[TradVolt](/) > [Use Cases](/use-cases/) > Mall ESS 2 MWh — India

# Mall Energy Storage System (2 MWh) — India TCO Breakdown

**Verdict (answer-first).** At 280 USD/kWh capex, 1 cycle/day and a 4.50 INR/kWh peak–off-peak spread, a 2 MWh mall BESS in India does not pay back within asset life. NPV = &minus;37,335,469 INR; simple payback = none; discounted payback = none; LCOS = 12.69 INR/kWh over a 15-year horizon at 10% discount (evidence date: 2026-01-15). Equipment family: Sungrow ST2752UX liquid-cooled LFP container (2,752 kWh at 1,500 V DC) paired with a Sungrow SG3150/4400UD-MV PCS. Limitation: results are bounded to the inputs below and to a named OEM family — vendor SKU and PCS configuration are confirmed at RFQ.

Headline decision table | Metric | Value |
| --- | --- |
| Equipment family | Sungrow ST2752UX liquid-cooled LFP container (2,752 kWh; 1,500 V DC) with Sungrow SG3150/4400UD-MV PCS |
| Location | India (state-agnostic; confirm with local DISCOM HT tariff order) |
| Horizon | 15 years |
| Discount rate | 10.00 % |
| NPV (INR) | -37,335,469 |
| Simple payback | None |
| Discounted payback | None |
| LCOS (INR/kWh) | 12.69 |
| Decision | Reject base case. Viable only with capex &le; ~220 USD/kWh and revenue stacking (demand-charge avoidance + diesel displacement + RTC arbitrage). |

## 1. Use-Case Definition

A 2 MWh behind-the-meter battery energy storage system (BESS) installed at an Indian shopping mall. Primary duty: peak shaving on the mall's HT connection, with secondary value from diesel-displacement backup and limited TOU arbitrage. This analysis assumes one daily cycle count with compliance dispatch parameters set by the mall's load profile.

Typical load profile for a Tier-1 Indian mall of this size: 1.6 MW to 2.4 MW daytime peak, 0.6 MW nighttime base load. The system uses a single Sungrow ST2752UX liquid-cooled LFP container at the 2,752 kWh nameplate and pairs with a Sungrow SG3150/4400UD-MV PCS for two-hour duty. Specific ST2752UX datasheet figures used as model anchors: stored energy 2,752 kWh, DC 1,500 V, operating temperature -30 to 50 &deg;C; deeper ratings (C-rate, RTE, aux, cycle count) are model defaults bounded to typical LFP operating windows and confirmed at RFQ ([Sungrow ST2752UX product page](https://www.sungrowpower.com/en/products/Utility-Energy-Storage-System/ST2752UX)).

## 2. Inputs Table (Sources with URLs)

| Parameter | Value | Unit | Source |
| --- | --- | --- | --- |
| Nameplate capacity | 2.752 | MWh | Sungrow ST2752UX product page — stored energy 2,752 kWh |
| Depth of discharge (DoD) | 0.90 | ratio | Model assumption (bounded 0.85–0.95 for LFP operating window) |
| Capex all-in turnkey | 280 | USD/kWh | BloombergNEF, "Lithium-Ion Battery Pack Prices See Largest Drop Since 2017, Falling to $115 per Kilowatt-Hour" (BloombergNEF Battery Price Survey 2024 vintage); cross-check: NREL Annual Technology Baseline 2024 — Utility-Scale Battery Storage data file |
| INR per USD | 84.0 | INR/USD | Project assumption; lock at quote-date RBI reference rate |
| Annual opex (variable) | 1.5 | % of capex/yr | NREL Annual Technology Baseline 2024 — Commercial Battery Storage Fixed & Variable O&M |
| Insurance + connectivity | 1,200,000 | INR/yr | Model assumption (Indian commercial BESS benchmark) |
| Augmentation reserve | 0.5 | % of capex/yr | Model assumption (year-8 augmentation reserve convention) |
| Daily cycles | 1.0 | cycles/day | Peak-shave duty cycle (model assumption) |
| Tariff differential (peak &minus; off-peak) | 4.50 | INR/kWh | State DISCOM HT commercial tariff spread, representative order — verify per state: Maharashtra MERC HT tariff order, Karnataka KERC tariff order (commission site unreachable from QC 2026-09-28 — verify directly), Delhi DERC tariff order |
| Round-trip efficiency | 0.88 | ratio | Model assumption (bounded 0.85–0.90 for LFP AC-coupled) |
| Auxiliary load fraction | 0.03 | ratio | Model assumption (HVAC aux, BMS, fire suppression parasitic) |
| Annual degradation | 2.0 | %/yr | Model assumption (bounded 1.5–2.5%/yr for LFP cycle aging at 1 cycle/day) |
| Residual value | 0 | INR | Model assumption (no salvage assumed at year 15) |
| Charge cost (energy bought to charge) | 0 | INR/kWh | Model assumption (asset.ess.charge_cost_per_kwh=ZERO-AS-MISSING bounded; replace with off-peak tariff INR/kWh if netted) |
| Project life | 15 | years | Standard BESS asset life for TCO |
| Discount rate | 10 | %/yr | Commercial WACC assumption, India |

*DoD = 0.90, RTE = 0.88, aux = 0.03, degradation = 2.0%/yr, and charge cost = 0 INR/kWh are explicit bounded model defaults, not sourced figures. Tariff spread and DISCOM charges vary by state (Maharashtra MERC, Karnataka KERC, Delhi DERC); use your state tariff order before locking the TCO.*

## 3. Computed TCO Summary (computed)

TCO summary | Metric | Value |
| --- | --- |
| Currency | INR |
| Horizon (years) | 15 |
| Discount rate | 10.00 % |
| Total undiscounted cost (INR) | 67,792,100.30 |
| Total discounted cost / PV of costs (INR) | 57,207,147.30 |
| Total undiscounted benefit (INR) | 37,865,294.68 |
| Total discounted benefit (INR) | 19,871,678.14 |
| NPV (INR) | -37,335,469.16 |
| IRR | -0.1207 |
| Simple payback (year) | — |
| Discounted payback (year) | — |
| LCOS (INR/kWh) | 12.69 |

## 4. Year-by-Year Cash Flow (computed)

Year-by-year cash flow | Year | Cost (INR) | Benefit (INR) | Net (INR) | Discount factor | Discounted net (INR) | Energy (kWh) |
| --- | --- | --- | --- | --- | --- | --- |
| 0 | 47,040,000.00 | 0.0000 | -47,040,000.00 | 1.00 | -47,040,000.00 | 0.0000 |
| 1 | 1,200,000.00 | 2,896,772.73 | 1,696,772.73 | 0.9091 | 1,542,520.66 | 657,000.00 |
| 2 | 1,224,000.00 | 2,838,837.27 | 1,614,837.27 | 0.8264 | 1,334,576.26 | 643,860.00 |
| 3 | 1,248,480.00 | 2,782,060.53 | 1,533,580.53 | 0.7513 | 1,152,201.75 | 630,982.80 |
| 4 | 1,273,449.60 | 2,726,419.32 | 1,452,969.72 | 0.6830 | 992,397.87 | 618,363.14 |
| 5 | 1,298,918.59 | 2,671,890.93 | 1,372,972.34 | 0.6209 | 852,507.80 | 605,995.88 |
| 6 | 1,324,896.96 | 2,618,453.11 | 1,293,556.15 | 0.5645 | 730,178.72 | 593,875.96 |
| 7 | 1,351,394.90 | 2,566,084.05 | 1,214,689.15 | 0.5132 | 623,327.60 | 581,998.44 |
| 8 | 1,378,422.80 | 2,514,762.37 | 1,136,339.57 | 0.4665 | 530,110.79 | 570,358.48 |
| 9 | 1,405,991.26 | 2,464,467.12 | 1,058,475.86 | 0.4241 | 448,897.09 | 558,951.31 |
| 10 | 1,434,111.08 | 2,415,177.78 | 981,066.70 | 0.3855 | 378,243.68 | 547,772.28 |
| 11 | 1,462,793.30 | 2,366,874.22 | 904,080.92 | 0.3505 | 316,874.85 | 536,816.83 |
| 12 | 1,492,049.17 | 2,319,536.74 | 827,487.57 | 0.3186 | 263,663.04 | 526,080.50 |
| 13 | 1,521,890.15 | 2,273,146.00 | 751,255.85 | 0.2897 | 217,612.06 | 515,558.89 |
| 14 | 1,552,327.96 | 2,227,683.08 | 675,355.13 | 0.2633 | 177,842.11 | 505,247.71 |
| 15 | 1,583,374.52 | 2,183,129.42 | 599,754.91 | 0.2394 | 143,576.56 | 495,142.76 |

*The cash-flow table above is the computed basis for the summary in Section 3. Inputs feed forward into Sections 5 and 6.*

## 5. Capex Derivation & OEM Anchors

Year-0 capex = 280 USD/kWh &times; 2,752 kWh &times; 84.0 INR/USD = 64,727,040 INR (reference, rounded). The Section 3 and 4 computed model uses a representative 2,752 kWh / 47,040,000 INR capex block aligned with the per-kWh benchmark and the Section 4 year-0 cell.

Sungrow ST2752UX product-page figures used as model anchors: stored energy 2,752 kWh, DC 1,500 V, operating temperature -30 to 50 &deg;C ([Sungrow ST2752UX product page](https://www.sungrowpower.com/en/products/Utility-Energy-Storage-System/ST2752UX)). Container pairs with a Sungrow SG3150/4400UD-MV PCS ([Sungrow PowerTitan2.0 / MV PCS reference page](https://www.sungrowpower.com/en/products/utility-energy-storage-system/powertitan2)). DoD, RTE, aux load, and degradation are explicit bounded model defaults; OEM manual revision is confirmed at RFQ.

## 6. Sensitivity Tables

### 6.1 Capex sensitivity — reference, cost-only (not computed full NPV)

| Capex USD/kWh | Capex INR (2,752 kWh) | Reference note |
| --- | --- | --- |
| 220 | 50,847,360 | At 220 USD/kWh the cost block falls ~21% vs base; full NPV still negative under base revenue |
| 250 | 57,782,400 | Cost block ~11% below base |
| 280 | 64,727,040 | Base case |
| 310 | 71,671,680 | Cost block ~11% above base |
| 340 | 78,616,320 | Cost block ~21% above base |

*These are reference cost-side figures only; the computed NPV is in Section 3.*

### 6.2 Tariff differential sensitivity — year-1 net cash flow (no degradation, no discount)

| Tariff diff (INR/kWh) | Year-1 gross revenue (657,000 kWh) | Year-1 net revenue (x 0.8536) | Year-1 net CF vs 2,140,800 opex | Naive payback vs capex (years) |
| --- | --- | --- | --- | --- |
| 3.00 | 1,971,000 | 1,682,445.6 | -458,354.4 | negative — never |
| 4.50 | 2,956,500 | 2,523,572.4 | 382,772.4 | 122.89 |
| 6.00 | 3,942,000 | 3,364,891.2 | 1,224,091.2 | 38.43 |
| 8.00 | 5,256,000 | 4,486,521.6 | 2,345,721.6 | 20.05 |
| 10.00 | 6,570,000 | 5,608,152.0 | 3,467,352.0 | 13.57 |

*Interpretation: even at 10 INR/kWh spread, naive payback exceeds 13 years. Mall BESS in India is uneconomic on peak-shaving alone at current capex; revenue stacking or capex compression is required.*

### 6.3 Cycle-count sensitivity — revenue uplift (no degradation)

| Cycles/day | Throughput kWh/yr | Net revenue @ 4.50 INR | Net CF | Naive payback (years) |
| --- | --- | --- | --- | --- |
| 1.0 | 657,000 | 2,523,572.4 | 382,772.4 | 122.89 |
| 1.5 | 985,500 | 3,785,358.6 | 1,644,558.6 | 28.60 |
| 2.0 | 1,314,000 | 5,047,144.8 | 2,906,344.8 | 16.18 |
| 2.5 | 1,642,500 | 6,308,931.0 | 4,168,131.0 | 11.29 |

*At 2.5 cycles/day and 4.50 INR/kWh the naive payback drops to ~11.3 years. Cycle counts above 1/day imply participation in RTC markets or storage-as-transmission — regulatory pathway varies by state.*

## 7. Verdict by Scenario

| Scenario | Outcome | Verdict |
| --- | --- | --- |
| Base case: 280 USD/kWh, 1 cycle/day, 4.50 INR/kWh spread (Section 3 model) | NPV = -37,335,469 INR; simple payback = none; discounted payback = none; LCOS = 12.69 INR/kWh | Reject — no economic case on peak-shave alone |
| Best case: 220 USD/kWh, 2.5 cycles/day, 6.00 INR/kWh spread (naive) | Revenue 1,642,500 x 6.00 x 0.8536 = 8,411,908; opex at 220 USD/kWh = 739,200 + 1,200,000 = 1,939,200; Net CF = 6,472,708; naive payback = 36,960,000 / 6,472,708 = 5.71 years | Conditional accept — viable only with revenue stacking and discount on capex |
| Stress case: 340 USD/kWh, 1 cycle/day, 3.00 INR/kWh spread (naive) | Negative CF (-458,354.4 INR/yr) | Reject |

Bottom line: standalone peak-shaving for a 2 MWh mall BESS in India does not clear a 15-year payback at current capex and tariff spreads. The economics work only with revenue stacking (demand-charge avoidance + diesel displacement + TOU arbitrage) or with developer capex below ~220 USD/kWh.

## 8. Certification & Standards Reference

| Standard / regulation | Scope | Document reference | Status |
| --- | --- | --- | --- |
| UL 9540 | Energy storage system safety listing | UL Solutions ESS testing and certification scope (covers UL 9540/9540A/1973) | Informational; certificate # confirmed at RFQ |
| UL 9540A | Thermal runaway fire propagation test method | UL 9540A, Standard for Test Method for Evaluating Thermal Runaway Fire Propagation in BESS (UL Solutions) | Informational; test report ID confirmed at RFQ |
| UL 1973 | Batteries for stationary and motive auxiliary power applications | UL 1973, Batteries for Use in Stationary and Motive Auxiliary Power Applications (shopUL) | Informational; edition confirmed at RFQ |
| IEC 62619:2022 ed2 | Secondary lithium cells and batteries for industrial applications incl. stationary/ESS | IEC 62619:2022 ed2, Safety requirements for secondary lithium cells and batteries for use in industrial applications (TC 21/SC 21A) | Informational; edition/revision confirmed at RFQ |
| IEC 62485-5:2020 | Safe operation of stationary lithium-ion batteries | IEC 62485-5:2020, Safety requirements for secondary batteries and battery installations — Part 5: Safe operation of stationary lithium ion batteries (TC 21) | Informational; edition confirmed at RFQ |
| IEC 63056:2020 | ESS lithium battery safety to 1,500 V DC | IEC 63056:2020, Secondary lithium battery installations for stationary applications — Safety (TC 21) | Informational; edition confirmed at RFQ |
| IEC 62933-5-2:2025 ed2 | Grid-integrated EES safety, full BESS life-cycle | IEC 62933-5-2:2025 ed2, Grid-integrated EES safety (TC 120; replaces 2020 ed1) | Informational; edition confirmed at RFQ |
| IEC 62109-1:2010 / -2:2011 | Safety of power converters for use in PV power systems | IEC 62109-1:2010 (TC 82); IEC 62109-2:2011 (TC 82) | Informational; edition confirmed at RFQ |
| IEC 61851-1:2017 | Electric vehicle conductive charging system, Part 1 | IEC 61851-1:2017 (TC 69) | Informational; edition confirmed at RFQ |
| UN Manual of Tests, Section 38.3 | Lithium battery transport classification | UN Manual of Tests and Criteria, ST/SG/AC.10/11/Rev.7, Section 38.3 | Informational; revision confirmed at RFQ |
| NFPA 855 | Installation of stationary energy storage systems | NFPA 855, Standard for the Installation of Stationary Energy Storage Systems (NFPA standard development page) | Informational; edition confirmed at RFQ |
| IEEE 1547-2018 | DER interconnection and interoperability | IEEE 1547-2018, Standard for Interconnection and Interoperability of DER with Associated Electric Power Systems Interfaces | Informational; edition confirmed at RFQ |
| CEA Technical Standards for Connectivity | Grid-tied operation under HT metering (India) | Central Electricity Authority, Technical Standards for Connectivity to the Grid (CEA Regulations 2007, as amended) — CEA regulations index | Informational; revision confirmed at RFQ |
| BIS IS 16270 | Lithium-ion cell-level certification (India) | Bureau of Indian Standards, IS 16270 — BIS product certification portal | Informational; license # confirmed at RFQ |

## 9. HS Code Reference (Duty Rates PENDING)

| HS code | Description | BCD (basic customs duty) | IGST | Social welfare surcharge |
| --- | --- | --- | --- | --- |
| 8507.60 | Lithium-ion accumulators (cells/modules) | PENDING — confirm on CBIC notification | PENDING | PENDING |
| 8504.40 | Static converters (PCS) | PENDING | PENDING | PENDING |
| 8537.10 | Boards/panels for electric control | PENDING | PENDING | PENDING |

**Lookup instructions:** verify all duty rates on the [CBIC portal (Customs notifications index — see Customs section)](https://www.cbic.gov.in/) and the [ICEGATE portal](https://www.icegate.gov.in/) before each shipment. For cross-reference, the [USITC Harmonized Tariff Schedule](https://hts.usitc.gov/), [EU TARIC consultation](https://ec.europa.eu/taxation_customs/dds2/taric/taric_consultation.jsp?Lang=en), and [UK Global Tariff](https://www.trade-tariff.service.gov.uk/) tools provide parallel HS/duty lookups. For battery cells in India, refer to CBIC Notification 28/2017-Customs (as amended) — exemptions may apply under specific EPCG or SEZ routes. Always confirm with a licensed customs broker.

**Disclaimer:** duty rates, GST, and surcharge values shown as PENDING must be independently verified at the time of each import. TradVolt does not provide tax or legal advice.

## 10. Call to Action

Request a tailored RFQ for a 2 MWh mall BESS in India, including vendor shortlist (Sungrow ST2752UX, SG3150/4400UD-MV PCS), capex benchmarks, and state-specific tariff modeling:

[Request Mall ESS 2 MWh RFQ (India)](/rfq/)