title: "Parking-Lot ESS — 1 MWh Container in Sea Region | TCO Use-Case | Tradvolt"
source_url: "https://tradvolt.com/en/tco/parking-lot-ess-1-mwh-container-in-sea-region-tco-use-case-tradvolt/"
lang: "en"
description: "Use-case TCO breakdown for a 1 MWh containerised parking-lot battery energy storage system (BESS) for site planners evaluating thermal-exposed coastal installations. Inputs cited, formulas worked, sensitivity included."
generator: "tradvolt-tier-c-edge-md"
---

[Tradvolt](/) &rsaquo; [Use-Cases](/use-cases/) &rsaquo; **Parking-Lot ESS — 1 MWh Container, Sea Region (R9)**

# Parking-Lot Energy Storage — 1 MWh Container in a Sea Region: Total Cost of Ownership

**Verdict: Do not proceed on arbitrage-only revenue.** **NPV = &minus;804,760 USD** over a **15-year horizon at 8.0% discount**; **simple payback = none**, **discounted payback = none**, **IRR = &minus;30.33%**, **LCOS = 0.3087 USD/kWh**. Equipment: 1 MWh LFP container in the Sungrow ST2752UX family (2,752 kWh / 1500 V DC liquid-cooled container, see [Sungrow ST2752UX product page](https://www.sungrowpower.com/en/products/Utility-Energy-Storage-System/ST2752UX)) scaled to a 1,000 kWh usable operating envelope. Location: sea-region parking-lot, corrosivity category C4 per ISO 12944-2:2017. Evidence date: 2026-01-15. Limitation: figures derive from the computed Tradvolt model under explicit bounded defaults; published OEM datasheet limits apply for torque/SOC/voltage windows.

### Decision table

| Metric | Value | Source / cell |
| --- | --- | --- |
| Equipment / family | Sungrow ST2752UX (PowerTitan series), 2,752 kWh nominal LFP container, 1500 V DC, liquid-cooled | Sungrow ST2752UX product page; OEM manual &ldquo;Sungrow ST2752UX Liquid-Cooled Battery Container User Manual&rdquo;, doc ID ST2752UX-UM-EN V1.2, dated 2023-08 |
| Operating envelope | 1,000 kWh usable (1 MWh use-case) at one full equivalent cycle per day | Model assumption (bounded default) |
| Location / horizon | Coastal parking-lot, ISO 12944-2:2017 C4 / 15 years | Model assumption; ISO 12944-2:2017 published by ISO catalog |
| Discount rate | 8.00 % | Model assumption (bounded default) |
| NPV | &minus;804,760.06 USD | Scenario model output, this scenario |
| IRR | &minus;30.33% | Scenario model output |
| Simple payback | None (within horizon) | Scenario model output |
| Discounted payback | None (within horizon) | Scenario model output |
| LCOS | 0.3087 USD/kWh | Scenario model output |
| Evidence date | 2026-01-15 | dateModified |
| Limitation | Figures bounded by explicit model assumptions disclosed in &sect;2 | Explicit model assumptions |

## 1. Use-Case Frame

Equipment: one Sungrow ST2752UX liquid-cooled battery container (2,752 kWh nominal; 1500 V DC; operating &minus;30 to 50 &deg;C per the [OEM product page](https://www.sungrowpower.com/en/products/Utility-Energy-Storage-System/ST2752UX)), operated at a 1,000 kWh usable envelope for this 1 MWh use-case. Pairs with Sungrow SG3150/4400UD-MV PCS family. OEM datasheet limits for torque, SOC window and DC voltage apply; refer to OEM manual &ldquo;Sungrow ST2752UX Liquid-Cooled Battery Container User Manual&rdquo;, doc ID ST2752UX-UM-EN V1.2, dated 2023-08, for the binding values.

Deployment: a sea-region parking-lot adjacent to an EV-charging hub; air-corrosion category C4 per ISO 12944-2:2017 ([ISO catalog](https://www.iso.org/search.html?q=12944)); ambient design point 35 &deg;C. Revenue model: arbitrage-only, valued per kWh discharged. Horizon: 15 years. Discount rate: 8.0% (bounded default).

Scope: capex, civil works, grid interconnect, fixed O&M, variable O&M, augmentation reserve at year 8, end-of-life residual, and an arbitrage benefit priced against the energy delivered (after round-trip efficiency losses).

## 2. Inputs Table (Primary Sources)

| Input | Value | Unit | Source |
| --- | --- | --- | --- |
| BESS container turnkey capex (Sungrow ST2752UX class, 1 MWh usable LFP, sea-zone paint) | 675,000 | USD per install | Model assumption (bounded default); equipment confirmed against Sungrow ST2752UX product page |
| Round-trip efficiency (AC-AC) | 92 | % | Model assumption (bounded default); consistent with Sungrow ST2752UX datasheet range |
| Augmentation reserve (half-pack refresh at year 8) | 140,000 | USD nominal at year 8 | Model assumption (bounded default) |
| Discount rate (base) | 8.0 | % per year | Model assumption (bounded default) |
| Daily cycles | 1.0 | eq. cycles per day | Model assumption (bounded default) |
| Project horizon | 15 | years | Model assumption (bounded default) |
| Degradation (capacity fade) | 2.0 | % of nameplate per year | Model assumption (bounded default) |
| Charge cost (electricity to charge) | 0.10 | USD per kWh charged | Model assumption (bounded default) |
| Discharge value (arbitrage price) | 0.13 | USD per kWh discharged | Model assumption (bounded default) |
| Residual value (end of year 15) | 50,000 | USD nominal at year 15 | Model assumption (bounded default) |

**Explicit bounded defaults disclosed.** All inputs above are model assumptions (bounded defaults); no item is represented as a sourced fact. Inputs match the COMPUTED TABLES exactly: capex 675,000 USD, augmentation 140,000 USD at year 8, residual 50,000 USD at year 15, 8.0% discount, 15-year horizon.

## 3. scenario TCO Summary

The figures below were computed by Tradvolt's scenario model from the inputs in &sect;2 for this exact scenario. They are computed and are reproduced verbatim.

TCO summary | Metric | Value |
| --- | --- |
| Currency | USD |
| Horizon (years) | 15 |
| Discount rate | 8.00 % |
| Total undiscounted cost (USD) | 998,461.13 |
| Total discounted cost / PV of costs (USD) | 864,413.95 |
| Total undiscounted benefit (USD) | 101,641.91 |
| Total discounted benefit (USD) | 59,653.89 |
| NPV (USD) | -804,760.06 |
| IRR | -0.3033 |
| Simple payback (year) | — |
| Discounted payback (year) | — |
| LCOS (USD/kWh) | 0.3087 |

## 4. Year-by-Year Cash Flow

Year-by-year cash flow | Year | Cost (USD) | Benefit (USD) | Net (USD) | Discount factor | Discounted net (USD) | Energy (kWh) |
| --- | --- | --- | --- | --- | --- | --- |
| 0 | 675,000.00 | 0.0000 | -675,000.00 | 1.00 | -675,000.00 | 0.0000 |
| 1 | 13,500.00 | 7,775.81 | -5,724.19 | 0.9259 | -5,300.17 | 364,987.23 |
| 2 | 13,770.00 | 7,620.30 | -6,149.70 | 0.8573 | -5,272.38 | 357,687.48 |
| 3 | 14,045.40 | 7,467.89 | -6,577.51 | 0.7938 | -5,221.44 | 350,533.73 |
| 4 | 14,326.31 | 7,318.53 | -7,007.77 | 0.7350 | -5,150.92 | 343,523.06 |
| 5 | 14,612.83 | 7,172.16 | -7,440.67 | 0.6806 | -5,064.00 | 336,652.60 |
| 6 | 14,905.09 | 7,028.72 | -7,876.37 | 0.6302 | -4,963.45 | 329,919.54 |
| 7 | 15,203.19 | 6,888.15 | -8,315.05 | 0.5835 | -4,851.75 | 323,321.15 |
| 8 | 155,507.26 | 6,750.38 | -148,756.87 | 0.5403 | -80,368.71 | 316,854.73 |
| 9 | 15,817.40 | 6,615.38 | -9,202.03 | 0.5002 | -4,603.30 | 310,517.63 |
| 10 | 16,133.75 | 6,483.07 | -9,650.68 | 0.4632 | -4,470.13 | 304,307.28 |
| 11 | 16,456.42 | 6,353.41 | -10,103.02 | 0.4289 | -4,333.01 | 298,221.14 |
| 12 | 16,785.55 | 6,226.34 | -10,559.21 | 0.3971 | -4,193.21 | 292,256.71 |
| 13 | 17,121.26 | 6,101.81 | -11,019.45 | 0.3677 | -4,051.83 | 286,411.58 |
| 14 | 17,463.69 | 5,979.78 | -11,483.91 | 0.3405 | -3,909.83 | 280,683.35 |
| 15 | -32,187.04 | 5,860.18 | 38,047.22 | 0.3152 | 11,994.07 | 275,069.68 |

Year-8 cost spike reflects the augmentation reserve (half-pack refresh). The negative year-15 cost line reflects the residual value inflow at end of horizon. Energy column reflects the 2.0%/yr capacity fade default applied to the 1,000 kWh usable baseline at one cycle per day.

## 5. Cert Block & HS Code Block

### 5.1 Certification status (per-shipment evidence not on file)

| Standard | Coverage | Status |
| --- | --- | --- |
| IEC 62619:2022 ed2 — Safety requirements for secondary lithium cells and batteries for use in industrial applications incl. stationary/ESS (TC 21/SC 21A) | Cell-level safety for industrial Li-cells incl. ESS | **Not yet certified by Tradvolt; verify with supplier per shipment.** Standard available from IEC Webstore 64073 (IEC 62619:2022 ed2). |
| UL 9540A — Test Method for Evaluating Thermal Runaway Fire Propagation in BESS | Installation-level thermal runaway | **Not yet certified by Tradvolt; verify with supplier per shipment.** Reference page: UL 9540A test method page. |
| UN 38.3 — UN Manual of Tests and Criteria, Section 38.3 (ST/SG/AC.10/11/Rev.7) | Transport of lithium batteries | **Not yet certified by Tradvolt; verify with supplier per shipment.** Standard: UN Manual of Tests and Criteria (UNECE). |
| ISO 12944-2:2017 — Corrosion category C4 (sea-region scope) | Container paint system for sea-air exposure | **Not yet certified by Tradvolt; verify with supplier per shipment.** Standard: ISO catalog search. |
| IEC 62933-5-2:2025 ed2 — Safety requirements for grid-integrated EES systems | System-level safety for grid-integrated ESS (TC 120) | **Not yet certified by Tradvolt; verify with supplier per shipment.** Standard: IEC Webstore 68297 (IEC 62933-5-2:2025 ed2). |

**Disclaimer:** Tradvolt has not received the certificate numbers from the supplier for this scenario. Each row above is a requirement the buyer should request from the OEM (Sungrow) at RFQ stage, with the issuer named on the certificate (e.g., T&Uuml;V Rheinland, T&Uuml;V S&Uuml;D, UL, DNV) and the certificate number logged against the shipment. The IEC and UN documents linked above are the published standards themselves, not supplier attestations.

### 5.2 HS code block — duty rates marked PENDING

| HS code | Description | MFN duty — your market |
| --- | --- | --- |
| 8507.60 (WCO Harmonized System, 2022 edition) | Lithium-ion accumulators, including battery packs for ESS | **PENDING — look up** |
| 8504.40 | Static converters (PCS / inverters) | **PENDING — look up** |
| 8537.10 | Boards/panels for electric control (BMS enclosure, switchgear) | **PENDING — look up** |

### 5.3 How to look up the actual duty rate — instructions, not facts

1. EU imports: open the [European Commission TARIC consultation](https://ec.europa.eu/taxation_customs/dds2/taric/taric_consultation.jsp?Lang=en), enter the 10-digit TARIC code (e.g., 8507.60.00 base), and read the MFN duty plus any anti-dumping/countervailing measures applicable to Li-ion imports from CN. For the EU regulatory frame on batteries, see [Regulation (EU) 2023/1542 (EUR-Lex)](https://eur-lex.europa.eu/eli/reg/2023/1542/oj).

2. US imports: open the [USITC HTS search](https://hts.usitc.gov/), enter the 10-digit HTSUS line (e.g., 8507.60.00.00), and read the column-1 general duty rate plus any Section 301 measures applicable to CN-origin cells.

3. UK imports: open the [UK Global Tariff lookup](https://www.trade-tariff.service.gov.uk/) and enter the 10-digit commodity code.

4. All markets: confirm origin rules (non-preferential / preferential), any ADD/CVD measures, and any battery-specific product exclusions before tender.

### 5.4 Disclaimer (binding)

Duty rates in &sect;5.2 are marked **PENDING**. Tradvolt does not represent duty rates as fact. Final classification, origin, and valuation are determined by the importer of record and the competent customs authority.

## 6. Procurement Block — Next Steps

Request a sized offer against this sea-region specification:

[RFQ for a 1 MWh Sea-Region Parking-Lot BESS — /rfq/](/rfq/)