title: "Peak Shaving — Definition & China Sourcing Guide | Tradvolt Glossary"
source_url: "https://tradvolt.com/glossary/peak-shaving/"
lang: "en"
description: "Peak shaving dispatches on-site battery energy storage during intervals of maximum facility electrical load to cap utility kW demand and reduce monthly demand charges."
generator: "tradvolt-tier-c-edge-md"
---

[Tradvolt](/)

[← Glossary](/glossary/) · [Methods](/methods/)

# Peak Shaving

**Peak Shaving** is the dispatch of an on-site battery energy storage system or behind-the-meter solar-plus-storage plant during short intervals of maximum facility electrical load to cap peak kilowatt or megavolt-ampere demand drawn from the utility grid, reducing monthly capacity demand charges and avoiding costly upstream transformer or feeder upgrades.

## How it is measured and specified

Commercial and industrial (C&I) utility tariffs typically bill large electricity users on two separate meters: volumetric energy consumption (measured in kilowatt-hours, kWh) and peak power demand (measured in kilowatts, kW, or kilovolt-amperes, kVA, averaged over a 15-minute or 30-minute billing interval). A single 15-minute spike caused by chiller startup, bottling lines, or harbor crane lifting can set the billing peak for the entire month or trigger a full-year capacity ratchet.

To shave a facility peak reliably, an energy storage system must be specified across two independent engineering axes: **power conversion system (PCS) kilowatt rating** (which determines the maximum height of the load spike the battery can clip) and **usable energy storage duration in kilowatt-hours** (which determines how many consecutive hours the system can hold the grid import below the target demand threshold without exhausting its [depth of discharge](/glossary/depth-of-discharge/)).

## How it matters when sourcing from China

When C&I buyers import Chinese LFP storage cabinets or containerized BESS—such as CATL EnerC, Sungrow PowerStack ST500CP, BYD Cube Pro, or Hanchu ESS outdoor cabinets—sizing the PCS-to-battery ratio ([C-rate](/glossary/c-rate/)) around the site's actual load profile is critical. If the plateau of the facility's peak load lasts four hours but the buyer imports a 2-hour (0.5C) cabinet, the battery will deplete mid-window and fail to prevent the monthly demand charge. As highlighted in [how battery and storage TCO is modelled](/methods/battery-tco/), the site duty cycle governs both revenue capture and ten-year degradation.

Across Tradvolt's commercial storage studies, peak shaving frequently delivers the largest share of annual cash savings or stacks alongside [time-of-use (TOU)](/glossary/time-of-use/) arbitrage:

- In the [750 kWh / 250 kW EU bottling plant ESS TCO study](/en/tco/750-kwh-bottling-plant-ess-eu-tco-use-case-tradvolt-com/), a 3-hour (0.33C) LFP cabinet charges overnight and discharges across the 14:00–19:00 weekday peak window on 260 operating days per year, shaving 150 kW of billing peak at a demand charge of €18.50/kW/month (€33,300/yr in demand-charge savings) alongside €17,154/yr in Year-1 TOU arbitrage.

- In the [3 MWh / 1.5 MW India harbor BESS TCO study](/en/tco/3-mwh-harbor-battery-energy-storage-system-india-use-case-tco/), a 2-hour (0.5C) containerized LFP system stacks 1.0 MWh/day of peak shaving with 0.5 MWh/day of quay-crane regenerative energy capture and 0.5 MWh/day of cold-ironing shore power dispatch.

- In the [1 MWh / 500 kW Canada commercial peak-shaving LFP container study](/en/tco/import-lfp-container-ess-from-china-to-canada-1-mwh-commercial-peak-shaving-tco-tradvolt/), a 20-foot container clips 380 kW of monthly billing demand ($14.50/kW-month) while shifting 810 kWh/day across a 300-day commercial operating schedule.

## What to confirm before procurement

- Analyze at least 12 months of 15-minute utility interval meter data before selecting a 1-hour (1C), 2-hour (0.5C), or 3-to-4-hour (0.33C–0.25C) Chinese BESS configuration.

- Confirm that the Energy Management System (EMS) and external revenue-grade current transformers (CTs) at the point of common coupling are included in the supplier's scope and support closed-loop peak-shaving control.

- Account for annual battery capacity fade in your multi-year demand-shaving projection so Year-8 usable kilowatt-hours still cover the width of the peak load window.