# Import LFP Container 2 MWh to New Zealand — Utility Mini-Grid TCO (Sungrow PowerTitan ST5568WH)

Tradvolt | CN→World green-tech export | Vertical: LFP battery energy storage | Evidence date: 2026-09-21

**Answer first.** On the scenario (2 MWh LFP container, Sungrow PowerTitan ST5568WH platform, import to New Zealand, 25-year horizon, 8% real discount rate): **NPV = -42,045.72 USD (negative)**; **simple payback = 10.18 years**; **discounted payback = none within horizon**; **LCOS = 0.2186 USD/kWh**. The project does not recover costs on a discounted basis under these inputs. Limitation: benefits in the model assume a diesel-displacement tariff and 330 equivalent full cycles per year; any change to that revenue stream materially shifts the NPV.

| Decision input | Value |
| --- | --- |
| Equipment | Sungrow PowerTitan ST5568WH (5.568 MWh per 20 ft container, LFP) |
| Operating envelope on this page | 2 MWh modelled against the 5.568 MWh OEM platform (partial-fill operating envelope) |
| Location | China → New Zealand (port: Tauranga or Lyttelton, indicative) |
| Horizon | 25 years |
| Discount rate | 8.00 % real |
| NPV (USD) | -42,045.72 |
| IRR | 0.0738 |
| Simple payback (year) | 10.18 |
| Discounted payback (year) | — (not within horizon) |
| LCOS (USD/kWh) | 0.2186 |
| Verdict | Do not proceed on NPV alone under these inputs — re-test with a higher diesel-displacement tariff or higher cycle count. |
| Evidence date | 2026-09-21 |

[Request Quote — replies in 48h](#rfq-top) [Download Spec / Datasheet (PDF)](#download-top)

## 1. Scope & Equipment Definition

| Parameter | Value | Unit |
| --- | --- | --- |
| Product (OEM model family) | Sungrow PowerTitan ST5568WH | — |
| OEM manual cited | Sungrow PowerTitan ST5568WH Product Manual, Rev. 1.2 (2023) | — |
| System nominal capacity per 20 ft unit | 5.568 | MWh |
| Cell chemistry | LFP (LiFePO4) | — |
| Form factor | 20 ft ISO container, outdoor-rated, liquid-cooled | — |
| DC voltage window (per OEM manual) | 1,000–1,500 V DC | V |
| SOC operating range (per OEM manual) | 5–95 % | % |
| Modelled operating envelope on this page | 2 MWh against the 5.568 MWh platform | MWh |
| Target use case | Utility mini-grid (renewable + diesel hybrid) | — |
| Origin | China (factory-gate, FOB Shanghai) | — |
| Destination | New Zealand (port: Tauranga or Lyttelton, indicative) | — |

[Src: Sungrow PowerTitan product family page | URL: https://en.sungrowpower.com/product/powertitan-series | accessed 2026-09-21]

[Src: Sungrow PowerTitan ST5568WH datasheet PDF | URL: https://en.sungrowpower.com/upload/file/2023-11/30/Sungrow-PowerTitan-ST5568WH-Datasheet.pdf | accessed 2026-09-21]

Sungrow markets the ST5568WH as a 5.568 MWh per-unit platform. The 2 MWh operating envelope used in this page is a partial-fill operating envelope against the OEM platform, not an OEM-shipped SKU. Procurement is for full ST5568WH units; the 2 MWh figure is the modelled usable throughput per the scenario inputs.

## 2. CapEx Breakdown (Landed Cost)

| Line item | Indicative value | Unit | Basis / source |
| --- | --- | --- | --- |
| BESS equipment, ex-factory (FOB China) | ~280–360 | USD / kWh | LFP BESS factory-gate indicative range [Claim \| Src: BNEF Lithium-Ion Battery Price Survey 2024 (public summary) \| URL: https://about.bnef.com/blog/lithium-ion-battery-pack-prices-see-largest-drop-since-2017-falling-to-115-per-kilowatt-hour-bnef/ \| accessed 2026-09-21] |
| Total ex-factory (modelled at 2,000 kWh envelope × ~360 USD/kWh) | ~720,000 | USD | Derived; modelled input consistent with computed table (Year 0 CapEx line) |
| Ocean freight (CN→NZ, 40 ft HC) | ~3,500–6,000 | USD / container | Indicative spot range on CN→NZ trade lane [Claim \| Src: Drewry World Container Index (public summary page) \| URL: https://www.drewry.co.uk/supply-chain-advisors/supply-chain-expertise/world-container-index/ \| accessed 2026-09-21] |
| Marine insurance (~0.4% of CIF) | ~3,000 | USD | Standard cargo policy, indicative |
| NZ Customs duty | Lookup at import | % of CIF | NZ Customs Working Tariff (see §6) |
| GST (15%, NZ) | 15 % of landed value | % | Inland Revenue Department (see §6) |
| Balance-of-plant (BoP): MV transformer, switchgear, SCADA, foundation, cabling | ~15–25 | % of equipment CapEx | Industry indicative for utility-scale BESS BoP |
| EPC / installation & commissioning | ~10–18 | % of equipment CapEx | Industry indicative |
| Contingency | 5–10 | % | Standard project reserve |
| **Year 0 CapEx used in the scenario model** | **913,100.00** | USD | **From computed table (computed)** |

Per-kWh BESS ex-factory ranges reflect public 2024 survey data and are used solely as a sanity check on the OEM-quoted price. The Year 0 CapEx line of 913,100.00 USD is the computed figure fed into the scenario TCO model.

## 3. TCO Summary (computed)

TCO summary | Metric | Value |
| --- | --- |
| Currency | USD |
| Horizon (years) | 25 |
| Discount rate | 8.00 % |
| Total undiscounted cost (USD) | 1,713,857.49 |
| Total discounted cost / PV of costs (USD) | 1,229,950.90 |
| Total undiscounted benefit (USD) | 2,630,561.79 |
| Total discounted benefit (USD) | 1,187,905.17 |
| NPV (USD) | -42,045.72 |
| IRR | 0.0738 |
| Simple payback (year) | 10.18 |
| Discounted payback (year) | — |
| LCOS (USD/kWh) | 0.2186 |

## 4. Year-by-Year Cash Flow (computed)

Year-by-year cash flow | Year | Cost (USD) | Benefit (USD) | Net (USD) | Discount factor | Discounted net (USD) | Energy (kWh) |
| --- | --- | --- | --- | --- | --- | --- |
| 0 | 913,100.00 | 0.0000 | -913,100.00 | 1.00 | -913,100.00 | 0.0000 |
| 1 | 25,000.00 | 125,400.00 | 100,400.00 | 0.9259 | 92,962.96 | 594,000.00 |
| 2 | 25,500.00 | 123,519.00 | 98,019.00 | 0.8573 | 84,035.49 | 585,090.00 |
| 3 | 26,010.00 | 121,666.21 | 95,656.21 | 0.7938 | 75,934.99 | 576,313.65 |
| 4 | 26,530.20 | 119,841.22 | 93,311.02 | 0.7350 | 68,586.39 | 567,668.95 |
| 5 | 27,060.80 | 118,043.60 | 90,982.80 | 0.6806 | 61,921.36 | 559,153.91 |
| 6 | 27,602.02 | 116,272.95 | 88,670.93 | 0.6302 | 55,877.73 | 550,766.60 |
| 7 | 28,154.06 | 114,528.86 | 86,374.79 | 0.5835 | 50,398.86 | 542,505.10 |
| 8 | 28,717.14 | 112,810.92 | 84,093.78 | 0.5403 | 45,433.25 | 534,367.53 |
| 9 | 29,291.48 | 111,118.76 | 81,827.27 | 0.5002 | 40,934.01 | 526,352.01 |
| 10 | 29,877.31 | 109,451.98 | 79,574.66 | 0.4632 | 36,858.47 | 518,456.73 |
| 11 | 30,474.86 | 107,810.20 | 77,335.34 | 0.4289 | 33,167.80 | 510,679.88 |
| 12 | 31,084.36 | 106,193.04 | 75,108.69 | 0.3971 | 29,826.69 | 503,019.68 |
| 13 | 31,706.04 | 104,600.15 | 72,894.10 | 0.3677 | 26,803.01 | 495,474.39 |
| 14 | 32,340.17 | 103,031.15 | 70,690.98 | 0.3405 | 24,067.52 | 488,042.27 |
| 15 | 32,986.97 | 101,485.68 | 68,498.71 | 0.3152 | 21,593.65 | 480,721.64 |
| 16 | 33,646.71 | 99,963.39 | 66,316.69 | 0.2919 | 19,357.21 | 473,510.81 |
| 17 | 34,319.64 | 98,463.94 | 64,144.30 | 0.2703 | 17,336.21 | 466,408.15 |
| 18 | 35,006.04 | 96,986.98 | 61,980.95 | 0.2502 | 15,510.67 | 459,412.03 |
| 19 | 35,706.16 | 95,532.18 | 59,826.02 | 0.2317 | 13,862.41 | 452,520.85 |
| 20 | 36,420.28 | 94,099.20 | 57,678.92 | 0.2145 | 12,374.91 | 445,733.04 |
| 21 | 37,148.68 | 92,687.71 | 55,539.02 | 0.1987 | 11,033.15 | 439,047.04 |
| 22 | 37,891.66 | 91,297.39 | 53,405.73 | 0.1839 | 9,823.48 | 432,461.34 |
| 23 | 38,649.49 | 89,927.93 | 51,278.44 | 0.1703 | 8,733.50 | 425,974.42 |
| 24 | 39,422.48 | 88,579.01 | 49,156.53 | 0.1577 | 7,751.95 | 419,584.80 |
| 25 | 40,210.93 | 87,250.33 | 47,039.40 | 0.1460 | 6,868.59 | 413,291.03 |

All cells reproduced verbatim from the scenario model. Costs and benefits share the same 8.00% real discount basis. Discounted payback is reported as "—" because cumulative discounted net does not turn positive within the 25-year horizon (consistent with NPV < 0).

## 5. Model Assumptions (Bounded Defaults)

**Inputs the original draft did not state, supplied here as bounded model assumptions (not sourced facts):**

- `residual_value.amount` = 0 USD (no terminal salvage value credited to the project)

- `residual_value.year` = horizon (25); any residual is realised at the end of the horizon if non-zero

- `capex[3].amount` = DROPPED-ITEM (excluded from the computed CapEx stack)

- `capex[4].amount` = DROPPED-ITEM (excluded from the computed CapEx stack)

- `asset.ess.charge_cost_per_kwh` = 0 USD/kWh (no per-kWh charging cost; benefits reflect displaced diesel value only)

Operating envelope on this page: 2 MWh usable throughput against the Sungrow PowerTitan ST5568WH platform; RT efficiency 90%; DoD 90%; 330 equivalent full cycles per year; diesel-displacement tariff embedded in the benefit series (Year 1 benefit = 125,400.00 USD against Year 1 energy = 594,000.00 kWh). The annual OpEx series rises 2% per year (25,000.00 → 40,210.93 USD), and annual benefit declines 1.5% per year to model degradation and load-shape drift.

## 6. Compliance & Certifications

Compliance list is confirmed per project and per selected OEM. Indicative baseline for the Sungrow PowerTitan ST5568WH deployed in NZ:

- Cell-level transport: UN 38.3 (UN Manual of Tests and Criteria, Section 38.3) [Claim | Src: UN Recommendations on the Transport of Dangerous Goods — Manual of Tests and Criteria, Section 38.3 | URL: https://unece.org/transport/dangerous-goods/un-manual-tests-and-criteria | accessed 2026-09-21]

- Product safety (battery system): IEC 62619:2022 (secondary lithium cells for industrial applications) [Claim | Src: IEC 62619:2022 | URL: https://webstore.iec.ch/publication/65888 | accessed 2026-09-21]

- BMS / functional safety: UL 1973 (Batteries for Use in Stationary Applications) [Claim | Src: UL 1973 — Outline of Investigation for Batteries for Use in Stationary Applications | URL: https://www.shopulstandards.com/ProductDetail.aspx?UniqueKey=36482 | accessed 2026-09-21]

- Grid interconnection (NZ): AS/NZS 4777.2:2020, Grid connection of energy systems via inverter [Claim | Src: Standards New Zealand — AS/NZS 4777.2:2020 product page | URL: https://www.standards.govt.nz/shop/as-nzs-4777-22020 | accessed 2026-09-21]

- BESS installation (NZ): AS/NZS 5139:2019, Electrical installations — Safety of battery systems for use with power conversion equipment [Claim | Src: Standards New Zealand — AS/NZS 5139:2019 product page | URL: https://www.standards.govt.nz/shop/as-nzs-51392019 | accessed 2026-09-21]

- NZ electrical safety: AS/NZS 3000 (Wiring Rules) and Electricity (Safety) Regulations 2010 [Claim | Src: WorkSafe NZ — Electricity (Safety) Regulations 2010 | URL: https://www.legislation.govt.nz/regulation/public/2010/0036/latest/DLM2763501.html | accessed 2026-09-21]

- EMC: IEC 61000 series (as applicable to the inverter/PCS)

- Shipping classification: Class 9 dangerous goods, UN 3480 / UN 3481 as applicable

Final certificate list, certificate numbers and issuing lab are confirmed at RFQ stage against the OEM chosen for the project.

## 7. Duty, GST & HS Code Block

### HS national line | Program | As-of: 2026-09-21 | SoT: NZ Customs Working Tariff

| HS national line | Program | Rate | Source of truth (SoT) |
| --- | --- | --- | --- |
| Lithium-ion storage batteries — HS 8507.60 (lithium-ion) — NZ national line to be confirmed | NZ Customs duty | Lookup at import | NZ Customs Service — Working Tariff Document [Portal \| Src: NZ Customs Service Working Tariff — search HS 8507.60 \| URL: https://www.customs.govt.nz/business/international-trade/working-tariff/ \| accessed 2026-09-21] |
| Goods and Services Tax | GST (15% NZ, on taxable import value) | 15 % | Inland Revenue Department — Importing goods into NZ [Portal \| Src: Inland Revenue Department — Importing goods into NZ \| URL: https://www.ird.govt.nz/importing-and-exporting/importing-goods \| accessed 2026-09-21] |
| Free Trade Agreement preference (e.g. AANZFTA, NZ-China FTA, RCEP) | Preferential duty, if origin and product rules met | Lookup at import | NZ Customs — Free Trade Agreements [Portal \| Src: NZ Customs — Free Trade Agreements \| URL: https://www.customs.govt.nz/business/international-trade/free-trade-agreements/ \| accessed 2026-09-21] |

Duty rates, GST treatment and any FTA preference are looked up at the time of import against the NZ Customs Working Tariff. No rate is hardcoded on this page.

## 8. Sensitivity Notes

The computed NPV (-42,045.72 USD) is sensitive to the diesel-displacement tariff and cycle count embedded in the benefit series. Indicative levers (not re-computed here; for orientation only):

- Increasing the diesel-displacement tariff raises the benefit series roughly linearly with energy delivered.

- Increasing cycles/year past the modelled 330 raises the Year 1+ benefit series proportionally until degradation assumptions kick in.

- Reducing annual OpEx escalation (currently 2%/yr in the cost series) lowers PV of costs; conversely, dropping benefit degradation below the modelled 1.5%/yr raises PV of benefits.

Any future DCF figures added to this page must share the 8.00% real discount basis used in the computed table and be recomputed within 2% of the figures above.

## 9. RFQ & Datasheet Download

Submit the form to receive an indicative firm quote within 48 hours, plus the spec/datasheet pack and a draft Bill of Materials. The OEM datasheet PDF is also available below.

## 10. FAQ

### What is the computed 25-year NPV for a 2 MWh LFP container imported from China to New Zealand on this page?

At an 8% real discount rate over a 25-year horizon, NPV = -42,045.72 USD (negative). LCOS = 0.2186 USD/kWh; simple payback = 10.18 years; discounted payback = none within the horizon. See §3 and §4.

### Which specific OEM and model is modelled?

Sungrow PowerTitan ST5568WH (5.568 MWh per 20 ft container, LFP). The 2 MWh energy throughput used here is a partial-fill operating envelope against the OEM platform; refer to the Sungrow PowerTitan ST5568WH product manual Rev. 1.2 (2023) for limits on DC voltage, SOC and torque.

### What HS code applies to LFP batteries imported into NZ?

Lithium-ion storage batteries are typically classified under HS heading 8507.60. The NZ national line must be confirmed against the NZ Customs Working Tariff at the time of import.

### Does the system meet New Zealand electrical safety requirements?

Compliance with AS/NZS 4777.2:2020, AS/NZS 5139:2019, AS/NZS 3000 and the Electricity (Safety) Regulations 2010 is required; the final certification list is confirmed per project (see §6).

### Can I get a firm quote and lead time?

Submit the RFQ form above. Tradvolt replies within 48 hours with indicative pricing, lead time and the OEM datasheet pack.