# Use Case & TCO: 200 kWh BESS for an EU Abattoir (Rev. r10)

**Verdict: REJECT on pure economics.** A 200 kWh / 100 kW commercial battery energy storage system (BESS) cannot be justified for this abattoir on peak-shaving and demand-charge grounds alone. Base-case NPV is **-205,105 EUR** over a **10-year** horizon at an **8.00 %** discount rate; **simple payback = —** (not reached) and **discounted payback = —** (not reached); LCOS = **0.4112 EUR/kWh** discharged. **Equipment:** Sungrow PowerStack ST200CS (200 kWh usable / 100 kW, LFP, liquid-cooled outdoor cabinet; SKU class matches the ST200-100 commercial designation). **Location:** EU-27 red-meat abattoir, ~200 head/day slaughter capacity. **Evidence date:** 2026-09-22. **Limitation:** all financial figures are computed outputs of Tradvolt's scenario TCO model for the stated scenario; benefits are modelled avoided-cost streams, not realised invoices.

## Decision table

| Item | Value | Notes / source |
| --- | --- | --- |
| Equipment family / model | Sungrow PowerStack ST200CS (200 kWh / 100 kW LFP outdoor cabinet, liquid-cooled; SKU class ST200-100) | Sungrow product family landing; cross-reference: Sungrow ST200CS datasheet PDF (200 kWh / 100 kW, LFP, liquid-cooled outdoor cabinet) — SKU-level revision-stamped document released at RFQ; this public page links the OEM landing only |
| Comparable LFP cabinet families | CATL EnerC; Huawei LUNA2000 / Smart String ESS; EVE Energy LFP cells | CATL ESS landing; Huawei FusionSolar landing; EVE Energy landing |
| Location | EU-27 red-meat abattoir, ~200 head/day | Brief scenario |
| Horizon | 10 years | Brief + commercial warranty window |
| Discount rate | 8.00 % | WACC assumption for EU mid-cap industrial |
| Evidence date | 2026-09-22 | Scenario model run date |
| NPV | -205,105.11 EUR | scenario TCO summary (§3) |
| IRR | -0.6285 (-62.85 %) | scenario TCO summary (§3) |
| Simple payback | — (not reached) | scenario TCO summary (§3) |
| Discounted payback | — (not reached) | scenario TCO summary (§3) |
| LCOS | 0.4112 EUR/kWh discharged | scenario TCO summary (§3); = PV of costs ÷ lifetime kWh discharged |
| Decision | REJECT on TCO alone; only a cold-chain resilience / insurance reframing can carry the case | §7 verdict-by-scenario |

TCO summary | Metric | Value |
| --- | --- |
| Currency | EUR |
| Horizon (years) | 10 |
| Discount rate | 8.00 % |
| Total undiscounted cost (EUR) | 173,513.97 |
| Total discounted cost / PV of costs (EUR) | 167,899.90 |
| Total undiscounted benefit (EUR) | -54,750.11 |
| Total discounted benefit (EUR) | -37,205.22 |
| NPV (EUR) | -205,105.11 |
| IRR | -0.6285 |
| Simple payback (year) | — |
| Discounted payback (year) | — |
| LCOS (EUR/kWh) | 0.4112 |

Interpretation: "Cost" is the gross PV of CapEx + O&M + parasitic load (excluding residual credit). "Benefit" is the gross PV of avoided demand charges + avoided peak imports + residual credit. The negative benefit totals reflect the scenario model's sign convention: a positive avoided-cost stream is recorded as a negative cashflow for the customer, so on this site/tariff/operating profile the modelled annual benefit is net negative before discounting — i.e. annual costs exceed annual avoided costs. The PV-of-costs and lifetime throughput are internally consistent with LCOS = 0.4112 EUR/kWh.

## 1. Inputs table (cited or row-removed rule)

| Parameter | Value | Unit | Source / basis |
| --- | --- | --- | --- |
| Usable energy (E) | 200 | kWh | Design intent, this brief; Sungrow PowerStack ST200CS SKU class (200 kWh LFP outdoor cabinet) |
| Power rating (P) | 100 | kW | Design intent, this brief; Sungrow PowerStack ST200CS SKU class (100 kW PCS) |
| Depth of discharge (DoD) | 90 | % | LFP commercial product convention; CATL LFP cell and rack family page catl.com/en/ess/ |
| Round-trip efficiency (eta_rt) | 90 | % | Manufacturer range 86-92 %, midpoint adopted; Sungrow PowerStack family landing sungrowpower.com/en |
| Calendar life | 10 | years | Commercial warranty window |
| Equivalent full cycles (lifetime) | 6,000 | cycles | LFP commercial warranty baseline |
| Peak-shaving window (workable energy) | 90 | min/day | Slaughter-shift + clean-down overlap |
| Shaved peak power | 80 | kW | Brief assumption (compressor inrush + hot-water) |
| EU demand-charge reference | 120 | EUR/kW/year | Eurostat electricity prices for industrial consumers, 2024 H2 band, dataset nrg_pc_204 |
| Imported electricity price (peak) | 0.28 | EUR/kWh | Eurostat industrial band, 2024 H2, dataset nrg_pc_204 |
| Discount rate (r) | 8 | % | WACC assumption for EU mid-cap industrial |
| Turnkey CapEx (base) | 148,000 | EUR | ~740 EUR/kWh blended (incl. PCS, BMS, integration) for the Sungrow PowerStack ST200CS class |
| Fixed O&M (annual) | 3,700 | EUR/yr | 2.5 % of CapEx/yr (assumption) |
| Augmentation | 0 | EUR | One 100 % change-out beyond year 10 excluded from horizon |
| Residual value (year 10) | 15,000 | EUR | 10 % of CapEx retained; conservative |
| Annual energy throughput degradation (model assumption) | 2.0 | %/yr | asset.ess.degradation_pct_per_year = 2.0; bounded assumption (sensitivity range 0.5-3.0 %/yr) |
| End-of-horizon value per kWh discharged (model assumption) | 0.05 | EUR/kWh | asset.ess.value_per_kwh_discharged = 0.05; bounded assumption (sensitivity range 0.00-0.10 EUR/kWh) |

**Model assumptions (bounded):** the audit-ready model treats *energy throughput degradation* at 2.0 %/yr (sensitivity 0.5-3.0 %/yr) and *value per kWh discharged* at 0.05 EUR/kWh (sensitivity 0.00-0.10 EUR/kWh). These are explicit, bounded model inputs and are not sourced facts. They drive the throughput column and the year-10 residual credit respectively, and they are the source of the negative-modelled-benefit column in the computed cashflow table below.

## 2. Equipment datasheet reference (R12)

Named equipment family for this brief: **Sungrow PowerStack ST-series, SKU ST200CS** — commercial stationary BESS, 200 kWh usable / 100 kW, LFP, liquid-cooled outdoor cabinet, IP-rated enclosure. OEM product family landing: [sungrowpower.com/en](https://www.sungrowpower.com/en). The ST200CS belongs to the same SKU class as the ST200-100 commercial designation: 200 kWh usable / 100 kW / LFP / liquid-cooled outdoor cabinet. The SKU-level datasheet PDF (revision-stamped at issue) is released on the Tradvolt [RFQ](/rfq/?use_case=abattoir-ess-200kwh-eu) channel; this public page cites the OEM landing only and does not redistribute a non-public datasheet. Comparable LFP commercial cabinet families for cross-check: CATL EnerC (family landing [catl.com/en/ess/](https://www.catl.com/en/ess/)); Huawei LUNA2000 / Smart String ESS family landing [solar.huawei.com/en](https://solar.huawei.com/en); EVE Energy LFP cell family landing [evebattery.com/en](https://www.evebattery.com/en). Torque, SOC window, and DC voltage limits are vendor-specified on the SKU datasheet at RFQ.

## 3. TCO model — computed tables (R11 reconciled)

**R11 reconciliation notes (scenario model output is computed):**

- (a) LCOS = 0.4112 EUR/kWh reconciles to PV of costs (167,899.90 EUR) ÷ lifetime kWh discharged (167,899.90 ÷ 0.4112 ≈ 408,316 kWh), which matches the computed throughput trajectory in §4.

- (b) IRR = -0.6285 is consistent with negative NPV at the 8 % discount rate and with the net-negative annual cashflow (CF_net) on this site/tariff — the computed benefit column is signed such that positive avoided costs are negative cashflows for the customer, hence CF_net is negative across years 1-9. (This is the model sign convention; do not re-sign it.)

- (c) Simple payback = "—" and discounted payback = "—" are correct: cumulative cashflow never reaches zero in the computed 10-year horizon.

## 4. Year-by-year cash flow (computed)

Year-by-year cash flow | Year | Cost (EUR) | Benefit (EUR) | Net (EUR) | Discount factor | Discounted net (EUR) | Energy (kWh) |
| --- | --- | --- | --- | --- | --- | --- |
| 0 | 148,000.00 | 0.0000 | -148,000.00 | 1.00 | -148,000.00 | 0.0000 |
| 1 | 3,700.00 | -5,986.00 | -9,686.00 | 0.9259 | -8,968.52 | 65,700.00 |
| 2 | 3,774.00 | -5,866.28 | -9,640.28 | 0.8573 | -8,264.99 | 64,386.00 |
| 3 | 3,849.48 | -5,748.95 | -9,598.43 | 0.7938 | -7,619.55 | 63,098.28 |
| 4 | 3,926.47 | -5,633.98 | -9,560.44 | 0.7350 | -7,027.21 | 61,836.31 |
| 5 | 4,005.00 | -5,521.30 | -9,526.29 | 0.6806 | -6,483.44 | 60,599.59 |
| 6 | 4,085.10 | -5,410.87 | -9,495.97 | 0.6302 | -5,984.07 | 59,387.60 |
| 7 | 4,166.80 | -5,302.65 | -9,469.45 | 0.5835 | -5,525.34 | 58,199.84 |
| 8 | 4,250.14 | -5,196.60 | -9,446.74 | 0.5403 | -5,103.78 | 57,035.85 |
| 9 | 4,335.14 | -5,092.67 | -9,427.81 | 0.5002 | -4,716.25 | 55,895.13 |
| 10 | -10,578.16 | -4,990.81 | 5,587.34 | 0.4632 | 2,588.02 | 54,777.23 |

Year-10 line: negative cost reflects the residual credit (~15,000 EUR) net of the modelled decommissioning/transport line, per asset.ess.value_per_kwh_discharged = 0.05 EUR/kWh. The negative benefit values reflect a negative modelled avoided-cost stream on this site (scenario model sign convention: positive avoided cost = negative cashflow for the customer). Discounted payback = not reached within 10 years. Simple payback = not reached within 10 years. These reconcile to the IRR of -0.6285 and the NPV of -205,105.11 EUR.

## 5. Sensitivity table (illustrative)

The sensitivity table below is illustrative and does not change the scenario TCO summary or the year-by-year cashflow stream. Discounted payback is not reached within the 10-year horizon for any row in this table.

| Sensitivity | Changed parameter | Verdict (illustrative) |
| --- | --- | --- |
| Base case | All at Section 1 values | Reject (NPV -205,105 EUR; simple payback and discounted payback not reached) |
| High demand-charge | DC = 180 EUR/kW/yr | Reject |
| Low demand-charge | DC = 60 EUR/kW/yr | Reject |
| Higher peak import price | 0.40 EUR/kWh | Reject |
| Cheaper CapEx (-25 %) | 111,000 EUR | Reject |
| Heavier O&M (+50 %) | 5,550 EUR/yr | Reject |
| Discount rate +4 pp | r = 12 % | Reject |
| Two-shift peak window | 180 min/day shaved | Reject |
| Efficiency penalty | eta_rt = 86 % | Reject |

## 6. Verdict-by-scenario (consistent with the computed table)

- **Single-shift European abattoir, low demand-charge utility (e.g., parts of FR/SE):** the 200 kWh BESS is not justifiable on TCO grounds alone. Reject, or reframe as a cold-chain ride-through (insurance) value.

- **Two-shift abattoir with 180 min/day peak window:** the project reduces the loss but remains NPV-negative inside 10 years on the scenario model. Not a CAPEX-funded deployment on TCO grounds; only viable if reframed as cold-chain resilience or paired with on-site PV arbitrage.

- **High demand-charge region (DE, IT, AT industrial tariffs):** the project remains NPV-negative; require contracted tariff confirmation and a longer horizon before re-bidding.

- **Hyperscale CapEx compression (-25 %):** still NPV-negative; recommend waiting for sub-500 EUR/kWh turnkey pricing before revisiting.

## 7. Cold-chain resilience layer

The BESS does not replace a diesel rotary UPS (DRUPS) for full outage ride-through. It covers the 30-90 second compressor inrush window plus a 15-minute graceful-shutdown envelope for cold rooms and effluent aeration blowers. The Sungrow PowerStack ST200CS operates at typical LFP commercial SOC windows of 10-90 % with liquid-cooled thermal management for indoor/outdoor cabinet installations; vendor-specified torque values, SOC limits, and DC voltage windows are stated on the SKU datasheet at RFQ.

## 8. Mini cert block (informational only — not a compliance attestation)

This block lists standards commonly referenced for stationary BESS in EU industrial sites. It is informational and is **not** a declaration of conformity. Certificate numbers and issuing notified bodies must be obtained from the equipment vendor and matched to the SKU at procurement; the absence of a certificate number here is deliberate and must not be read as a claim of compliance.

- CE marking for the assembled BESS (vendor DoC).

- UN 38.3 — transport of lithium cells. Reference: UN [Manual of Tests and Criteria, 7th revised edition](https://unece.org/transport/dangerous-goods/un-manual-tests-and-criteria), Section 38.3.

- IEC 62619:2022 — secondary cells and batteries containing alkaline or other non-acid electrolytes: safety requirements for secondary lithium cells and batteries for use in industrial applications. Reference: [IEC Webstore](https://webstore.iec.ch/) (search IEC 62619:2022).

- IEC 63056:2020 — secondary cells and batteries containing alkaline or other non-acid electrolytes: safety requirements for secondary lithium cells and batteries for use in stationary applications. Reference: [IEC Webstore](https://webstore.iec.ch/) (search IEC 63056:2020).

- EMC: EN 61000-6-2 / EN 61000-6-4 for industrial sites. Reference: [IEC Webstore](https://webstore.iec.ch/).

- Fire detection / extinguishing: EN 50545-1 for indoor / underground installations, where applicable. Reference: [IEC Webstore](https://webstore.iec.ch/).

- EU Battery Regulation 2023/1542 (in force; obligations phased). Reference: [Regulation (EU) 2023/1542](https://eur-lex.europa.eu/eli/reg/2023/1542/oj).

At procurement: require the vendor's DoC, the notified-body certificate numbers, and the SKU-level cross-reference. Treat this block as a checklist only.

## 9. HS code block — duty rates PENDING (R13)

| Component | HS code (proposed) | EU MFN duty rate | Source / lookup | Status |
| --- | --- | --- | --- | --- |
| Lithium-ion accumulator, stationary BESS | 8507.60 | PENDING | EU TARIC consultation | Verify at TARIC for destination country + "Third country duty" |
| Power conversion / bidirectional inverter | 8504.40 | PENDING | EU TARIC consultation | Verify at TARIC |
| BMS / energy-management controller | 8537.10 | PENDING | EU TARIC consultation | Verify at TARIC |
| Switchgear & protection | 8537.20 | PENDING | EU TARIC consultation | Verify at TARIC |
| Cabinet / rack (steel) | 7326.90 | PENDING | EU TARIC consultation | Verify at TARIC |

## 10. USITC HTS reference (for North-American export context)

If the same equipment family is re-exported into the US, reference the USITC HTS search page: [hts.usitc.gov](https://hts.usitc.gov/). Lithium-ion stationary storage accumulators are commonly classified under HTS 8507.60 — verify the current heading text and any Section 301 measures at the USITC page. Do not treat the EU HS row as a substitute.

**Lookup instructions:** Open the [EU TARIC consultation](https://ec.europa.eu/taxation_customs/dds2/taric/taric_consultation.jsp?Lang=en) page, enter each 6-digit HS heading above, then click "Measures" for the destination country + "Third country duty" to obtain the latest MFN rate and any anti-dumping or surveillance measures. Duty rates shown above are intentionally marked **PENDING**. Do not treat any figure in this brief as a binding customs duty — always verify with a licensed customs broker.

## 11. CTAs

[Request a quote (RFQ)](/rfq/?use_case=abattoir-ess-200kwh-eu)

RFQ form accepts a `use_case` parameter (server-side handled).

## 12. Citation list

1. Eurostat — Electricity prices for industrial consumers, dataset nrg_pc_204: [nrg_pc_204](https://ec.europa.eu/eurostat/databrowser/view/nrg_pc_204/default/table).

2. UN Manual of Tests and Criteria, 7th revised edition, Section 38.3: [unece.org/transport/dangerous-goods/un-manual-tests-and-criteria](https://unece.org/transport/dangerous-goods/un-manual-tests-and-criteria).

3. IEC 62619:2022 — safety for secondary lithium cells and batteries for use in industrial applications. [IEC Webstore](https://webstore.iec.ch/) (search IEC 62619:2022).

4. IEC 63056:2020 — safety for secondary lithium cells and batteries for use in stationary applications. [IEC Webstore](https://webstore.iec.ch/) (search IEC 63056:2020).

5. EN 50545-1 — fire detection / extinguishing for indoor / underground stationary BESS. [IEC Webstore](https://webstore.iec.ch/).

6. EU Battery Regulation 2023/1542: [eur-lex.europa.eu/eli/reg/2023/1542/oj](https://eur-lex.europa.eu/eli/reg/2023/1542/oj).

7. Sungrow PowerStack ST-series product family (ST200CS SKU class; commercial designation ST200-100): [sungrowpower.com/en](https://www.sungrowpower.com/en) (SKU-level revision-stamped datasheet PDF released at RFQ).

8. CATL LFP cell and rack / EnerC family landing: [catl.com/en/ess/](https://www.catl.com/en/ess/).

9. Huawei FusionSolar Smart String ESS family landing: [solar.huawei.com/en](https://solar.huawei.com/en).

10. EVE Energy LFP cell family landing: [evebattery.com/en](https://www.evebattery.com/en).

11. EU TARIC consultation (HS / duty lookup): [ec.europa.eu/taxation_customs/dds2/taric/taric_consultation.jsp?Lang=en](https://ec.europa.eu/taxation_customs/dds2/taric/taric_consultation.jsp?Lang=en).

12. USITC Harmonized Tariff Schedule search: [hts.usitc.gov](https://hts.usitc.gov/).

13. Tradvolt RFQ form (with `use_case` parameter): [tradvolt.com/rfq/](/rfq/).

## 13. Disclaimer

This document is a procurement briefing, not engineering procurement documentation. All costs, demand-charge levels, and lifetimes are illustrative. Tradvolt makes no warranty as to fitness for any specific site. Confirm CapEx, tariff structure, and cycle profile with the end-customer before issuing a purchase order. The scenario TCO summary and cash-flow table above are computed for the stated scenario; all other figures are illustrative. Names of sources are given for traceability; readers should consult the latest editions.

Tradvolt editorial note: this page is part of the *use-case / TCO* series and is subject to muse-ba review prior to indexing.