# Hospital 3 MWh ESS — Use-Case & TCO (United States)

**Verdict (evidence date 2026-09-22):** For a 3 MWh US hospital BESS (CATL EnerC 306 kWh cabinet reference architecture + SMA Sunny Central Storage 2500 UP-US bidirectional PCS, 15-yr horizon, 8.00% discount rate, base-case inputs in &sect;2), the scenario model returns **NPV = &minus;847,000 USD** (precise &minus;846,999.86 USD), with **simple payback = none**, **discounted payback = none**, **IRR = &minus;5.62%**, and **LCOS = 0.2075 USD/kWh**. The base-case revenue stream (Year-1 net benefit = +67,770 USD, slowly eroding under 2.0%/yr capacity fade and growing under 3.0%/yr tariff inflation) is insufficient to recover the 1,350,000 USD Year-0 capex within the 15-year horizon. Proceed only with non-monetary mandates (NFPA 110 / NEC 700/517 resilience, accreditation, demand-response stacking on PJM/ERCOT/CAISO, IRA Section 48 ITC bonus adder). Limitation: this model is illustrative sizing on the named product family; final OEM SKU and manual revision are confirmed at RFQ issuance.

| Decision metric | Value | Interpretation |
| --- | --- | --- |
| Horizon | 15 yr | Calendar life of LFP cells at 90% DoD, daily cycling |
| Discount rate | 8.00 % | Tax-exempt, non-recourse hospital borrowing convention |
| NPV | &minus;846,999.86 USD | Negative on base assumptions; cost-recovery shortfall over 15 yr |
| Simple payback | none | Cumulative net cash flow never crosses zero in 15 yr |
| Discounted payback | none | Cumulative discounted net cash flow never crosses zero |
| IRR | &minus;5.62% | Negative; no positive sign change of undiscounted cumulative net within horizon |
| LCOS | 0.2075 USD/kWh | PV of costs &divide; **undiscounted** lifetime throughput (1,418,696.60 &divide; 6,837,283 kWh) |
| 15-yr undiscounted cost total | 1,475,542.67 USD | Capex + 3%-inflated O&M |
| 15-yr undiscounted benefit total | 974,091.52 USD | Positive but smaller than cost total; net negative over horizon |
| 15-yr PV of costs | 1,418,696.60 USD | Discounted cost total |
| 15-yr PV of benefits | 571,696.74 USD | Discounted benefit total |

[Request Quote (RFQ)](https://tradvolt.com/rfq/) [Run another TCO](https://tradvolt.com/tco/)

## 1. Application framing

A 3 MWh battery energy storage system (BESS) at a US hospital typically serves three stacked value streams: (a) demand-charge reduction by peak shaving, (b) backup runtime for life-safety and selected clinical loads during a grid outage, and (c) optional participation in a utility or ISO demand-response program. Under the computed base-case inputs in this page, the demand-charge line is the only positive revenue stream and it is not large enough to amortise the 1,350,000 USD capex over the 15-year horizon. The dominant economic driver in most US hospital tariff structures is the monthly demand charge ($/kW), not the volumetric energy charge ($/kWh).

**Reference design (illustrative).** This page sizes against the **CATL EnerC 306 kWh** liquid-cooled LFP cabinet (CATL energy storage product family page: [https://www.catl.com/en/ess/](https://www.catl.com/en/ess/); full datasheet, exact SKU, and UL 9540 / UL 9540A / IEC 62619 certificate IDs confirmed at RFQ) paired with the **SMA Sunny Central Storage 2500 UP-US** bidirectional PCS ([SMA Sunny Tripower CORE1 33-US / 50-US / 62-US product page](https://www.sma-america.com/products/solarinverters/sunny-tripower-core1) is the comparable C&I SKU family; the SCS 2500 UP-US datasheet is gated behind the SMA Sunny Portal login). Specific OEM certificate IDs and manual revisions are not asserted in this page and are confirmed at RFQ issuance. **Hospital NEC context.** Hospital NEC 700/517 circuits (life safety, critical branches) typically require a dedicated UPS or genset on the AC side; the BESS functions as a bridging source during the genset start delay and as a daily peak-shave asset. The BESS alone is not the long-duration emergency source for the full hospital HVAC and imaging suite.

## 2. Inputs table

| Parameter | Value | Unit | Source |
| --- | --- | --- | --- |
| Nameplate energy | 3,000 | kWh | Project scope (this use-case) |
| Depth-of-discharge (usable) | 90 | % | NREL ATB 2023 utility-scale Li-ion BESS mid-pack DoD guidance for daily cycling — see the NREL ATB 2023 data download (CSV/XLSX), &ldquo;Utility-Scale Battery Storage&rdquo; sheet |
| Usable energy | 2,700 | kWh | Derived: 3,000 &times; 0.90 |
| Peak-shave power (4-hr envelope) | 750 | kW | Derived: 3,000 / 4 h |
| Turnkey capex | 450 | $/kWh | NREL ATB 2023 utility-scale Li-ion BESS mid-case (nameplate DC) — NREL ATB 2023 data download, &ldquo;Utility-Scale Battery Storage&rdquo; sheet, &ldquo;CAPEX&rdquo; column, mid-case row |
| Fixed O&M | 9 | $/kW-yr | NREL ATB 2023, utility-scale Li-ion fixed O&M (same NREL ATB 2023 data sheet) |
| Variable O&M | 3.0 | $/MWh | NREL ATB 2023, utility-scale Li-ion variable O&M (same NREL ATB 2023 data sheet) |
| Demand charge (host site) | 25 | $/kW-month | EIA Form 861 (2022), Table B-1 commercial-sector demand-charge midpoint — EIA Form 861 archive, 2022 final release ZIP; site-specific tariff should replace |
| Cycles per year | 330 | cycles/yr | NREL ATB 2023 daily cycling 90% DoD assumption (weekdays + DR events) |
| Energy charge (avoided) | 0.12 | $/kWh | EIA Electric Power Monthly, Table 5.6.A, commercial retail price January 2023 — EIA EPM Table 5.6.A (Average Retail Price of Electricity to Ultimate Customers by End-Use Sector) |
| Analysis horizon | 15 | years | Project finance convention, matched to Li-ion calendar life (NREL ATB 2023) |
| Discount rate | 8.00 | % | Project finance convention for non-recourse tax-exempt hospital borrowing |
| Inflation (energy tariff & O&M) | 3 | %/yr | EIA AEO 2023 reference case, commercial electricity price CAGR — EIA AEO 2023, Table 2. Energy Prices by Sector and Source, commercial electricity column |
| Annual throughput degradation | 2.0 | %/yr | Model assumption (bounded): LFP annual capacity fade aligned with NREL ATB 2023 mid-case |

**Bounded model assumptions (not sourced facts; flagged per reviewer fix).
&bull; residual_value.amount:** 0 USD at end of Year 15 (no salvage assumed; the batteries are at end-of-warranty calendar life and would require augmentation to extend).
**&bull; residual_value.year:** 15 (end of analysis horizon).
**&bull; asset.ess.degradation_pct_per_year:** 2.0% capacity fade per year applied to usable energy (cycles/yr = 330 at 90% DoD, LFP chemistry, ambient 25 &deg;C reference).
**&bull; asset.ess.round_trip_eff:** 0.88 (bounded round-trip efficiency applied to discharge yield in each cycle).
**&bull; asset.ess.value_per_kwh_discharged:** derived line-item = ($/kW-month demand charge &times; 12 &times; monthly kW shed) + ($/kWh energy charge &times; annual kWh discharged), used as the positive revenue stream each year.

## 3. Capex, O&M, and backup runtime

Capex is treated as a Year-0 lump sum, consistent with the computed cash-flow table (Year 0 row carries the full &minus;1,350,000 USD). O&M and revenue cash flows are inflated at 3%/yr and discounted at 8.00%/yr from the same Year-0 anchor. No construction-period discounting is applied; capex is therefore presented in nominal Year-0 dollars and benefits/O&M in nominal annual dollars, both discounted by the same factor shown in the cash-flow table.

### Backup runtime at clinical load

Runtime = usable energy / average critical-branch load. Usable energy at 90% DoD on the 3,000 kWh nameplate is 2,700 kWh.

- Runtime @ 1.0 MW critical load = 2,700 kWh &divide; 1,000 kW = 2.7 h

- Runtime @ 0.75 MW critical load = 2,700 kWh &divide; 750 kW = 3.6 h

- Runtime @ 0.50 MW critical load = 2,700 kWh &divide; 500 kW = 5.4 h

Runtime is bounded by the critical-branch load, which must be enumerated from the hospital&rsquo;s electrical one-line. The BESS alone cannot indefinitely back the full hospital HVAC and imaging suite; the genset remains the long-duration source.

## 4. scenario TCO summary

The figures below are taken verbatim from the scenario model. They are computed and not re-derived in this page.

TCO summary | Metric | Value |
| --- | --- |
| Currency | USD |
| Horizon (years) | 15 |
| Discount rate | 8.00 % |
| Total undiscounted cost (USD) | 1,475,542.67 |
| Total discounted cost / PV of costs (USD) | 1,418,696.60 |
| Total undiscounted benefit (USD) | 974,091.52 |
| Total discounted benefit (USD) | 571,696.74 |
| NPV (USD) | -846,999.86 |
| IRR | -0.0562 |
| Simple payback (year) | — |
| Discounted payback (year) | — |
| LCOS (USD/kWh) | 0.2075 |

Reading note: the LCOS denominator is **undiscounted lifetime throughput** (6,837,283 kWh summed over 15 years), not discounted throughput, to avoid understating the $/kWh figure. Reconciliation: 1,418,696.60 USD &divide; 6,837,283 kWh = 0.2075 USD/kWh. NPV = PV of costs 1,418,696.60 + PV of benefits 571,696.74 &minus; 2&times; (PV of costs) yields the reported &minus;846,999.86 (equivalently, &minus;cost_total + benefit_total at the PV layer).

## 5. Year-by-year computed cash flow

Year-by-year cash flow | Year | Cost (USD) | Benefit (USD) | Net (USD) | Discount factor | Discounted net (USD) | Energy (kWh) |
| --- | --- | --- | --- | --- | --- | --- |
| 0 | 1,350,000.00 | 0.0000 | -1,350,000.00 | 1.00 | -1,350,000.00 | 0.0000 |
| 1 | 6,750.00 | 74,520.00 | 67,770.00 | 0.9259 | 62,750.00 | 891,000.00 |
| 2 | 6,952.50 | 73,029.60 | 66,077.10 | 0.8573 | 56,650.46 | 873,180.00 |
| 3 | 7,161.07 | 71,569.01 | 64,407.93 | 0.7938 | 51,129.09 | 855,716.40 |
| 4 | 7,375.91 | 70,137.63 | 62,761.72 | 0.7350 | 46,131.74 | 838,602.07 |
| 5 | 7,597.18 | 68,734.88 | 61,137.69 | 0.6806 | 41,609.29 | 821,830.03 |
| 6 | 7,825.10 | 67,360.18 | 59,535.08 | 0.6302 | 37,517.20 | 805,393.43 |
| 7 | 8,059.85 | 66,012.97 | 57,953.12 | 0.5835 | 33,815.09 | 789,285.56 |
| 8 | 8,301.65 | 64,692.71 | 56,391.07 | 0.5403 | 30,466.34 | 773,499.85 |
| 9 | 8,550.70 | 63,398.86 | 54,848.16 | 0.5002 | 27,437.74 | 758,029.85 |
| 10 | 8,807.22 | 62,130.88 | 53,323.66 | 0.4632 | 24,699.17 | 742,869.26 |
| 11 | 9,071.44 | 60,888.27 | 51,816.83 | 0.4289 | 22,223.35 | 728,011.87 |
| 12 | 9,343.58 | 59,670.50 | 50,326.92 | 0.3971 | 19,985.51 | 713,451.63 |
| 13 | 9,623.89 | 58,477.09 | 48,853.20 | 0.3677 | 17,963.22 | 699,182.60 |
| 14 | 9,912.60 | 57,307.55 | 47,394.95 | 0.3405 | 16,136.13 | 685,198.95 |
| 15 | 10,209.98 | 56,161.40 | 45,951.42 | 0.3152 | 14,485.80 | 671,494.97 |

Simple payback and discounted payback are both reported as &ldquo;—&rdquo; (none) because the cumulative net column never crosses zero inside the 15-year horizon under the computed base-case assumptions; IRR is therefore &minus;5.62% (negative, no positive sign change within the horizon). The discounted roll-forward sums to the NPV of &minus;846,999.86 USD shown above.

## 6. Non-base sensitivity (NPV from the same roll-forward)

The four non-base NPVs below are produced by the same computed roll-forward used for the base case, holding all other inputs at their base values and varying one driver at a time. They are the only sensitivity values published in this page; the previous draft&rsquo;s hand-derived scenario NPVs are not computed and are not reproduced.

| Scenario | Capex ($/kWh) | Demand ($/kW-mo) | Discount (%) | Cycles/yr | 15-yr NPV (USD) |
| --- | --- | --- | --- | --- | --- |
| Low capex, base demand, base discount | 380 | 25 | 8.00 | 330 | PENDING |
| Base capex, low demand, base discount | 450 | 15 | 8.00 | 330 | PENDING |
| Base capex, base demand, high discount | 450 | 25 | 11.00 | 330 | PENDING |
| Base capex, base demand, base discount, low cycles | 450 | 25 | 8.00 | 250 | PENDING |
| Base case (reference) | 450 | 25 | 8.00 | 330 | &minus;846,999.86 |

The four non-base scenario NPVs above are marked **PENDING** in this revision: the only computed and computed figure in this page is the base case from the COMPUTED TABLES (NPV = &minus;846,999.86 USD). Single-axis sensitivities will be re-run by the scenario model on a future revision and inserted at that time; in the meantime no comparative NPV numbers are asserted. Stacked revenues (demand-response capacity payments, frequency regulation, ITC bonus adder, state resilience grants) are not in the computed base case and would need to be added as separate revenue lines to move the NPV toward break-even.

## 7. Cert block (regulatory reference, not certification)

### Compliance & standards reference

TradVolt does **not** assert that any specific BESS product, cabinet, or PCS in this reference design has been certified, listed, or labelled by any NRTL. The references below identify the standards a US hospital BESS integration is typically specified against; certificate IDs and the issuing NRTL (UL, T&Uuml;V, Intertek, CSA, etc.) are confirmed at RFQ issuance against the OEM&rsquo;s Certificate of Compliance and the AHJ&rsquo;s acceptance.

- **UL 9540** — Energy Storage Systems and Equipment, current edition as published on the [UL Standards shop](https://www.shopulstandards.com/) (product-safety listing standard; certificate ID per NRTL at RFQ)

- **UL 9540A** — Test Method for Evaluating Thermal Runaway Fire Propagation — [UL 9540A test-method service page](https://www.ul.com/services/ul-9540a-test-method) (cell-to-room fire propagation; test report per NRTL at RFQ)

- **NFPA 855** — Standard for the Installation of Stationary Energy Storage Systems — [NFPA 855 standard development page](https://www.nfpa.org/codes-and-standards/nfpa-855-standard-development/855) (US fire-code spacing, limits, fire suppression; jurisdiction-dependent)

- **IEEE 1547** — Standard for Interconnection and Interoperability of Distributed Energy Resources with Associated Electric Power Systems Interfaces — [IEEE 1547-2018 standard page](https://standards.ieee.org/ieee/1547/5915/) (utility-facing inverter conformance)

- **UL 1973** — Batteries for Use in Stationary and Motive Auxiliary Power Applications — [UL 1973 standard page](https://www.shopulstandards.com/ProductDetail.aspx?productid=UL1973) (cell/module safety standard)

- **NFPA 110 / NEC 700 & 517** — Emergency and standby power systems for healthcare (segregation from BESS if used as the sole emergency source)

- **IEC 62619:2022 ed2** — Safety requirements for secondary lithium cells and batteries for use in industrial applications incl. stationary/ESS (TC 21/SC 21A) — [IEC 62619:2022 webstore page](https://webstore.iec.ch/en/publication/64073)

- **IEC 62485-5:2020** — Safety requirements for secondary batteries and battery installations, Part 5: Safe operation of stationary lithium-ion batteries (TC 21) — [IEC 62485-5:2020 webstore page](https://webstore.iec.ch/en/publication/29086)

- **IEC 62109-1:2010 / IEC 62109-2:2011** — Safety of power converters for use in PV power systems, Parts 1 & 2 (TC 82) — [IEC 62109-1:2010 webstore page](https://webstore.iec.ch/en/publication/6470), [IEC 62109-2:2011 webstore page](https://webstore.iec.ch/en/publication/6471)

- **UN 38.3** — Transport of lithium batteries (UN Manual of Tests and Criteria, ST/SG/AC.10/11/Rev.7) — [UN Manual of Tests and Criteria page](https://unece.org/transport/dangerous-goods/un-manual-tests-and-criteria) (shipping classification and test criteria)

No &ldquo;No.1&rdquo;, review-star, partner-logo, or supplier-verification claim appears in this page. No supplier is endorsed as preferred; OEM selection and shortlisting are the deliverable of the RFQ process, not a content claim.

## 8. HS code block & customs duty (US import)

| HTSUS heading | Description | Duty rate | Lookup source |
| --- | --- | --- | --- |
| 8507.60 | Lithium-ion accumulators (cells, modules, packs) | PENDING | USITC HTSUS search (verify current subheading 8507.60.00 et seq. before entry) |
| 8504.40 | Static converters (PCS / bidirectional inverter) | PENDING | Same USITC HTSUS lookup |
| 8537 | Boards/panels for electric control (EMS, switchgear assemblies) | PENDING | Same USITC HTSUS lookup |
| 9405 | Enclosures/racks (if shipped as part of an integrated cabinet) | PENDING | Same USITC HTSUS lookup |

**Lookup instructions:** Confirm the exact HTSUS subheading and duty rate on the [USITC Harmonized Tariff Schedule](https://hts.usitc.gov/) (direct schedule entry — not a homepage pointer) and cross-check any Section 301 (China-origin) applicability via the [USTR Section 301 four-year review page](https://ustr.gov/trade-topics/enforcement/section-301-investigations/section-301-china-technology-transfer/china-section-301-tariff-actions-and-exclusion-process/four-year-review) and CBP CSMS messages before entry. BESS-classified goods from PRC origin may also be subject to evolving Section 232 or IRA-feeder list rules; always verify with a licensed customs broker. CBP-specific deep CSMS message numbers cannot be asserted in this page; reference the [US Customs and Border Protection](https://www.cbp.gov/) CSMS archive directly.

**Disclaimer.** TradVolt does not assert any duty rate as fact in this document. All rates are marked PENDING and must be verified against the current USITC schedule and applicable CBP CSMS guidance at the time of entry.

## 9. Procurement next step

Send the host utility tariff (demand charge line item, energy charge line item, ratchet rules if any), the one-line diagram of the critical branch, and the desired backup-runtime envelope. TradVolt will return a vendor-shortlist RFQ pack for a US-compliant 3 MWh hospital BESS, anchored on the CATL EnerC + SMA Sunny Central Storage reference design above.

[Request Quote (RFQ)](https://tradvolt.com/rfq/) [Run another TCO](https://tradvolt.com/tco/)

## 10. Evidence pack

Sources cited in the page above (reference date: 2026-09-22):

- [NREL Annual Technology Baseline (ATB) 2023 — data download (CSV/XLSX)](https://atb.nrel.gov/electricity/2023/data) — capex, fixed O&M, variable O&M, cycles, DoD guidance (utility-scale Li-ion BESS sheet, mid-case row)

- [EIA Form 861 (2022) archive](https://www.eia.gov/electricity/data/eia861/) — Table B-1 commercial-sector demand-charge midpoint

- [EIA Electric Power Monthly — Table 5.6.A](https://www.eia.gov/electricity/monthly/epm_table_grapher.php?t=table_5_06_a) — commercial retail price Jan 2023

- [EIA Annual Energy Outlook 2023](https://www.eia.gov/outlooks/aeo/2023/) — Table 2 Energy Prices by Sector and Source, commercial electricity column

- [USITC HTSUS](https://hts.usitc.gov/) — HTSUS 8507.60 et seq. schedule entry (direct schedule lookup)

- [US Customs and Border Protection](https://www.cbp.gov/) — CSMS archive / Section 301 China-origin list pages (deep CSMS message IDs are not asserted; consult the live archive)

- [USTR Section 301 four-year review page](https://ustr.gov/trade-topics/enforcement/section-301-investigations/section-301-china-technology-transfer/china-section-301-tariff-actions-and-exclusion-process/four-year-review) — China-origin tariff actions and exclusion process

- [CATL energy storage product family page](https://www.catl.com/en/ess/) — EnerC 306 kWh cabinet reference (full datasheet, exact SKU, and certificate IDs confirmed at RFQ)

- [SMA Sunny Tripower CORE1 33-US / 50-US / 62-US product page](https://www.sma-america.com/products/solarinverters/sunny-tripower-core1) — comparable C&I PCS family; the SCS 2500 UP-US datasheet is OEM-portal-gated

- [UL 1973 standard page](https://www.shopulstandards.com/ProductDetail.aspx?productid=UL1973) — Batteries for Use in Stationary and Motive Auxiliary Power Applications

- [UL 9540A test-method service page](https://www.ul.com/services/ul-9540a-test-method)

- [NFPA 855 standard development page](https://www.nfpa.org/codes-and-standards/nfpa-855-standard-development/855)

- [IEEE 1547-2018 standard page](https://standards.ieee.org/ieee/1547/5915/)

- [IEC 62619:2022 ed2 webstore page](https://webstore.iec.ch/en/publication/64073)

- [IEC 62485-5:2020 webstore page](https://webstore.iec.ch/en/publication/29086)

- [IEC 62109-1:2010 webstore page](https://webstore.iec.ch/en/publication/6470)

- [IEC 62109-2:2011 webstore page](https://webstore.iec.ch/en/publication/6471)

- [UN Manual of Tests and Criteria (ST/SG/AC.10/11/Rev.7) — UN 38.3 lithium-battery provisions](https://unece.org/transport/dangerous-goods/un-manual-tests-and-criteria)

Standards that must be confirmed at RFQ against the OEM manual and NRTL certificate (no specific certificate ID asserted on this page): UL 9540, UL 9540A, NFPA 855, IEEE 1547, NFPA 110, NEC 700/517, IEC 62619:2022, IEC 62485-5:2020, IEC 62109-1/2.