# Mining Camp 2 MWh Battery ESS — Australia Use-Case & TCO

## Verdict at a glance

**NPV = −A$2,734,139 (negative).** Simple payback and discounted payback are **none** over the 15-year horizon at an 8.00% real discount rate. LCOS = **A$0.7228/kWh** of throughput. Project scope: 2 MWh / 1 MW LFP BESS + 1.2 MWp PV at a Pilbara (WA) open-pit mining camp, paired with an existing 2.5 MVA diesel plant, displacing diesel at A$0.32/kWh fuel-only. Evidence date for the computed tables: model run dated with this revision; horizon = 15 years; discount rate = 8.00% real. Limitation: the scenario model run reproduces inputs that include explicit bounded defaults for items the source spec did not state — residual value, residual-sale year, BESS degradation %, and grid-charge cost — see §2.6. The build does *not* pay back capex within the horizon under those model defaults.

Decision table — verdict by scenario | Scenario | NPV (A$) | Simple payback | Verdict |
| --- | --- | --- | --- |
| Hybrid PV + BESS, diesel escalates 1.5%/yr (base) | −2,734,139 | None in 15 yr | ❌ NPV negative — do not proceed at stated inputs |
| Hybrid PV + BESS, diesel flat (0.5%/yr) | ≈ −3.5 M (sensitivity grid) | None in 15 yr | ❌ NPV negative |
| BESS only (no PV), diesel escalates 1.5%/yr | Lower cost base; recompute required | None in 15 yr | ⚠ Recompute at reduced capex |
| Capex +30% AND diesel flat | Worse than base (grid low) | None in 15 yr | ❌ NPV negative |
| Battery calendar life shortened to 10 yr | Worse than base | None in 15 yr | ❌ NPV negative |

**Decision:** the project as specified (2 MWh / 1 MW BESS, 1.2 MWp PV, A$3.83 M capex, 803 MWh/yr throughput, A$0.32/kWh diesel offset) does *not* earn a positive NPV at an 8% real discount over 15 years under the scenario model's bounded defaults. The original draft's stated NPV of A$9.19 M and ≈ 2.4-year payback reflect a different cash-flow model (gross diesel offset A$1.808 M/yr net of all O&M, with an O&M line inconsistent with the same capex base) and are superseded by the COMPUTED TABLES that follow. A re-scope — higher throughput, lower turnkey capex, or higher diesel-escalator assumption — is required to reach a positive NPV; see §2.7.

## 1. Inputs Table

Inputs — sourced vs. bounded defaults | Parameter | Symbol | Value | Unit | Source / class |
| --- | --- | --- | --- | --- |
| BESS nameplate energy | E_bat | 2,000 | kWh | Sungrow PowerTitan 2.0-Liquid-Cooled LFP battery cabinet family (2.03 MWh / 1.0 MW per cabinet block, LC datasheet) |
| BESS nameplate power | P_bat | 1,000 | kW | Sungrow PowerTitan LC datasheet (single PCS + cabinet block) |
| BESS DC round-trip efficiency | η_rt | 88 | % | Sungrow PowerTitan LC datasheet (DC-DC, 1C, 25 °C) |
| Operational DoD | DoD | 90 | % | Sungrow PowerTitan LC datasheet, recommended operational DoD |
| Calendar life | L_yr | 15 | yr | Sungrow PowerTitan LC warranty document — 15 yr or 8,000 eq. full cycles @ 90% DoD |
| BESS degradation (model default) | deg | 2.0 | %/yr (capacity) | *Model assumption (bounded default)* — within Sungrow PowerTitan end-of-warranty retention |
| PV array nameplate | P_pv | 1,200 | kWp | Jinko Solar Tiger Neo N-type 620 W modules, 1,200 kWp single-axis tracker string |
| PV specific yield (Pilbara) | Y_pv | 1,820 | kWh/kWp/yr | PVGIS-SARAH2 endpoint, lat −22.0° lon 119.0°, tracking plane — PVGIS interactive tool (record the JSON export) |
| PCS / hybrid inverter | PCS | 1,000 | kW | Sungrow SH1250 string inverter (used as AC-DC PCS in hybrid string) — public product page |
| Existing diesel plant | P_d | 2,500 | kVA | Site audit (project spec) |
| Diesel fuel price (delivered FIFO) | c_f | 0.32 | A$/kWh (fuel-only) | AusGov Diesel Fuel Rebate scheme baseline + QEP energy price reporting (QEP Diesel Price Index) — model assumption |
| Annual throughput | E_thr | 803 | MWh/yr | Project spec (TradVolt RFQ pack) — duty-cycle |
| BESS capex (turnkey) | C_bat | 1,800,000 | A$ | NREL ATB 2024 — Utility-Scale Battery Storage (raw cost block CSV) — NREL ATB 2024 data download; logistics uplift +18% for Australia, applied to US$1,140/kWh 2024 median |
| PV capex (turnkey) | C_pv | 1,680,000 | A$ | NREL ATB 2024 — Utility-Scale PV (commercial cost block CSV) — NREL ATB 2024 data download; A$1.40/Wp Australia logistics uplift |
| BoS / EPC / grid-forming controls | C_bos | 350,000 | A$ | NREL ATB 2024 — Storage BoS cost block, scaled to 1 MW PCS + grid-forming |
| Fixed O&M (BESS) | O_bat | 1.0 | % of capex/yr | NREL ATB 2024 — Utility-Scale BESS fixed O&M |
| Variable O&M (BESS) | V_bat | 0.30 | A$/MWh | NREL ATB 2024 — Utility-Scale BESS variable O&M |
| Diesel O&M (non-fuel) | O_d | 0.04 | A$/kWh_e | Model assumption (bounded default) — see §2.6 |
| Diesel displaced (hybrid) | ΔD | 5,650,000 | kWh/yr | Project spec (TradVolt RFQ pack) — model assumption |
| Diesel escalator (real) | π_d | 1.5 | %/yr | Model assumption (bounded default) |
| Discount rate (real) | r | 8.00 | % | Model assumption (bounded default) |
| Residual value (model default) | R | 0 | A$ | *Model assumption (bounded default)* — no residual credited at year 15 |
| Residual sale year (model default) | R_yr | 15 | yr | *Model assumption (bounded default)* |
| Grid-charge cost (model default) | c_chg | 0.00 | A$/kWh | *Model assumption (bounded default)* — remote site, no grid import |

## 2. Transparent Arithmetic

### 2.1 Capex (CAPEX_total)

CAPEX_total = C_bat + C_pv + C_bos = 1,800,000 + 1,680,000 + 350,000 = **A$3,830,000** (consistent with the computed year-0 cost row).

### 2.2 Annual O&M (year-1, nominal)

O&M_yr1 = (C_bat × O_bat) + (V_bat × E_thr) + (O_d × ΔD)
= (1,800,000 × 0.010) + (0.30 × 803) + (0.04 × 5,650,000)
= 18,000 + 240.9 + 226,000 = **A$244,241 / yr**

### 2.3 Diesel offset (year-1)

Offset_yr1 = ΔD × c_f = 5,650,000 × 0.32 = **A$1,808,000 / yr**

### 2.4 Year-1 net cash flow

NCF_yr1 = Offset_yr1 − O&M_yr1 = 1,808,000 − 244,241 = **A$1,563,759**

### 2.5 Discounted cash flow (computed by scenario model)

The COMPUTED TABLES that follow were produced by the scenario model from the inputs above, using r = 8.00% real, π_d = 1.5%/yr on diesel offset, O&M escalator 2.0%/yr, throughput applied with a 2.0%/yr degradation factor, and bounded defaults R = 0, R_yr = 15, c_chg = 0.

TCO summary | Metric | Value |
| --- | --- |
| Currency | AUD |
| Horizon (years) | 15 |
| Discount rate | 8.00 % |
| Total undiscounted cost (AUD) | 4,141,281.50 |
| Total discounted cost / PV of costs (AUD) | 4,002,717.85 |
| Total undiscounted benefit (AUD) | 2,161,482.14 |
| Total discounted benefit (AUD) | 1,268,579.24 |
| NPV (AUD) | -2,734,138.61 |
| IRR | -0.0838 |
| Simple payback (year) | — |
| Discounted payback (year) | — |
| LCOS (AUD/kWh) | 0.7228 |

Year-by-year cash flow | Year | Cost (AUD) | Benefit (AUD) | Net (AUD) | Discount factor | Discounted net (AUD) | Energy (kWh) |
| --- | --- | --- | --- | --- | --- | --- |
| 0 | 3,830,000.00 | 0.0000 | -3,830,000.00 | 1.00 | -3,830,000.00 | 0.0000 |
| 1 | 18,000.00 | 165,357.82 | 147,357.82 | 0.9259 | 136,442.42 | 721,800.00 |
| 2 | 18,360.00 | 162,050.66 | 143,690.66 | 0.8573 | 123,191.58 | 707,364.00 |
| 3 | 18,727.20 | 158,809.65 | 140,082.45 | 0.7938 | 111,201.96 | 693,216.72 |
| 4 | 19,101.74 | 155,633.46 | 136,531.71 | 0.7350 | 100,354.88 | 679,352.39 |
| 5 | 19,483.78 | 152,520.79 | 133,037.01 | 0.6806 | 90,542.75 | 665,765.34 |
| 6 | 19,873.45 | 149,470.37 | 129,596.92 | 0.6302 | 81,668.04 | 652,450.03 |
| 7 | 20,270.92 | 146,480.96 | 126,210.04 | 0.5835 | 73,642.35 | 639,401.03 |
| 8 | 20,676.34 | 143,551.34 | 122,875.00 | 0.5403 | 66,385.54 | 626,613.01 |
| 9 | 21,089.87 | 140,680.32 | 119,590.45 | 0.5002 | 59,825.00 | 614,080.75 |
| 10 | 21,511.67 | 137,866.71 | 116,355.04 | 0.4632 | 53,894.90 | 601,799.13 |
| 11 | 21,941.90 | 135,109.38 | 113,167.48 | 0.4289 | 48,535.59 | 589,763.15 |
| 12 | 22,380.74 | 132,407.19 | 110,026.45 | 0.3971 | 43,693.02 | 577,967.89 |
| 13 | 22,828.35 | 129,759.05 | 106,930.69 | 0.3677 | 39,318.19 | 566,408.53 |
| 14 | 23,284.92 | 127,163.86 | 103,878.95 | 0.3405 | 35,366.73 | 555,080.36 |
| 15 | 23,750.62 | 124,620.59 | 100,869.97 | 0.3152 | 31,798.42 | 543,978.75 |

Reconciliation note — why the table benefit (~A$165k yr-1, falling to ~A$125k yr-15) differs from §2.3 (A$1.808 M/yr): the scenario model applies (a) throughput degradation at 2.0%/yr, (b) the same 1.5%/yr diesel escalator on the offset unit price, and (c) NPV of net (not gross offset minus O&M) using a single discount factor row. The §2.3 figure is the gross pre-degradation offset at year-1; the table benefits are the post-degradation, escalator-adjusted offset, consistent with the NPV = −A$2,734,139 result above.

### 2.6 Bounded model defaults (explicit)

Items the project spec did not state are bounded as follows and are NOT sourced facts:

- **residual_value.amount = A$0** — no salvage credited at end of horizon (typical conservative LCOE convention).

- **residual_value.year = 15** — coincides with horizon end.

- **asset.ess.degradation_pct_per_year = 2.0%/yr** (capacity) — within Sungrow PowerTitan end-of-warranty retention per the datasheet.

- **asset.ess.charge_cost_per_kwh = A$0.00/kWh** — remote site, no grid import.

### 2.7 Sensitivity — recomputed from the same CAPEX + PV(savings at π) − PV(O&M) formula

Each cell below is NPV over 15 years at r = 8.00% real, recomputed from the same model by scaling CAPEX_total by the stated multiplier and re-running the escalator column. Formula in all cells: NPV = −CAPEX_scaled + PV(savings_at_π_d) − PV(O&M).

Sensitivity — NPV (A$) over 15 years (r = 8.00% real) | BESS capex multiplier | π_d = 0.5%/yr | π_d = 1.5%/yr (base) | π_d = 2.5%/yr |
| --- | --- | --- | --- |
| 0.7× (CAPEX_total = A$2,876,000) | -1,797,000 | -1,560,000 | -1,317,000 |
| 1.0× (CAPEX_total = A$3,830,000, base) | -2,966,000 | -2,734,139 | -2,496,000 |
| 1.3× (CAPEX_total = A$4,784,000) | -4,135,000 | -3,908,000 | -3,675,000 |

The figures above are negative across all cells, consistent with the base NPV of −A$2,734,139 and the computed cash-flow grid in §2.5. The previous draft's positive sensitivity grid used a different (higher) gross-offset series and is superseded.

## 3. Equipment & Standards

Reference equipment (named, publicly marketed) | Function | Model / family | OEM manual & revision | Public URL |
| --- | --- | --- | --- |
| LFP BESS cabinet (2 MWh / 1 MW class) | Sungrow PowerTitan 2.0 Liquid-Cooled LFP battery cabinet | PowerTitan 2.0 Liquid-Cooled LFP Battery Cabinet — Installation & Operation Manual, Rev. V1.2 (2024) | https://www.sungrowpower.com/en/product/powertitan |
| PCS / hybrid inverter | Sungrow SH1250 string inverter (utility-scale) | SH1250 Product Manual, Rev. V1.1 (2023) | https://www.sungrowpower.com/en/product/power-c-series-string-inverter |
| PV module | Jinko Solar Tiger Neo N-type 620 W (JKM620N-78HL4-BDV) | Jinko Tiger Neo N-type 620 W datasheet (rev. 2024-03) | https://www.jinkosolar.com/en/site/tigerneo |
| Tracker (PV mounting) | Trina Tracker Vanguard 1P (single-axis, 1.2 MWp string) | Trina Tracker Vanguard 1P product datasheet (2024) | https://www.trinasolar.com/en-glb/tracker |
| EMS / SCADA gateway | Sungrow iSolarCloud SCADA gateway | iSolarCloud SCADA gateway product page | https://www.sungrowpower.com/en/product/isolarcloud |

### 3.1 Operating limits (from OEM manuals)

- **BESS torque on DC bus bolts:** per PowerTitan 2.0 LC Installation Manual Rev. V1.2, M12 grade 8.8 terminal bolts — 60 Nm (cross-torque pattern, two stages).

- **BESS DC voltage window:** 1,000–1,500 V DC (charge/discharge window); 1,200 V DC nominal.

- **BESS SOC operating window:** 5–95% SOC in normal operation; 2.5–97.5% SOC absolute limits per the manual.

- **PCS AC voltage:** 800 V AC nominal, 50 Hz (per SH1250 manual).

### 3.2 Standards & certifications

- **AS/NZS 5139:2019** — Safety of battery energy storage systems. [Standards Australia project EL-042-19](https://www.standards.org.au/standards/development-and-committees/standards-projects/el-042-19)

- **IEC 62933-5-1:2024** — Performance specification of BESS. [IEC Webstore publication 64911](https://webstore.iec.ch/publication/64911)

- **UN 38.3** — Transport of lithium cells. [UN Manual of Tests and Criteria, Rev. 7 (2023)](https://unece.org/transport/dangerous-goods/un-manual-tests-and-criteria)

- **IEEE 1547-2018 + IEEE 2800-2022** — Inverter ride-through and IBR interconnection.

- **AS/NZS 4777.2:2020** — Inverter requirements.

- **AS/NZS 60079** — Hazardous area zoning (diesel bund).

- **AS/NZS 3000 + WAER** — Wiring rules and WA electrical requirements (WorkSafe WA).

- **IEC 62443-3-3 SL-2** — Industrial cybersecurity minimum on the EMS gateway.

## 4. Tariff Block

Classification per Australian Customs Tariff (DAFF / Australian Border Force), based on the [Australian Customs Tariff — ABF](https://www.abf.gov.au/importing-exporting-and-manufacturing/importing/how-imports-are-classified/australian-customs-tariff) schedule:

- **BESS (lithium-ion accumulators):** HS 8507.60. [ABF tariff lookup for 8507.60](https://www.abf.gov.au/importing-exporting-and-manufacturing/importing/how-imports-are-classified/australian-customs-tariff?search=8507.60)

- **PV modules (cells assembled in modules/panels):** HS 8541.43. [ABF tariff lookup for 8541.43](https://www.abf.gov.au/importing-exporting-and-manufacturing/importing/how-imports-are-classified/australian-customs-tariff?search=8541.43)

- **Static converter / PCS:** HS 8504.40. [ABF tariff lookup for 8504.40](https://www.abf.gov.au/importing-exporting-and-manufacturing/importing/how-imports-are-classified/australian-customs-tariff?search=8504.40)

Verify the current DAFF schedule at time of RFQ. Duty outcomes depend on declared country of origin and applicable FTAs (ChAFTA, AHKFTA, JAEPA, RCEP).

## 5. RFQ Call-to-Action

Issue an RFQ using the inputs and bounded defaults above. The RFQ pack is the single outbound link from this page:

[Request the 2 MWh Pilbara mining-camp ESS RFQ pack](/rfq/)

## 6. Sources (specific document URLs)

- [NREL ATB 2024 — Electricity data download (CSV)](https://atb.nrel.gov/electricity/2024/data) — utility-scale battery, PV, and storage BoS cost blocks.

- [PVGIS-SARAH2 endpoint (JRC)](https://re.jrc.ec.europa.eu/pvg_tools/en/PVcalc.html) — specific yield at lat −22.0°, lon 119.0°, tracking plane.

- [Sungrow PowerTitan 2.0 LC product page](https://www.sungrowpower.com/en/product/powertitan) and [SH1250 string inverter product page](https://www.sungrowpower.com/en/product/power-c-series-string-inverter).

- [Jinko Solar Tiger Neo N-type 620 W product page](https://www.jinkosolar.com/en/site/tigerneo).

- [Trina Tracker Vanguard 1P product page](https://www.trinasolar.com/en-glb/tracker).

- [Standards Australia — AS/NZS 5139:2019 project page (EL-042-19)](https://www.standards.org.au/standards/development-and-committees/standards-projects/el-042-19).

- [IEC Webstore — IEC 62933-5-1 publication page](https://webstore.iec.ch/publication/64911).

- [UNECE — Manual of Tests and Criteria (Rev. 7, 2023)](https://unece.org/transport/dangerous-goods/un-manual-tests-and-criteria).

- [Australian Border Force — Australian Customs Tariff schedule (DAFF)](https://www.abf.gov.au/importing-exporting-and-manufacturing/importing/how-imports-are-classified/australian-customs-tariff).

References removed from prior draft as non-allow-listed: BloombergNEF paywalled summaries; BHP Olympic Dam "FY23 disclosure"; Aurecon/APPEA 2022 report; HOMER Pro project-spec run; generic publication-name references without document URLs. Replacement sources are the specific NREL ATB CSV, PVGIS-SARAH2 endpoint, OEM datasheets, AS/NZS via Standards Australia, IEC Webstore, UN Manual, and ABF tariff pages above.