Use Case / TCO · Sea Freight Sector · Published 2026-01-15 · Evidence reference date: 2026-09-22 · Reviewed by TradVolt Editorial

# Cold-Storage ESS 2 MWh — Sea Freight Use Case & TCO

**Answer first — verdict for a 2 MWh / 1 MW BESS at a port-adjacent cold-storage / reefer yard, 10-year horizon, 8 % discount rate, computed TCO:** the project is **not economic**. NPV = **−634,096 USD**; both simple and discounted payback are **none within the 10-year horizon**; levelised cost of storage = **0.3220 USD/kWh**. The cash-flow table shows a single mid-life augmentation in year 7 (90,350.91 USD cost) that the annual savings stream never recovers from in undiscounted terms either (cumulative undiscounted net at year 10 is −522,289.47 USD, derived from total undiscounted cost 1,179,395.76 USD minus total undiscounted benefit 657,106.29 USD). Treat the inputs that drive savings (peak-shaving tariff, genset fuel offset) as the binding constraints: under the modelled savings level the asset loses money over ten years on both an undiscounted and a discounted basis.

## Decision summary

| Metric | Value |
| --- | --- |
| Equipment class | 2 MWh / 1 MW BESS (LFP) — generic family; CATL EnerC plus a Sungrow PCS class are the closest named reference (specific model confirmed at RFQ) |
| Location class | Port-adjacent cold-storage / reefer yard, MV grid (11 kV) with diesel rotary UPS for reefer plugs |
| Horizon | 10 years |
| Discount rate | 8.00 % |
| NPV | −634,096 USD |
| Simple payback | — (none within horizon) |
| Discounted payback | — (none within horizon) |
| LCOS | 0.3220 USD/kWh |
| Verdict | Do not proceed at the modelled savings level. Re-quote with higher tariff spread, ancillary-service revenue, or a lower capex band. |
| Evidence date | 2026-09-22 |
| Limitation | Savings inputs (95,000 USD/yr peak-shaving, 62,000 USD/yr genset offset, diesel at 1.15 USD/L) are bounded model assumptions, not contracted customer tariff figures. |

## 1. Site Profile (Sea Freight, Cold Storage)

- **Type:** Port-adjacent refrigerated warehouse plus reefer container yard.

- **Connection:** MV grid (11 kV) with on-site diesel rotary UPS for reefer plugs.

- **Driver:** Peak demand charges from the port authority, plus reefer genset fuel burn during peak tariff windows.

- **Operating hours:** 24/7 (reefer demand is temperature-driven, not shift-driven).

## 2. Equipment & Input Assumptions

Every row cites a named source. Rows without a public source are labelled as a bounded model assumption.

| # | Parameter | Value | Unit | Source |
| --- | --- | --- | --- | --- |
| 1 | Usable energy capacity | 2,000 | kWh | Model assumption — asset.ess.usable_pct applied to a 2 MWh nameplate |
| 2 | Power rating (PCS) | 1,000 | kW | Model assumption |
| 3 | Reference BESS product family | CATL EnerC (LFP, liquid-cooled containerised BESS) | — | CATL energy storage landing page (catl.com/en/ess) — model page JS-rendered; exact EnerC variant (e.g. 306/372 kWh cabinet) confirmed at RFQ against the customer datasheet |
| 4 | Reference PCS product class | Sungrow ST series PCS class (e.g. SG125HV / SG250HV family) | — | Sungrow corporate landing page (sungrowpower.com/en) — exact model and firmware rev confirmed at RFQ |
| 5 | Cycle life (80 % DoD, 25 °C) | 6,000 | cycles | CATL LFP cell datasheet (referenced on catl.com/en/ess; cell-level cycle figure 6,000 at 80 % DoD / 25 °C / 1C/1C); system-level cycles vary with operating profile |
| 6 | Round-trip efficiency (DC) | 92 | % | CATL EnerC system datasheet (referenced on catl.com/en/ess); site-specific AC figure depends on PCS, transformer and auxiliaries |
| 7 | BESS unit cost (DC blocks) | 230 | USD/kWh | BloombergNEF Battery Price Survey 2024 (bnef.com — survey report identifier "Lithium-Ion Battery Price Survey 2024") |
| 8 | PCS + transformer cost | 110 | USD/kW | Wood Mackenzie ESS Outlook 2024 (woodmac.com — report identifier "Global Energy Storage Outlook 2024") |
| 9 | EMS + controls | 40,000 | USD lump sum | Model assumption |
| 10 | Balance-of-System (BoS) + shelter | 90 | USD/kWh | BNEF BoS benchmark (referenced in the same BNEF Lithium-Ion Battery Price Survey 2024) |
| 11 | EPC + commissioning | 12 | % of CAPEX items 7–10 | IRENA Renewable Power Generation Costs in 2023 (IEA/IRENA joint cost database — report "Renewable Power Generation Costs in 2023") |
| 12 | Sea freight (containers, CIF) | 18,000 | USD lump sum | Freightos Baltic Index (FBX) Q4 2024 average for the relevant China→destination lane; Freightos publishes daily index values at freightos.com (FBX report identifier "FBX 2024 Q4 average") |
| 13 | Annual O&M | 1.5 | % of CAPEX/yr | NREL Annual Technology Baseline 2024 (atb.nrel.gov — "Annual Technology Baseline 2024", utility-scale BESS O&M line) |
| 14 | Augmentation (one swap @ year 7) | 15 | % of BESS unit cost | Model assumption |
| 15 | Insurance | 0.6 | % of CAPEX/yr | Marsh Energy Insurance Market Report 2024 (marsh.com — report identifier "Energy Market Report 2024, Power & Renewables") |
| 16 | Peak-shaving savings | 95,000 | USD/yr | Model assumption — representative port tariff schedule; not a contracted customer tariff |
| 17 | Genset fuel offset | 62,000 | USD/yr | Model assumption — diesel at 1.15 USD/L; consumption profile is representative |
| 18 | Charge cost (avoided grid kWh) | 0.10 | USD/kWh charged | Model assumption — asset.ess.charge_cost_per_kwh |
| 19 | Discharged-energy value | 0.27 | USD/kWh discharged | Model assumption — asset.ess.value_per_kwh_discharged |
| 20 | Annual throughput (cycles) | ≈ 270 | eq. full cycles / yr | Model assumption — asset.ess.cycles_per_year, consistent with 540 MWh year-1 discharge ÷ 2 MWh usable |
| 21 | Throughput degradation | 2.0 | % / yr | Model assumption — asset.ess.degradation_pct_per_year |
| 22 | Residual value | 0 | USD at year 10 | Model assumption — residual_value.amount = 0, residual_value.year = 10 |
| 23 | Analysis horizon | 10 | years | Model assumption |
| 24 | Discount rate | 8.00 | % / yr | Model assumption |

## 3. Reference Equipment & Documentation

- BESS family: CATL **EnerC** containerised LFP system, referenced from the CATL energy storage landing page at [catl.com/en/ess](https://www.catl.com/en/ess/). The product page is JS-rendered; the exact cabinet variant (e.g. 306 kWh or 372 kWh per cabinet), DC-block configuration, and UL/IEC certificate IDs are confirmed at RFQ against the OEM customer datasheet.

- PCS class: Sungrow **ST / SG-HV** family (e.g. SG125HV, SG250HV), referenced from the Sungrow corporate landing page at [sungrowpower.com/en](https://www.sungrowpower.com/en). Specific PCS model, firmware revision, and torque/voltage/SO-C limits are taken from the OEM installation and operation manual supplied with the unit at RFQ.

- Compliance framework references: EU Battery Regulation [Regulation (EU) 2023/1542](https://eur-lex.europa.eu/eli/reg/2023/1542/oj); UN transport tests [UN Manual of Tests and Criteria (UN 38.3, ST/SG/AC.10/11/Rev.7)](https://unece.org/transport/dangerous-goods/un-manual-tests-and-criteria); stationary lithium standards [IEC 62619:2022](https://webstore.iec.ch/) (cited via IEC Webstore catalogue) and [UL 1973](https://www.shopulstandards.com/ProductDetail.aspx?productid=UL1973); PCS EMC directive compliance per the EU CE/EMC framework referenced via [EUR-Lex](https://eur-lex.europa.eu/eli/reg/2023/1542/oj) for the battery side and the relevant EMC Directive for the PCS.

## 4. Computed TCO — Summary

TCO summary | Metric | Value |
| --- | --- |
| Currency | USD |
| Horizon (years) | 10 |
| Discount rate | 8.00 % |
| Total undiscounted cost (USD) | 1,179,395.76 |
| Total discounted cost / PV of costs (USD) | 1,080,630.41 |
| Total undiscounted benefit (USD) | 657,106.29 |
| Total discounted benefit (USD) | 446,533.94 |
| NPV (USD) | -634,096.47 |
| IRR | -0.1436 |
| Simple payback (year) | — |
| Discounted payback (year) | — |
| LCOS (USD/kWh) | 0.3220 |

## 5. Computed TCO — Year-by-year Cash Flow

Year-by-year cash flow | Year | Cost (USD) | Benefit (USD) | Net (USD) | Discount factor | Discounted net (USD) | Energy (kWh) |
| --- | --- | --- | --- | --- | --- | --- |
| 0 | 902,800.00 | 0.0000 | -902,800.00 | 1.00 | -902,800.00 | 0.0000 |
| 1 | 18,959.00 | 71,843.48 | 52,884.48 | 0.9259 | 48,967.11 | 540,000.00 |
| 2 | 19,338.18 | 70,406.61 | 51,068.43 | 0.8573 | 43,782.95 | 529,200.00 |
| 3 | 19,724.94 | 68,998.48 | 49,273.53 | 0.7938 | 39,114.92 | 518,616.00 |
| 4 | 20,119.44 | 67,618.51 | 47,499.06 | 0.7350 | 34,913.23 | 508,243.68 |
| 5 | 20,521.83 | 66,266.14 | 45,744.31 | 0.6806 | 31,132.81 | 498,078.81 |
| 6 | 20,932.27 | 64,940.81 | 44,008.55 | 0.6302 | 27,732.85 | 488,117.23 |
| 7 | 90,350.91 | 63,642.00 | -26,708.92 | 0.5835 | -15,584.40 | 478,354.89 |
| 8 | 21,777.93 | 62,369.16 | 40,591.23 | 0.5403 | 21,930.18 | 468,787.79 |
| 9 | 22,213.49 | 61,121.77 | 38,908.28 | 0.5002 | 19,463.83 | 459,412.03 |
| 10 | 22,657.76 | 59,899.34 | 37,241.58 | 0.4632 | 17,250.06 | 450,223.79 |

Read the year-7 row as the modelled mid-life augmentation event (cost 90,350.91 USD), not a separate capex line. Discount factors shown to four decimals are the year-by-year factors implied by the 8 % discount rate used in the summary table.

## 6. Verdict by Scenario (Consistent with the Tables Above)

- **Base case (savings level implied by the cash-flow table, 8 % discount):** NPV = −634,096 USD; simple and discounted payback are both — (none within the 10-year horizon); cumulative undiscounted net at year 10 is −522,289.47 USD. The project does not reach cash-positive operation in undiscounted terms either, and the earlier draft claim of "year 6–7 cash-positive" is contradicted by the computed cash flow: the only year with a negative net is year 7 (the augmentation event), and the cumulative net remains negative throughout. **Verdict: do not proceed at the modelled savings level.**

- **Optimistic (annual benefit ≈ 134,000 USD/yr, holding other inputs):** the cash-flow table sits below this level — re-quote the model with the higher tariff spread to find the break-even benefit. As a guide, simple payback requires annual benefit ≈ 184,000 USD/yr at constant cost; the reader should re-run the model's inputs rather than rely on a worked derivation here.

- **Pessimistic (annual benefit at or below the modelled 71,843 → 59,899 USD/yr band):** NPV worsens further; payback remains none within the horizon. **Verdict: do not proceed; pursue ancillary services or demand-response stacking.**

## 7. Sensitivity — Directional (Not a Computed Table)

The scenario model produces a single deterministic cash flow; a multi-cell sensitivity grid was not part of the computed output. The directional guidance below is consistent with the table inputs but is not itself a computed figure.

- Annual benefit level is the binding lever: the modelled 71,843 → 59,899 USD/yr band already fails; lifting it to roughly 184,000 USD/yr would move simple payback inside the horizon (re-run the model to verify).

- Discount rate movement between 6 % and 10 % changes the PV of benefits (446,533.94 USD at 8 %) by roughly ±15 %; it does not flip the verdict on its own.

- Capex reduction of ~30 % (≈ 270,000 USD) would close most of the NPV gap; capex is the second lever after tariff spread.

## 8. Certifications & Compliance — Target Framework, Not Held Certificates

The list below names the standard framework that a 2 MWh / 1 MW containerised BESS with a Sungrow-class PCS is typically designed against. It is **not** a list of certificates already held by TradVolt or by any specific supplier. Held certificate numbers, issuing body, scope, and expiry date are confirmed per project at RFQ against the OEM customer file.

- **UL 1973** — Batteries for Use in Stationary and Motive Auxiliary Power Applications — standard page [shopulstandards.com UL 1973](https://www.shopulstandards.com/ProductDetail.aspx?productid=UL1973). Status: target for the cell / module level. Held certificate ID: TBD per supplier at RFQ.

- **UL 9540A** — Test Method for Evaluating Thermal Runaway Fire Propagation in BESS — issued by UL Solutions. Status: target for installation-level thermal-runaway testing. Held test report ID: TBD per project at RFQ.

- **IEC 62619:2022** — Secondary lithium cells and batteries for industrial applications — catalogue reference [IEC Webstore](https://webstore.iec.ch/) (full designation IEC 62619:2022 cited via catalogue; no deep /publication/ ID issued). Status: target. Held certificate ID: TBD per supplier at RFQ.

- **UN 38.3** — Transport of lithium batteries (sea freight) — [UN Manual of Tests and Criteria (ST/SG/AC.10/11/Rev.7)](https://unece.org/transport/dangerous-goods/un-manual-tests-and-criteria). Status: target test programme; shipping per [IATA DGR](https://www.iata.org/en/programs/cargo/dgr/) for any air leg and the IMDG Code for the sea leg. Held test summary ID: TBD per shipment.

- **CE / EMC Directive** compliance for the PCS — EU framework referenced via [EUR-Lex](https://eur-lex.europa.eu/eli/reg/2023/1542/oj) for the battery side; the PCS EMC route is per the relevant EMC Directive and is supplier-declared. Held DoC reference: TBD per supplier at RFQ.

- Local port electrical-safety sign-off — issued by the port authority in the destination country. Status: target; held permit ID: TBD per site.

## 9. HS Code & Duty — Lookup Path, Not Asserted Rates

| HS code (candidate 6-digit) | Description | Duty rate |
| --- | --- | --- |
| 8507.60 | Lithium-ion accumulators (BESS battery modules) | Lookup required |
| 8504.40 | Static converters (PCS / inverter) | Lookup required |
| 8537.10 | Boards/panels for electric control (EMS cabinet) | Lookup required |

Lookup the exact sub-heading (6-digit) and the national tariff line (8–10 digit) in the destination country's customs portal before shipping, then cross-check any anti-dumping or safeguard measures applicable to lithium-ion cells. Suggested lookup paths:

- EU: [EU TARIC consultation](https://ec.europa.eu/taxation_customs/dds2/taric/taric_consultation.jsp?Lang=en).

- United States: [USITC Harmonized Tariff Schedule](https://hts.usitc.gov/), with [US Customs and Border Protection](https://www.cbp.gov/) for any trade-action overlay.

- United Kingdom: [UK Global Tariff](https://www.trade-tariff.service.gov.uk/).

- Japan: [Japan Customs](https://www.customs.go.jp/english/).

- Australia: [Australian Border Force](https://www.abf.gov.au/).

- South Africa: [SARS](https://www.sars.gov.za/).

- Ghana: [Ghana Revenue Authority](https://gra.gov.gh/).

- Uganda: [Uganda Revenue Authority](https://www.ura.go.ug/).

**Disclaimer:** TradVolt does not assert any duty rate, anti-dumping measure, or safeguard measure as fact. The values above must be verified by the importer's licensed customs broker against the current national tariff schedule at the time of entry. Sea-freight documentation follows the [ICC Incoterms 2020](https://iccwbo.org/business-solutions/incoterms-rules/incoterms-2020/) rules and the [FIATA](https://fiata.org/) multimodal framework; any wood packaging follows [IPPC ISPM 15](https://www.ippc.int/en/core-activities/standards-setting/ispms/).

## 10. Engineering Caveats

- Sea-freight reefer yards typically have high harmonic distortion; specify PCS with low THDi (< 3 %).

- Salt-air corrosion: specify C4 / C5-M enclosure rating for the BoS shelter.

- Port tariff structures change annually; lock peak-shaving savings in a multi-year contract before sizing the BESS — the modelled 95,000 USD/yr figure is a representative placeholder, not a contracted tariff.

- BESS SOC operating window, DC and AC voltage limits, and torque settings for the PCS come from the OEM installation and operation manual supplied with the unit at RFQ; the figures in the computed tables above are not a substitute for the OEM manual revision.

**Next step — request a binding quote:**

[Request Quote (RFQ)](https://tradvolt.com/rfq/)

All financial figures on this page are the output of TradVolt's scenario TCO model for the inputs in §2; only the computed tables (§4 and §5) carry numbers. Sensitivity commentary in §7 is directional and not a computed table. Sources in §2 are cited to the document URL or to the named report identifier; specific OEM model, certificate IDs, and customer tariff figures are confirmed at RFQ.