Verdict (central scenario, 5,000 kWp ground-mount PV, 25-year horizon, 8.00% real discount, evidence date 2026-01-15): NPV USD 6,643,252, IRR 34.29%, simple payback 2.99 years, discounted payback 3.55 years, LCOE USD 0.0417 / kWh. Solar LCOE is 54–75% below the IEA 2025 SEA grid reference (USD 0.09–0.16/kWh) and 81% below the World Bank 2024 Indonesia diesel reference (USD 0.22/kWh). Recommendation: BUY in all three SEA market scenarios, with a BESS overlay for night-time SLA in Scenario C. Limitation: the LCOE figure is the 25-year levelized cost; it is not a one-year tariff and excludes import duty, VAT/GST, accelerated depreciation, and BESS capex (all site-specific overlays).
| Metric | Value | Unit |
|---|---|---|
| NPV | 6,643,252.03 | USD |
| IRR | 34.29 | % |
| Simple payback | 2.99 | year |
| Discounted payback | 3.55 | year |
| LCOE | 0.0417 | USD/kWh |
| Total PV of costs | 2,883,327.35 | USD |
| Total PV of benefits | 9,526,579.38 | USD |
| Self-consumption tariff (model default) | 0.12 | USD/kWh |
| Tariff escalation (model default) | 1.5 | %/yr (real) |
| Export tariff (model default) | 0.00 | USD/kWh |
Equipment: Jinko Solar Tiger Neo 625 W bifacial monocrystalline modules (8,000 units) + Sungrow SG250HX 250 kW string inverters (20 units), DC/AC ratio 1.25. HTWG Report 25-year limit is bounded by inverter re-stack at year 12 (Sungrow SG250HX Datasheet Rev. 12, 2024, §3 Service Life). Model defaults for tariff inputs are bounded assumptions, not sourced facts.
| Component | Model | Qty | OEM datasheet / manual | Operating limits cited |
|---|---|---|---|---|
| PV module | Jinko Solar Tiger Neo JKM625N-78HL4-BDV (bifacial monocrystalline PERC/TBC, 625 Wp) | 8,000 | Jinko Tiger Neo 625 W Datasheet (PDF) | Voc 56.4 V; Isc 14.20 A; Pmax 625 W; bifaciality 80±5%; 30-year linear power warranty (year-1 ≤1%, year 2–30 ≤0.40%/yr) |
| String inverter | Sungrow SG250HX (250 kW, 1500 Vdc) | 20 | Sungrow SG250HX Datasheet V12 (2024) | Max DC voltage 1500 V; MPPT range 860–1450 V; Max AC output 250 kVA; IP66; service life defined by inverter re-stack at year 12 (manual §3) |
| DC combiners / MV transformer | Sungrow MVS6750-LV (6,750 kVA pad-mount) | 1 | Sungrow MVS6750-LV Datasheet (PDF) | MV step-up 0.8/22 kV (site-dependent), ONAN cooling |
| Mounting structure | Aluminum ground-mount, fixed-tilt 10–15° (model: generic Schletter / K2 Systems-class single-post; final BoS pending EPC) | ~5 ha | — (BoS; not used to set any OEM limit) | — |
Limits above are taken directly from the linked OEM documents. Other parameters (e.g. SoC for any BESS overlay) are out of scope here.
| Metric | Value |
|---|---|
| Currency | USD |
| Horizon (years) | 25 |
| Discount rate | 8.00 % |
| Total undiscounted cost (USD) | 3,778,863.49 |
| Total discounted cost / PV of costs (USD) | 2,883,327.35 |
| Total undiscounted benefit (USD) | 23,611,084.54 |
| Total discounted benefit (USD) | 9,526,579.38 |
| NPV (USD) | 6,643,252.03 |
| IRR | 0.3429 |
| Simple payback (year) | 2.99 |
| Discounted payback (year) | 3.55 |
| LCOE (USD/kWh) | 0.0417 |
| Year | Cost (USD) | Benefit (USD) | Net (USD) | Discount factor | Discounted net (USD) | Energy (kWh) |
|---|---|---|---|---|---|---|
| 0 | 2,250,000.00 | 0.0000 | -2,250,000.00 | 1.00 | -2,250,000.00 | 0.0000 |
| 1 | 45,000.00 | 786,375.00 | 741,375.00 | 0.9259 | 686,458.33 | 6,750,000.00 |
| 2 | 45,900.00 | 798,091.99 | 752,191.99 | 0.8573 | 644,883.39 | 6,716,250.00 |
| 3 | 46,818.00 | 809,983.56 | 763,165.56 | 0.7938 | 605,825.43 | 6,682,668.75 |
| 4 | 47,754.36 | 822,052.31 | 774,297.95 | 0.7350 | 569,132.11 | 6,649,255.41 |
| 5 | 48,709.45 | 834,300.89 | 785,591.45 | 0.6806 | 534,660.34 | 6,616,009.13 |
| 6 | 49,683.64 | 846,731.98 | 797,048.34 | 0.6302 | 502,275.65 | 6,582,929.08 |
| 7 | 50,677.31 | 859,348.28 | 808,670.97 | 0.5835 | 471,851.75 | 6,550,014.44 |
| 8 | 51,690.86 | 872,152.57 | 820,461.72 | 0.5403 | 443,269.94 | 6,517,264.37 |
| 9 | 52,724.67 | 885,147.65 | 832,422.97 | 0.5002 | 416,418.73 | 6,484,678.04 |
| 10 | 53,779.17 | 898,336.34 | 844,557.18 | 0.4632 | 391,193.39 | 6,452,254.65 |
| 11 | 54,854.75 | 911,721.56 | 856,866.81 | 0.4289 | 367,495.49 | 6,419,993.38 |
| 12 | 255,951.84 | 925,306.21 | 669,354.36 | 0.3971 | 265,809.83 | 6,387,893.41 |
| 13 | 57,070.88 | 939,093.27 | 882,022.39 | 0.3677 | 324,317.80 | 6,355,953.95 |
| 14 | 58,212.30 | 953,085.76 | 894,873.46 | 0.3405 | 304,669.55 | 6,324,174.18 |
| 15 | 59,376.54 | 967,286.74 | 907,910.19 | 0.3152 | 286,211.16 | 6,292,553.31 |
| 16 | 60,564.08 | 981,699.31 | 921,135.23 | 0.2919 | 268,870.59 | 6,261,090.54 |
| 17 | 61,775.36 | 996,326.63 | 934,551.27 | 0.2703 | 252,580.19 | 6,229,785.09 |
| 18 | 63,010.86 | 1,011,171.90 | 948,161.03 | 0.2502 | 237,276.38 | 6,198,636.16 |
| 19 | 64,271.08 | 1,026,238.36 | 961,967.28 | 0.2317 | 222,899.42 | 6,167,642.98 |
| 20 | 65,556.50 | 1,041,529.31 | 975,972.81 | 0.2145 | 209,393.22 | 6,136,804.77 |
| 21 | 66,867.63 | 1,057,048.10 | 990,180.46 | 0.1987 | 196,705.04 | 6,106,120.74 |
| 22 | 68,204.99 | 1,072,798.11 | 1,004,593.13 | 0.1839 | 184,785.37 | 6,075,590.14 |
| 23 | 69,569.09 | 1,088,782.80 | 1,019,213.72 | 0.1703 | 173,587.67 | 6,045,212.19 |
| 24 | 70,960.47 | 1,105,005.67 | 1,034,045.20 | 0.1577 | 163,068.24 | 6,014,986.13 |
| 25 | -40,120.32 | 1,121,470.25 | 1,161,590.58 | 0.1460 | 169,613.02 | 5,984,911.20 |
Year-25 cost is shown as a negative because the page treats the residual/avoided-replacement credit as a cost-stream negative (the scenario model sums it the same way); the year-25 net cash flow of USD 1,161,590.58 already reflects this convention. Net position remains strongly positive.
| Input | Value used | Bound | Status |
|---|---|---|---|
| asset.pv.tariff_per_kwh | 0.12 USD/kWh | Bounded to 0.09–0.16 (IEA EMRE SEA July 2025) | Model assumption; recalc per site tariff |
| asset.pv.tariff_escalation_pct | 1.5 %/yr (real) | Bounded to 0–3 %/yr (TradVolt bounded set) | Model assumption |
| asset.pv.export_tariff_per_kwh | 0.00 USD/kWh | Bounded to 0–0.04 USD/kWh (PPA export regime) | Model assumption; sit-specific |
| Discount rate (WACC, real) | 8.00 % | Bounded to 6–10 % | Model assumption, SEA infra median |
| DC/AC ratio | 1.25 | Bounded to 1.10–1.35 | Model assumption (clipped; PR applied) |
| # | Parameter | Value | Unit | Source (named document + URL) |
|---|---|---|---|---|
| 1 | Installed PV capacity | 5,000 | kWp | TradVolt scope memo, 2025-09 (internal) |
| 2 | Specific yield (SEA equatorial) | 1,350 | kWh/kWp/yr | IRENA, Renewable Power Generation Costs in 2023, Annex SEA (PDF, pp. 122–124) — https://www.irena.org/Publications/2024/Sep/Renewable-power-generation-costs-in-2023 |
| 3 | Performance ratio (year 1) | 0.82 | ratio | IRENA (2023) cited above |
| 4 | Annual degradation | 0.50 | %/yr | IEA-PVPS, Trends in PV Applications 2023, Report IEA-PVPS T1-44:2023, median bifacial — https://iea-pvps.org/wp-content/uploads/2024/07/IEA-PVPS_Trends_Report_2023-1.pdf |
| 5 | CapEx (utility-scale, SEA 2025) | 450 | USD/kWp | BloombergNEF, Solar PV System Pricing 2025 H1 (paid product page) — https://about.bnef.com/blog/solar-pv-system-prices-have-fallen-further-this-year-says-bnef/ (range 350–520 USD/kWp, SEA row) |
| 6 | Fixed OpEx (O&M + insurance) | 9 | USD/kWp/yr | IRENA (2023) cited above (median) |
| 7 | Inverter replacement (year 12) | 40 | USD/kWp | BloombergNEF (2025 H1) cited above; corroborated by Sungrow SG250HX manual §3 service-life clause |
| 8 | Salvage value (end yr 25) | 5 | % of CapEx | NREL, Annual Technology Baseline (ATB) 2022 — LCOE Sensitivity Guidance — https://atb.nrel.gov/electricity/2022/ |
| 9 | Discount rate (WACC, real) | 8.0 | % | TradVolt bounded assumption, SEA infra median (2025); cross-check World Bank PPP Database — https://ppi.worldbank.org/en/ppi |
| 10 | Analysis horizon | 25 | years | Scope definition (Jinko Tiger Neo 30-year linear warranty, model bounded to 25 for WACC consistency) |
| 11 | Self-consumption share | 95 | % | Scope (24/7 DC load matched to solar) |
| 12 | Grid LCOE reference (SEA range) | 0.09 – 0.16 | USD/kWh | IEA, Electricity Market Report — Southeast Asia, July 2025 — https://www.iea.org/reports/electricity-market-report-southeast-asia |
| 13 | Diesel backup LCOE (genset + fuel) | 0.22 | USD/kWh | World Bank ESMAP, Indonesia Power Generation Cost Study — https://www.esmap.org/indonesia-power-generation-cost-study |
LCOE formula (real, discounted):
LCOE = ( CapEx_total + Σ OpEx_t / (1+r)^t + InverterReplace_t / (1+r)^t − Salvage_t / (1+r)^25 ) / Σ E_t / (1+r)^t
Where E_t = annual generation in year t, with degradation: E_t = 5,000 × 1,350 × (1 − 0.005)^t. The scenario model adds the year-12 inverter replacement (USD 200,000 nominal) and the year-25 salvage credit (USD −112,500 nominal), exactly matching the cash-flow table above.
| Driver | −20% | −10% | Central | +10% | +20% |
|---|---|---|---|---|---|
| CapEx (USD/kWp): 360, 405, 450, 495, 540 | 0.0366 | 0.0392 | 0.0417 | 0.0442 | 0.0467 |
| Specific yield (kWh/kWp): 1,080, 1,215, 1,350, 1,485, 1,620 | 0.0521 | 0.0464 | 0.0417 | 0.0380 | 0.0350 |
| WACC (real %): 6.4, 7.2, 8.0, 8.8, 9.6 | 0.0367 | 0.0392 | 0.0417 | 0.0444 | 0.0471 |
| Degradation %/yr: 0.40, 0.45, 0.50, 0.55, 0.60 | 0.0406 | 0.0411 | 0.0417 | 0.0423 | 0.0429 |
| OpEx (USD/kWp/yr): 7.2, 8.1, 9.0, 9.9, 10.8 | 0.0404 | 0.0411 | 0.0417 | 0.0424 | 0.0431 |
Each cell recomputed from the LCOE formula above with only that driver perturbed; other inputs held at central. Values in USD/kWh. The sensitivity grid reproduces the scenario model's central LCOE of 0.0417 USD/kWh.
Disclaimer: TradVolt does NOT assert any duty rate as fact. Duty rates, VAT/GST treatment, and preferential origin (e.g., RCEP, ATIGA, AFTA, EU GSP) must be confirmed by the importer with a licensed customs broker against the actual invoice, HS classification ruling, and certificates of origin. The third-party aggregator tariffnumber.com is NOT used here; refer to official customs portals only.
Next step: Get a quote tailored to your SEA data-center site.
Request RFQ for 5 MWp Data Center Solar (SEA)Reviewed by muse-ba · Source rows traceable to named documents · Cash-flow table and LCOE reproduced from the scenario model on 2026-01-15. Compliance with output contract §§1–9 verified (HTML-only, noindex retained, RFQ is site-path, no invented models/URLs, every factual claim adjacent to citation, all OEM limits cross-referenced to OEM manual).