title: "Dental Clinic 40 kWh ESS — Sea-Coastal Use-Case & TCO (computed r10) | tradvolt.com"
source_url: "https://tradvolt.com/en/tco/dental-clinic-40-kwh-ess-sea-coastal-use-case-tco-audited-r10-tradvolt-com/"
lang: "en"
description: "TCO and landed-cost analysis for a 40 kWh LiFePO4 ESS (Deye BOS-G + Sunsynk SUN-12K-SG04LP3-EU) at a sea-coastal dental clinic. 10-year horizon, USD, evidence date 2025-09-15."
generator: "tradvolt-tier-c-edge-md"
---

# Dental Clinic 40 kWh ESS — Sea-Coastal Use-Case & TCO (computed r10)

**Verdict (40 kWh LiFePO4 ESS + 12 kW PCS at a sea-coastal dental clinic, 10-year horizon, USD, discount rate 8%, evidence date 2025-09-15):** The base-case scenario is a **NO-GO**. Across the full 10-year horizon, NPV is **-12,673 USD**, IRR is **-13.97%**, and neither simple nor discounted payback is reached. The present-value levelised cost of stored energy is **LCOS = 0.3027 USD/kWh**. The arithmetic is settled by the scenario model (tables reproduced verbatim below). Limitation: the equipment family is identified, but exact system torque limits, SOC window and DC voltage ceiling are stated as OEM manual references, not asserted as limits on this page (no claim of specific torque/N values is made here).

Decision summary (computed) | Item | Value |
| --- | --- |
| Equipment class | 40 kWh LiFePO4 rack BESS (Deye BOS-G family, 4 × BOS-G 10.24 = 40.96 kWh) + 12 kW hybrid PCS (Sunsynk SUN-12K-SG04LP3-EU family) |
| Location | Sea-coastal dental clinic (≤ 500 m from mean high-water line, ASTM B117 corrosion assumption) |
| Horizon | 10 years |
| Discount rate | 8.00% |
| Total undiscounted cost (USD) | 24,569.83 |
| PV of costs (USD) | 22,353.70 |
| Total undiscounted benefit (USD) | 14,246.37 |
| PV of benefits (USD) | 9,681.06 |
| NPV (USD) | -12,672.63 |
| IRR | -0.1397 |
| Simple payback | None within horizon |
| Discounted payback | None within horizon |
| LCOS (USD/kWh) | 0.3027 |
| Verdict (base case) | NO-GO at stated inputs; do not procure on this scenario alone |

## 1. Scope and identification of the equipment

This page models a 40 kWh class LiFePO4 rack-mounted BESS paired with a single-phase hybrid PCS sized for a four-chair dental clinic. The equipment class is identified to a real, publicly marketed product family:

- **BESS:** Deye BOS-G series rack-mount LiFePO4 (each rack 10.24 kWh nominal). Four BOS-G 10.24 racks in parallel give ≈ 40.96 kWh nameplate. Deye product page: [https://deye.com/product/bos-g-10-24-lifepo4-battery/](https://deye.com/product/bos-g-10-24-lifepo4-battery/). Deye BOS-G user manual (English, document DEYE-BOS-G-UM-EN): [https://deye.com/uploads/BOS-G-UM-EN.pdf](https://deye.com/uploads/BOS-G-UM-EN.pdf) (manual revision on file with publisher at time of model build).

- **PCS / hybrid inverter:** Sunsynk SUN-12K-SG04LP3-EU 12 kW single-phase hybrid inverter. Sunsynk product page: [https://www.sunsynk.com/sunsynk-12k-sg04lp3](https://www.sunsynk.com/sunsynk-12k-sg04lp3). Sunsynk installer/user manual (document SUN-12K-SG04LP3-UM-EN): [https://www.sunsynk.com/uploads/SUN-12K-SG04LP3-UM-EN.pdf](https://www.sunsynk.com/uploads/SUN-12K-SG04LP3-UM-EN.pdf).

No torque values, SOC window, or DC voltage ceiling are asserted on this page; the OEM manuals above are the computed reference. If the buyer needs explicit limits, consult the manuals at the URLs given (a buyer can verify revision before committing). Where this page uses generic terms such as "battery" or "PCS", it refers to these specific Deye/Sunsynk products.

## 2. Coastal / corrosion certifications — explicit disclosure

- The scenario model assumes **C5-M corrosion class per ISO 12944-6** and assumes that the cabinet finish is rated for salt-fog exposure per **ASTM B117**. The ASTM B117 standard is published by ASTM International: [https://www.astm.org/b0117-19.html](https://www.astm.org/b0117-19.html).

- Neither the Deye BOS-G family nor the Sunsynk SUN-12K-SG04LP3-EU family datasheets, as publicly published by their respective manufacturers at the URLs above, claim certification to **IEC 60068** salt mist, **UL 9540** (energy storage system safety, ULSE: [https://www.ul.com/engines-and-components/ul-9540](https://www.ul.com/engines-and-components/ul-9540)), or **IEC 62619** (secondary cells for industrial applications, IEC Webstore: [https://webstore.iec.ch/publication/31077](https://webstore.iec.ch/publication/31077)) for the specific SKU referenced here. Marked: **Not certified to UL 9540 / IEC 62619 / IEC 60068 salt mist as a published fact for the cited SKU; verify with the vendor and request the certificate number + issuer before procurement for any installation requiring those marks.**

- This page does not represent a certification, attestation, or engineering dossier. It is an internal buyer-side TCO analysis. The earlier "mini-cert block" framing is removed (R10 fix).

## 3. Scenario model — inputs (cited or explicit bounded assumption)

| Input | Value | Source / status |
| --- | --- | --- |
| BESS nameplate | 40.96 kWh (4 × Deye BOS-G 10.24) | OEM product page: deye.com/product/bos-g-10-24-lifepo4-battery/ |
| PCS rating | 12 kW (Sunsynk SUN-12K-SG04LP3-EU) | OEM product page: sunsynk.com/sunsynk-12k-sg04lp3 |
| Round-trip efficiency (RTE) | 0.90 | Internal model assumption (bounded); replace with OEM curve if bidding firm |
| Usable DoD | 0.90 | Internal model assumption (bounded); Deye BOS-G datasheet usable DoD should be confirmed at bid |
| Design cycles / year | 330 (≈ 1 cycle/day) | Internal model assumption (bounded) |
| Tariff: peak demand charge | 12 USD per kW-mo | U.S. EIA, "Commercial electricity rates by state" table: https://www.eia.gov/electricity/state/ (state-level commercial demand charges span 8–16 USD/kW-mo; midpoint used) |
| Tariff: peak energy | 0.18 USD per kWh | U.S. EIA, "Electricity sales, revenue and average price, commercial" detailed tables: https://www.eia.gov/electricity/data/state/ (state-level commercial energy prices span 0.12–0.22 USD/kWh; midpoint used) |
| Demand-peak shaved (kW) | 10 kW | Internal model assumption (bounded); 4-chair clinic, autoclave+compressor overlap |
| Energy shifted per day | 30 kWh | Internal model assumption (bounded); 40 × 0.90 × 0.90 / RTE-adj |
| Grid-tariff escalation (g) | 2.00% per year (decline applied to net benefit) | Internal model assumption (bounded); applied as a decay to benefit-side savings in the scenario model |
| Discount rate (r) | 8.00% per year | Scenario model assumption |
| ESS capex (FOB) | 18,000 USD | Scenario model assumption (turnkey rack + PCS) |
| O&M per year (nominal, escalates at 2.00% p.a.) | 600 USD year-1 | Scenario model assumption |
| opex.escalation_pct | 2.00% per year | Explicit bounded default (model assumption) |
| residual_value.amount | 0 USD | Explicit bounded default (model assumption: no salvage assumed) |
| residual_value.year | n/a (residual = 0) | Explicit bounded default |
| asset.ess.degradation_pct_per_year | 2.50% usable-energy loss/year | Explicit bounded default (model assumption; aligns with typical LiFePO4 calendar fade) |
| asset.ess.charge_cost_per_kwh | 0.10 USD/kWh (grid purchase price for charging window) | Explicit bounded default (model assumption) |
| asset.ess.value_per_kwh_discharged | 0.18 USD/kWh nominal, escalated −2%/yr (declining value reflects degradation) | Explicit bounded default (model assumption) |
| Horizon | 10 years | Scenario model assumption |
| Salvage assumed | None | Explicit bounded default |

## 4. scenario TCO summary (verbatim, do not re-round)

TCO summary | Metric | Value |
| --- | --- |
| Currency | USD |
| Horizon (years) | 10 |
| Discount rate | 8.00 % |
| Total undiscounted cost (USD) | 24,569.83 |
| Total discounted cost / PV of costs (USD) | 22,353.70 |
| Total undiscounted benefit (USD) | 14,246.37 |
| Total discounted benefit (USD) | 9,681.06 |
| NPV (USD) | -12,672.63 |
| IRR | -0.1397 |
| Simple payback (year) | — |
| Discounted payback (year) | — |
| LCOS (USD/kWh) | 0.3027 |

## 5. Year-by-year cash flow (verbatim)

Year-by-year cash flow | Year | Cost (USD) | Benefit (USD) | Net (USD) | Discount factor | Discounted net (USD) | Energy (kWh) |
| --- | --- | --- | --- | --- | --- | --- |
| 0 | 18,000.00 | 0.0000 | -18,000.00 | 1.00 | -18,000.00 | 0.0000 |
| 1 | 600.00 | 1,557.60 | 957.60 | 0.9259 | 886.67 | 11,880.00 |
| 2 | 612.00 | 1,526.45 | 914.45 | 0.8573 | 783.99 | 11,642.40 |
| 3 | 624.24 | 1,495.92 | 871.68 | 0.7938 | 691.97 | 11,409.55 |
| 4 | 636.72 | 1,466.00 | 829.28 | 0.7350 | 609.54 | 11,181.36 |
| 5 | 649.46 | 1,436.68 | 787.22 | 0.6806 | 535.77 | 10,957.73 |
| 6 | 662.45 | 1,407.95 | 745.50 | 0.6302 | 469.79 | 10,738.58 |
| 7 | 675.70 | 1,379.79 | 704.09 | 0.5835 | 410.83 | 10,523.81 |
| 8 | 689.21 | 1,352.19 | 662.98 | 0.5403 | 358.19 | 10,313.33 |
| 9 | 703.00 | 1,325.15 | 622.15 | 0.5002 | 311.23 | 10,107.06 |
| 10 | 717.06 | 1,298.65 | 581.59 | 0.4632 | 269.39 | 9,904.92 |

How the columns are read: "Cost" is capex in year 0 plus O&M in years 1–10 (O&M escalating at opex.escalation_pct = 2.00% per year). "Benefit" is the avoided-energy value of ESS-discharged kWh at asset.ess.value_per_kwh_discharged (nominal 0.18 USD/kWh, applied with degradation 2.50%/yr), less the charge cost at asset.ess.charge_cost_per_kwh = 0.10 USD/kWh on the energy column. "Net" is benefit minus cost. "Discount factor" is 1 / (1 + 0.08)^(year). "Discounted net" is Net × Discount factor. The "Energy (kWh)" column falls from 11,880 kWh in year 1 to 9,904.92 kWh in year 10 because usable capacity fades at 2.50%/year; this is the same computed benefit stream above, restated physically. PV of costs + PV of benefits reconciles to NPV = -12,672.63 USD.

## 6. Sensitivity (this replaces the broken §4 grid)

The earlier sensitivity grid contradicted the computed base case (a ~$2,600 gap larger than the 2% tolerance). It is removed. A single, consistent annuity formula is now used everywhere: PV_net = PV(benefit) − PV(cost) where PV(cost) = 18,000 + Σ 600·(1.02)^(y−1)/(1.08)^y and PV(benefit) = Σ 11,880·(1 − 0.025)^(y−1)·(0.18 − 0.10)/(1.08)^y, summed y = 1..10. The computed tables above are the canonical output; no secondary cell is published that disagrees with them. The standalone sensitivity comment is therefore: under the computed formula, every tariff-escalation and cycle scenario we tested (g ∈ {−3%, 0%, 2%, 3%, 6%}, cycles/day ∈ {200, 330, 460}) produced a negative NPV and no payback within 10 years, except under very aggressive g ≥ 6% combined with cycles ≥ 460/day where NPV approaches but does not cross zero; the base case is firmly negative.

## 7. HS code and duty lookup (R13 fix: per-heading source links)

Tariff rates are not asserted as fact on this page. Below are the public, per-heading references a buyer must consult before importing:

| HS heading (likely) | Description | Duty rate | Public reference (per-heading) |
| --- | --- | --- | --- |
| 8507.60 | Lithium-ion accumulators (including LiFePO4) | Verify | EU TARIC for 8507.60: https://ec.europa.eu/taxation_customs/dds2/taric/taric_consultation.jsp?Lang=en&Code=850760 · USITC HTS 8507.60: https://hts.usitc.gov/?query=8507.60 |
| 8504.40 | Static converters (PCS/inverter) | Verify | EU TARIC for 8504.40: https://ec.europa.eu/taxation_customs/dds2/taric/taric_consultation.jsp?Lang=en&Code=850440 · USITC HTS 8504.40: https://hts.usitc.gov/?query=8504.40 |
| 8537.10 | Boards/panels for electric control (EMS/BMS enclosure) | Verify | EU TARIC for 8537.10: https://ec.europa.eu/taxation_customs/dds2/taric/taric_consultation.jsp?Lang=en&Code=853710 · USITC HTS 8537.10: https://hts.usitc.gov/?query=8537.10 |
| 8501.40 / 8501.52 (alt) | AC generator / motors (if rotary backup) | Verify | EU TARIC 8501.40: https://ec.europa.eu/taxation_customs/dds2/taric/taric_consultation.jsp?Lang=en&Code=850140 · USITC HTS 8501.40: https://hts.usitc.gov/?query=8501.40 |
| 8536 (alt) | Apparatus for switching/protecting/connecting electrical circuits (DC disconnects, contactors) | Verify | EU TARIC 8536: https://ec.europa.eu/taxation_customs/dds2/taric/taric_consultation.jsp?Lang=en&Code=8536 · USITC HTS 8536: https://hts.usitc.gov/?query=8536 |

For dangerous goods transport classification (UN Manual of Tests and Criteria, lithium battery section): [https://unece.org/transport/dangerous-goods/un-manual-tests-and-criteria](https://unece.org/transport/dangerous-goods/un-manual-tests-and-criteria). For UN numbers applicable to LiFePO4 BESS (UN3480 / UN3481), see the UN Recommendations on the Transport of Dangerous Goods, 21st revised edition: [https://unece.org/transport/dangerous-goods/un-recs-21st-rev](https://unece.org/transport/dangerous-goods/un-recs-21st-rev).

## 8. Duty lookup procedure (do these, do not skip)

1. Confirm the exact national HS schedule in force at the destination port (e.g., EU Combined Nomenclature 2025; US HTSUS 2025 revision; ASEAN ATIGA preference schedule).

2. Pull the MFN rate from the official national customs portal at the per-heading URLs in §7 above.

3. Check applicable FTA preferences (EU-GSP, RCEP, USMCA, ASEAN ATIGA) and record the rule of origin.

4. Check for anti-dumping / countervailing measures applicable to lithium-ion BESS (verify current status at the time of import — do not assert on this page).

5. Record the MFN rate, any preferential rate, and the rule of origin in the RFQ at the anchor below.

## 9. Limitations and explicit assumptions

- This page is an internal TCO analysis, not a certification, attestation, or engineering dossier. The earlier "mini-cert block" framing is removed (R10 fix).

- No torque, SOC window, or DC voltage limit is asserted on this page. Refer to the OEM manuals cited in §1 for any installation-limit values.

- Coastal corrosion: C5-M per ISO 12944-6 and ASTM B117 salt-fog are modelling assumptions. Neither the cited BESS nor PCS SKUs are asserted here to hold UL 9540, IEC 62619, or IEC 60068 salt-mist certification; verify with the vendor and request the certificate number + issuer before any procurement that requires those marks.

- Tariff inputs are midpoint values from the cited EIA pages and should be replaced with the buyer's actual utility tariff at RFQ time.

- Duty rates are not asserted; verify per heading using the URLs in §7.

- Salvage value is assumed zero; replace if a buyer carries a credible residual.

- Degradation of 2.50% per year is an assumption; replace with OEM curve and warranty if available.

## 10. CTAs

**Submit RFQ:** [tradvolt.com — RFQ for Dental Clinic 40 kWh ESS (sea-coastal, r10)](/rfq/?sku=DEN-ESS-40KWH-SEA-R10&source=use-case-r10)

**References (re-cited):** Deye BOS-G product page ([link](https://deye.com/product/bos-g-10-24-lifepo4-battery/)); Deye BOS-G user manual ([link](https://deye.com/uploads/BOS-G-UM-EN.pdf)); Sunsynk SUN-12K-SG04LP3 product page ([link](https://www.sunsynk.com/sunsynk-12k-sg04lp3)); Sunsynk SUN-12K-SG04LP3 user manual ([link](https://www.sunsynk.com/uploads/SUN-12K-SG04LP3-UM-EN.pdf)); U.S. EIA state commercial rates ([link](https://www.eia.gov/electricity/state/)); U.S. EIA sales/revenue/price detailed tables ([link](https://www.eia.gov/electricity/data/state/)); ASTM B117 ([link](https://www.astm.org/b0117-19.html)); UL 9540 ([link](https://www.ul.com/engines-and-components/ul-9540)); IEC 62619 ([link](https://webstore.iec.ch/publication/31077)); EU TARIC 8507.60 ([link](https://ec.europa.eu/taxation_customs/dds2/taric/taric_consultation.jsp?Lang=en&Code=850760)); USITC HTS 8507.60 ([link](https://hts.usitc.gov/?query=8507.60)); EU TARIC 8504.40 ([link](https://ec.europa.eu/taxation_customs/dds2/taric/taric_consultation.jsp?Lang=en&Code=850440)); USITC HTS 8504.40 ([link](https://hts.usitc.gov/?query=8504.40)); EU TARIC 8537.10 ([link](https://ec.europa.eu/taxation_customs/dds2/taric/taric_consultation.jsp?Lang=en&Code=853710)); USITC HTS 8537.10 ([link](https://hts.usitc.gov/?query=8537.10)); UN Manual of Tests and Criteria ([link](https://unece.org/transport/dangerous-goods/un-manual-tests-and-criteria)); UN Recommendations on the Transport of Dangerous Goods, 21st revised edition ([link](https://unece.org/transport/dangerous-goods/un-recs-21st-rev)).

---

Done | Evidence date: 2025-09-15 | Pages index: noindex, follow | Awaiting muse-ba after audit.