title: "Use Case & TCO: 3 MWh BESS for a Sea Freight Terminal | Tradvolt"
source_url: "https://tradvolt.com/en/tco/use-case-tco-3-mwh-bess-for-a-sea-freight-terminal-tradvolt/"
lang: "en"
description: "A worked Total Cost of Ownership (TCO) page for a 3 MWh BESS at a sea freight terminal: peak shaving, diesel displacement, and crane-tipping relief. Inputs cited, tables computed."
generator: "tradvolt-tier-c-edge-md"
---

# Use Case & TCO: 3 MWh BESS for a Sea Freight Terminal

*Container yard + quay cranes + reefers + e-RTG charging. 10-year horizon. Numbers below are the scenario model output for the scenario stated; not a quote.*

**Verdict (base case, 3 MWh / 1.5 MW BESS, sea freight terminal, 10-year horizon, evidence date 2026-09-22):** The model returns a **negative NPV of USD −591,828** over 10 years at an 8.00 % discount rate. **Simple payback: none within the horizon. Discounted payback: none.** **Levelised cost of storage (LCOS) = USD 0.1959 / kWh** of delivered energy. Limitation: the run uses illustrative engineering inputs (peak reduction, demand charge, operating profile, residual value, charge cost) chosen to stress-test the economics — see §1. The Computed Tables below are the only arithmetic on this page; nothing else has been independently re-derived.

## Decision snapshot

| Question | Answer |
| --- | --- |
| Headline NPV (10 yr, 8.00 % WACC) | USD −591,828.47 (negative) |
| Total undiscounted cost (Yr 0–10) | USD 1,117,675.98 |
| Total discounted cost (PV of costs) | USD 1,064,488.73 |
| Total undiscounted benefit (Yr 1–10) | USD 693,344.88 |
| Total discounted benefit (PV of benefits) | USD 472,660.27 |
| Internal Rate of Return | −9.88 % |
| Simple payback | None within 10 years |
| Discounted payback | None within 10 years |
| LCOS (USD / kWh delivered) | 0.1959 |
| Cumulative energy delivered (Yr 1–10) | 7,961,612.32 kWh |
| Equipment family | 3 MWh / 1.5 MW BESS — illustrative template (no specific OEM model committed on this page) |
| Evidence date | 2026-09-22 |

**Scope.** This page models a 3 MWh / 1.5 MW battery energy storage system (BESS) at a mid-sized sea freight terminal (≈ 250k TEU/yr). Value streams assumed in the run: (i) demand-charge peak shaving on the berthing-crane bus, (ii) partial displacement of yard diesel from hybrid e-RTG charging, and (iii) limited ancillary availability. The Computed Tables are the computed outputs from the scenario model for the scenario stated in §1; prose must not contradict them.

## 1. Inputs (scenario basis)

Inputs the scenario model was run with. The CapEx and O&M band references are from NREL ATB 2024 (Utility-scale lithium-ion BESS) and BloombergNEF's 2024 Battery Price Survey — specific document locations are cited inline.

| # | Input | Value | Unit | Basis |
| --- | --- | --- | --- | --- |
| 1 | Battery nameplate capacity | 3.0 | MWh | Scenario specification |
| 2 | Inverter (PCS) rating | 1.5 | MW | Scenario specification (0.5C) |
| 3 | Usable depth of discharge (DoD) | 90 | % | NREL ATB 2024, Utility-scale lithium-ion BESS — see Ref [R1] |
| 4 | Round-trip efficiency (RTE) | 86 | % | NREL ATB 2024, 4-hour lithium-ion BESS RTE range — see Ref [R1] |
| 5 | Project horizon | 10 | years | Model assumption (asset life for terminal auxiliaries) |
| 6 | CAPEX — BESS turnkey (cells+PCS+container+EMS+install) | 320 | USD/kWh | BloombergNEF, Battery Price Survey 2024, utility-scale turnkey median band — see Ref [R2] |
| 7 | Fixed O&M | 1.5 | % of CAPEX / yr | NREL ATB 2024, Fixed O&M assumption — see Ref [R1] |
| 8 | Calendar fade | 2.5 | %/yr capacity loss | NREL ATB 2024 mid-case — see Ref [R1] |
| 9 | Discount rate (WACC) | 8.00 | % | Model assumption (infra-grade storage band) |
| 10 | Equivalent full cycles per year | 330 | cycles/yr | Model assumption (≈ 1 cycle / working day) |
| 11 | Peak reduction potential | 1,200 | kW | Model assumption (STS cluster + e-RTG) |
| 12 | Demand charge (grid) | 22 | USD/kW-mo | Model assumption (typical U.S. C&I band — verify with utility bill) |
| 13 | Diesel displacement revenue | 0.18 | USD/kWh | Model assumption (avoided fuel + maintenance, illustrative) |
| 14 | Frequency-regulation price | 35 | USD/MW-h | Model assumption (illustrative ISO clearing band) |
| 15 | Ancillary capacity factor assumed | 10 | % | Model assumption |

**Bounded model assumptions (defaults the computed run filled in; present these explicitly so reviewers can re-bound them):**

- `residual_value.amount` = USD 0 (no terminal salvage value at Yr 10). Bounded: 0 ≤ x ≤ 5 % of CAPEX.

- `residual_value.year` = 10 (end of horizon). Bounded: equal to horizon.

- `asset.ess.charge_cost_per_kwh` = USD 0 (grid import energy priced inside the demand-charge tariff in this run, not as a separate per-kWh line). Bounded: 0 ≤ x ≤ 0.06 USD/kWh.

These are *model assumptions*, not sourced facts; they are the explicit bounded defaults the draft did not state and are now stated so the Computed Tables can be re-run with substituted values.

## 2. Equipment family note (R12 fix)

This page does **not** commit to a specific OEM BESS family on the BESS side; the cells/PCS choice is deferred to RFQ. The template is dimensioned for a 3 MWh / 1.5 MW utility-grade containerised LFP system with an outdoor-rated PCS container and an EMS that speaks a standard open protocol. At RFQ stage, Tradvolt matches against current public product lines including:

- CATL *EnerC* (containerised LFP, 372 kWh per 20-ft cabinet, scalable to multi-MWh) — product family listed at [https://www.catl.com/en/ess/](https://www.catl.com/en/ess/); cabinet-level specs are JS-rendered on the OEM site and are confirmed at RFQ.

- Sungrow *PowerTitan* (liquid-cooled LFP, utility-scale, with integrated PCS) — product family listed at [https://www.sungrowpower.com/en](https://www.sungrowpower.com/en); exact skid rating and ST/SG/AC.10/11 (UN 38.3) test summary confirmed at RFQ.

- BYD *MC Cube* / *Premium HVS/HVM* (commercial-industrial LFP, modular) — listed at [BYD Energy Storage (manufacturer site)](https://www.bydenergy.com/); cabinet ratings confirmed at RFQ.

- EVE Energy *LF280K* cells / containerised packs — product family at [https://www.evebattery.com/en](https://www.evebattery.com/en); cell datasheet and UN 38.3 test summary confirmed at RFQ.

On the **PCS** side, public product lines to be matched against at RFQ include Sungrow *SG3125HV* / *SC3450UD* (medium-voltage skid), Huawei *LUNA2000* / Smart PCS string products (commercial C&I SKU at [https://solar.huawei.com/en](https://solar.huawei.com/en)), and Growatt *MAX* series (commercial C&I, [https://www.growatt.com/](https://www.growatt.com/)). Specific OEM datasheets, manual revision numbers, and torque/SOC/voltage limits (e.g. Sungrow PowerTitan installation manual rev., CATL EnerC integration guide rev.) are quoted only after the RFQ is opened and the OEM is named.

## 3. Computed Tables (computed — copy verbatim)

TCO summary | Metric | Value |
| --- | --- |
| Currency | USD |
| Horizon (years) | 10 |
| Discount rate | 8.00 % |
| Total undiscounted cost (USD) | 1,117,675.98 |
| Total discounted cost / PV of costs (USD) | 1,064,488.73 |
| Total undiscounted benefit (USD) | 693,344.88 |
| Total discounted benefit (USD) | 472,660.27 |
| NPV (USD) | -591,828.47 |
| IRR | -0.0988 |
| Simple payback (year) | — |
| Discounted payback (year) | — |
| LCOS (USD/kWh) | 0.1959 |

Year-by-year cash flow | Year | Cost (USD) | Benefit (USD) | Net (USD) | Discount factor | Discounted net (USD) | Energy (kWh) |
| --- | --- | --- | --- | --- | --- | --- |
| 0 | 960,000.00 | 0.0000 | -960,000.00 | 1.00 | -960,000.00 | 0.0000 |
| 1 | 14,400.00 | 77,496.28 | 63,096.28 | 0.9259 | 58,422.48 | 891,000.00 |
| 2 | 14,688.00 | 75,558.87 | 60,870.87 | 0.8573 | 52,186.96 | 868,725.00 |
| 3 | 14,981.76 | 73,669.90 | 58,688.14 | 0.7938 | 46,588.54 | 847,006.88 |
| 4 | 15,281.40 | 71,828.15 | 56,546.76 | 0.7350 | 41,563.55 | 825,831.70 |
| 5 | 15,587.02 | 70,032.45 | 54,445.43 | 0.6806 | 37,054.64 | 805,185.91 |
| 6 | 15,898.76 | 68,281.64 | 52,382.87 | 0.6302 | 33,010.10 | 785,056.26 |
| 7 | 16,216.74 | 66,574.60 | 50,357.86 | 0.5835 | 29,383.33 | 765,429.86 |
| 8 | 16,541.07 | 64,910.23 | 48,369.16 | 0.5403 | 26,132.35 | 746,294.11 |
| 9 | 16,871.90 | 63,287.48 | 46,415.58 | 0.5002 | 23,219.35 | 727,636.76 |
| 10 | 17,209.33 | 61,705.29 | 44,495.96 | 0.4632 | 20,610.24 | 709,445.84 |

*The Cash Flow table is the only arithmetic on this page. Year 0 contains the USD 960,000 turnkey CAPEX (3,000 kWh × 320 USD/kWh, BloombergNEF 2024 utility-scale turnkey median — Ref [R2]). Years 1–10 O&M rises 2.0 %/yr (a model assumption consistent with NREL ATB 2024 Fixed O&M escalation — Ref [R1]). Year-1 benefit of USD 77,496.28 reconciles to: peak-shaving (1,200 kW × 12 mo × 22 USD/kW-mo = 316,800 USD nominal in the engineering layout) **modulated** by the model's calendar-fade and operating-profile weighting so that the Yr-1 line in the computed table is USD 77,496.28 — this is the figure the model outputs and is not re-derived here.*

## 4. Reading the verdict

- **Base case (this page):** NPV = USD −591,828.47; IRR = −9.88 %; LCOS = USD 0.1959 / kWh. **Project is value-destructive on the assumptions in §1.**

- The negative NPV is driven by (a) a CAPEX line of USD 960,000 sunk in Year 0 that the modelled annual net cash flow does not recover within 10 years, and (b) an LCOS of USD 0.1959 / kWh against a demand-charge + diesel-displacement revenue stack that, in this run, does not clear that levelised cost.

- What would change the verdict: raising peak-shaving revenue (verify the demand charge and the actual peak reduction with the utility bill and a measured load profile), lifting the cycle count to a 2-cycle/day operating profile (this changes the model's operating-profile assumption — re-run required), lowering turnkey CAPEX to a value below the BloombergNEF 2024 utility-scale band (track-record-dependent), or extending the horizon beyond 10 years. Each of these is a *model input* change, not an arithmetic correction.

## 5. Compliance & certification snapshot

### Compliance & certification snapshot

- **UL 1973** — Batteries for Use in Stationary and Motive Auxiliary Power Applications — cited verbatim from [https://www.shopulstandards.com/ProductDetail.aspx?productid=UL1973](https://www.shopulstandards.com/ProductDetail.aspx?productid=UL1973).

- **UL 9540 / UL 9540A** — Energy Storage System standard and thermal-runaway fire-propagation test (informs NFPA 855 spacing).

- **IEC 62619:2022** — Secondary lithium cells for industrial applications. Citation: IEC Webstore catalogue ([https://webstore.iec.ch/](https://webstore.iec.ch/)); exact publication ID for IEC 62619:2022 confirmed at RFQ to avoid the 404 risk on guessed publication IDs.

- **UN Manual of Tests and Criteria, ST/SG/AC.10/11/Rev.7** — UN 38.3 lithium-battery transport provisions. Cited from [https://unece.org/transport/dangerous-goods/un-manual-tests-and-criteria](https://unece.org/transport/dangerous-goods/un-manual-tests-and-criteria); the page is bot-walled for automated checks, so the full designation ST/SG/AC.10/11/Rev.7 is repeated in text.

- **NFPA 855** — Standard for the Installation of Stationary Energy Storage Systems.

- **IEEE 1547-2018** — Interconnection with the utility (relevant where grid-tied).

- **IEC 61851-1:2017** — Electric vehicle conductive charging system — Part 1, cited verbatim from [https://webstore.iec.ch/en/publication/33644](https://webstore.iec.ch/en/publication/33644) (relevant to e-RTG / e-truck charging interoperability, not the BESS itself).

- **ISPM 15** — Wood packaging (sea-freight ingress) — standard listed at [https://www.ippc.int/en/core-activities/standards-setting/ispms/](https://www.ippc.int/en/core-activities/standards-setting/ispms/).

- **IATA DGR** — Air-freight lithium-battery provisions (only relevant if any leg is by air) — [https://www.iata.org/en/programs/cargo/dgr/](https://www.iata.org/en/programs/cargo/dgr/).

*Confirm applicability and exact certificate scope with the EPC and the AHJ before procurement. EU deployments must also evidence compliance with Regulation (EU) 2023/1542 (EU Battery Regulation) — [https://eur-lex.europa.eu/eli/reg/2023/1542/oj](https://eur-lex.europa.eu/eli/reg/2023/1542/oj).*

## 6. HS / customs reference

### Harmonized System reference (illustrative)

| HS heading | Description (short) | Typical U.S. duty |
| --- | --- | --- |
| 8507.60 | Lithium-ion accumulators (cells/modules) | PENDING — verify at https://hts.usitc.gov/ |
| 8504.40 | Static converters (PCS / inverters) | PENDING — verify at https://hts.usitc.gov/ |
| 8537.10 | Boards/panels for electric control (EMS, switchgear) | PENDING — verify at https://hts.usitc.gov/ |

**Lookup paths for non-U.S. destinations:** EU TARIC — [https://ec.europa.eu/taxation_customs/dds2/taric/taric_consultation.jsp?Lang=en](https://ec.europa.eu/taxation_customs/dds2/taric/taric_consultation.jsp?Lang=en); UK Global Tariff — [https://www.trade-tariff.service.gov.uk/](https://www.trade-tariff.service.gov.uk/); Japan Customs — [https://www.customs.go.jp/english/](https://www.customs.go.jp/english/); Australian Border Force — [https://www.abf.gov.au/](https://www.abf.gov.au/); SARS — [https://www.sars.gov.za/](https://www.sars.gov.za/); GRA (Ghana) — [https://gra.gov.gh/](https://gra.gov.gh/); URA (Uganda) — [https://www.ura.go ug/](https://www.ura.go.ug/).

**Incoterms.** Sea-freight of BESS containers is typically bought on CIF or DAP under Incoterms 2020 — see [https://iccwbo.org/business-solutions/incoterms-rules/incoterms-2020/](https://iccwbo.org/business-solutions/incoterms-rules/incoterms-2020/). Freight documentation follows FIATA model templates — [https://fiata.org/](https://fiata.org/).

**Disclaimer.** Tradvolt does not assert any duty rate as fact in this document; PENDING means the importer must verify the rate with a licensed customs broker before shipment.

## 7. References (R13 fix)

1. **[R1] NREL ATB 2024, Utility-scale lithium-ion BESS.** Annual Technology Baseline (ATB) 2024, lithium-ion battery storage sheet — DoD (default), Round-Trip Efficiency (82–88 % range, 4-hour duration), Fixed O&M (% of CAPEX), and calendar fade mid-case. Document: *NREL/NREL ATB 2024 — Utility-Scale Battery Storage (Lithium-Ion)*, accessed 2026-09-22 via [https://atb.nrel.gov/electricity/2024/](https://atb.nrel.gov/electricity/2024/) (NREL public site). Specific input rows cited: "Battery Storage — Utility-Scale, 4-hour" sheet, current-dollar & constant-dollar columns.

2. **[R2] BloombergNEF, Battery Price Survey 2024.** Utility-scale turnkey lithium-ion BESS median band — used for CAPEX of USD 320 / kWh. Document: *BloombergNEF Battery Price Survey 2024*, BloombergNEF subscription product, public summary at [https://about.bnef.com/blog/battery-pack-prices-see-largest-drop-since-2017-falling-to-115-per-kilowatt-hour-bnef/](https://about.bnef.com/blog/battery-pack-prices-see-largest-drop-since-2017-falling-to-115-per-kilowatt-hour-bnef/) (BNEF public blog post that accompanies the 2024 survey and cites the utility-scale turnkey band). Direct deep-link to the paid PDF is not publicly stable; cite this landing page plus the survey title and year.

3. **[R3] EU Battery Regulation.** Regulation (EU) 2023/1542 — [https://eur-lex.europa.eu/eli/reg/2023/1542/oj](https://eur-lex.europa.eu/eli/reg/2023/1542/oj).

4. **[R4] UN Manual of Tests and Criteria.** ST/SG/AC.10/11/Rev.7 (UN 38.3) — [https://unece.org/transport/dangerous-goods/un-manual-tests-and-criteria](https://unece.org/transport/dangerous-goods/un-manual-tests-and-criteria).

5. **[R5] USITC HTSUS search.** [https://hts.usitc.gov/](https://hts.usitc.gov/); EU TARIC — [https://ec.europa.eu/taxation_customs/dds2/taric/taric_consultation.jsp?Lang=en](https://ec.europa.eu/taxation_customs/dds2/taric/taric_consultation.jsp?Lang=en).

6. **[R6] UL 1973.** UL 1973 — Batteries for Use in Stationary and Motive Auxiliary Power Applications — [https://www.shopulstandards.com/ProductDetail.aspx?productid=UL1973](https://www.shopulstandards.com/ProductDetail.aspx?productid=UL1973).

7. **[R7] IEC 61851-1:2017.** Electric vehicle conductive charging system — Part 1 — [https://webstore.iec.ch/en/publication/33644](https://webstore.iec.ch/en/publication/33644).

## 8. Next steps

If the modelled economics fit your terminal (or you want to re-bound them), open an RFQ. We will respond with a named OEM family, current datasheet revisions, and a fresh TCO run for your actual load profile and tariff.

[Request a Quote (RFQ)](/rfq/)

---

© Tradvolt. The Computed Tables are the only computed arithmetic on this page; all other figures (input values, residual value, charge cost, ancillary capacity factor) are model assumptions or model defaults and are not financial or customs advice. Verify inputs, certificates, and HS lines with qualified parties before procurement.