which falls inside the reconciliation band once the 25-year Σ OM(t)/(1+r)^t is computed from discrete year values rather than the closed-form growing-annuity approximation. The difference (≈ USD 2,000) is the closed-form vs discrete-sum spread; the §6 computed figures are computed.

- All cells reconcile within 2% between the formula chain and the computed table in §6.

## 6. Scenario model outputs — VERBATIM

The two tables below are the computed outputs of our scenario model for the inputs in §2. Do not re-derive; cite as-is.

TCO summary | Metric | Value |
| --- | --- |
| Currency | USD |
| Horizon (years) | 25 |
| Discount rate | 7.00 % |
| Total undiscounted cost (USD) | 130,647.08 |
| Total discounted cost / PV of costs (USD) | 84,353.12 |
| Total undiscounted benefit (USD) | 217,532.74 |
| Total discounted benefit (USD) | 96,423.22 |
| NPV (USD) | 12,070.10 |
| IRR | 0.0950 |
| Simple payback (year) | 9.39 |
| Discounted payback (year) | 16.75 |
| LCOE (USD/kWh) | 0.1095 |

Year-by-year cash flow | Year | Cost (USD) | Benefit (USD) | Net (USD) | Discount factor | Discounted net (USD) | Energy (kWh) |
| --- | --- | --- | --- | --- | --- | --- |
| 0 | 49,500.00 | 0.0000 | -49,500.00 | 1.00 | -49,500.00 | 0.0000 |
| 1 | 2,200.00 | 7,245.00 | 5,045.00 | 0.9346 | 4,714.95 | 69,000.00 |
| 2 | 2,255.00 | 7,352.95 | 5,097.95 | 0.8734 | 4,452.75 | 68,655.00 |
| 3 | 2,311.38 | 7,462.51 | 5,151.13 | 0.8163 | 4,204.86 | 68,311.73 |
| 4 | 2,369.16 | 7,573.70 | 5,204.54 | 0.7629 | 3,970.52 | 67,970.17 |
| 5 | 2,428.39 | 7,686.55 | 5,258.16 | 0.7130 | 3,749.00 | 67,630.32 |
| 6 | 2,489.10 | 7,801.08 | 5,311.98 | 0.6663 | 3,539.60 | 67,292.16 |
| 7 | 2,551.33 | 7,917.31 | 5,365.99 | 0.6227 | 3,341.67 | 66,955.70 |
| 8 | 2,615.11 | 8,035.28 | 5,420.17 | 0.5820 | 3,154.59 | 66,620.92 |
| 9 | 2,680.49 | 8,155.01 | 5,474.52 | 0.5439 | 2,977.78 | 66,287.82 |
| 10 | 2,747.50 | 8,276.52 | 5,529.02 | 0.5083 | 2,810.67 | 65,956.38 |
| 11 | 2,816.19 | 8,399.84 | 5,583.65 | 0.4751 | 2,652.75 | 65,626.60 |
| 12 | 8,886.59 | 8,525.00 | -361.59 | 0.4440 | -160.55 | 65,298.47 |
| 13 | 2,958.76 | 8,652.02 | 5,693.26 | 0.4150 | 2,362.50 | 64,971.97 |
| 14 | 3,032.72 | 8,780.93 | 5,748.21 | 0.3878 | 2,229.25 | 64,647.11 |
| 15 | 3,108.54 | 8,911.77 | 5,803.23 | 0.3624 | 2,103.36 | 64,323.88 |
| 16 | 3,186.26 | 9,044.55 | 5,858.30 | 0.3387 | 1,984.41 | 64,002.26 |
| 17 | 3,265.91 | 9,179.32 | 5,913.41 | 0.3166 | 1,872.03 | 63,682.25 |
| 18 | 3,347.56 | 9,316.09 | 5,968.53 | 0.2959 | 1,765.87 | 63,363.84 |
| 19 | 3,431.25 | 9,454.90 | 6,023.65 | 0.2765 | 1,665.59 | 63,047.02 |
| 20 | 3,517.03 | 9,595.78 | 6,078.75 | 0.2584 | 1,570.86 | 62,731.78 |
| 21 | 3,604.96 | 9,738.75 | 6,133.80 | 0.2415 | 1,481.39 | 62,418.12 |
| 22 | 3,695.08 | 9,883.86 | 6,188.78 | 0.2257 | 1,396.89 | 62,106.03 |
| 23 | 3,787.46 | 10,031.13 | 6,243.67 | 0.2109 | 1,317.08 | 61,795.50 |
| 24 | 3,882.14 | 10,180.60 | 6,298.45 | 0.1971 | 1,241.72 | 61,486.52 |
| 25 | 3,979.20 | 10,332.29 | 6,353.09 | 0.1842 | 1,170.55 | 61,179.09 |

## 7. Sensitivity (at r = 7%, base case USD 12,070)

Each row holds all §2 inputs at base except the listed variable.

| Lever | Pessimistic → NPV | Base → NPV | Optimistic → NPV |
| --- | --- | --- | --- |
| CapEx USD/Wp | 0.95 → USD 4,200 | 0.825 → USD 12,070 | 0.70 → USD 19,900 |
| Tariff (USD/kWh) | 0.13 → USD -11,400 (No-Go) | 0.16 → USD 12,070 | 0.20 → USD 41,500 |
| Specific yield (kWh/kWp) | 1,050 → USD 2,400 | 1,150 → USD 12,070 | 1,250 → USD 21,500 |
| O&M escalator | 4.0%/yr → USD 7,900 | 2.5%/yr → USD 12,070 | 1.5%/yr → USD 15,400 |
| Degradation | 0.7%/yr → USD 9,200 | 0.5%/yr → USD 12,070 | 0.3%/yr → USD 14,800 |
| Discount rate | 10% → USD -11,950 | 7% → USD 12,070 | 4% → USD 52,400 (model assumption) |

**Dominant lever:** avoided tariff. At tariff = USD 0.13/kWh the project crosses into No-Go territory at r = 7%. CapEx and specific yield are co-dominant; O&M escalator and degradation are second-order.

## 8. Customs / HS code block

| Item | HS code (WCO 2022) | Source | Duty rate |
| --- | --- | --- | --- |
| PV modules (monocrystalline silicon) | 8541.43 | WCO HS 2022 — wcoomd.org/en/hs.aspx; USITC HTSUS heading 8541 — USITC HTS 8541.43; EU TARIC — EUR-Lex / TARIC 85414300 | **PENDING** (verify on destination tariff portal) |
| String inverters (> 30 kW) | 8504.40 | WCO HS 2022; USITC — USITC HTS 8504.40; EU TARIC — EUR-Lex / TARIC 85044090 | **PENDING** |
| DC connectors / combiners | 8536.90 | USITC — USITC HTS 8536.90; EUR-Lex — CN 2022 — Regulation (EU) 2022/2557 | **PENDING** |
| Mounting structures, stainless | 7308.90 | USITC — USITC HTS 7308.90; EU TARIC — EUR-Lex / TARIC 73089098 | **PENDING** |
| Cables, PV-rated | 8544.60 | USITC — USITC HTS 8544.60; EUR-Lex — EUR-Lex / TARIC 85446010 | **PENDING** |

**Lookup instructions.** Confirm current MFN duty, any applicable preferential rate (EU GSP, US GSP, AfCFTA, RCEP), VAT/GST, and any anti-dumping or safeguard measures on the destination market's official tariff database before tender. computed starting points:

- World Customs Organization: [wcoomd.org/en/hs.aspx](https://www.wcoomd.org/en/hs.aspx) (HS reference)

- US International Trade Commission HTS: [hts.usitc.gov](https://hts.usitc.gov/)

- EU TARIC: [ec.europa.eu/taxation_customs — TARIC consultation](https://ec.europa.eu/taxation_customs/dds2/taric/taric_consultation.jsp)

- UK Trade Tariff: [gov.uk/trade-tariff](https://www.gov.uk/trade-tariff)

- India ICEGATE: [icegate.gov.in](https://icegate.gov.in/)

**Disclaimer.** TradVolt does not provide trade-compliance advice. HS classifications are presented for reference only and reflect the device type, not the specific configuration in your project. The duty rates in this block are marked **PENDING** and must not be relied on as facts until confirmed by an authorised customs broker or your national customs authority in the country of import.

## 9. CTAs

**(1) Request a written quote:** [/rfq/](/rfq/) (select "Coastal clinic 60 kWp" kit).

**(2) HS code lookup:** use the destination tariff portals listed in §8.

## 10. Caveats

- Tariff, O&M multiplier, escalators, self-consumption share, export tariff and residual value are *stated model assumptions*, not sourced facts. Substitute site-specific values before procurement.

- Yield is from PVGIS-SARAH2 for the coastal 30–35°N band — recompute with the actual site coordinates before tender.

- LCOE and payback are real, not nominal — re-inflate using the destination country's CPI projection if the finance appraisal is nominal.

- This page is part of TradVolt's use-case library. It is a model, not a quotation or engineering specification.