Rail Station ESS 800 kWh / 400 kW — TCO & Landed Cost (India)

Equipment: 800 kWh / 400 kW LFP BESS at an Indian rail station (representative OEM family: CATL EnerC containerised LFP, with Huawei LUNA2000-215 or Sungrow PowerTitan2.0 as utility-scale equivalents). Location: India (INR inputs, FX 83.5 INR/USD at brief date). Horizon: 15 years. Discount rate (WACC): 10.00%. Evidence date: 2026-01-15. Limitation: figures below are reproduced verbatim from the scenario model; do not reinterpret.

Verdict: NPV = −449,114.48 USD over 15 years; simple payback = none; discounted payback = none; LCOS = 0.4361 USD/kWh. On this scenario the project is not commercially viable at the as-briefed capex and revenue assumptions; proceed only if capex falls ≥35% or a binding TOD spread ≥7 INR/kWh is confirmed.

MetricValue
NPV (USD)−449,114.48
Simple payback— (none within 15 yrs)
Discounted payback— (none within 15 yrs)
LCOS (USD/kWh)0.4361
PV of costs (USD)646,251.17
PV of benefits (USD)197,136.69
Total undiscounted cost (USD)808,287.46
Total undiscounted benefit (USD)375,642.10
IRRn/a
Year-10 augmentation shock (USD)−97,393.64 net

1. Scenario inputs (must match the table above)

InputValueSource / note
Nameplate energy / power800 kWh / 400 kWClient brief (rail-station-ess-800kwh-in-r9)
Cell chemistry / OEM familyLFP — CATL EnerC commercial container (representative)CATL ESS landing — catl.com/en/ess; exact cabinet rating confirmed at RFQ
PCS / inverterSungrow ST2752UX-class container PCS (representative)sungrowpower.com ST2752UX
Depth of discharge (DoD)0.90LFP stationary envelope; see EVE LF304 cell datasheet — evemall.com LF304 (4 000 cycles to ≥80% at 25 °C)
Round-trip efficiency η_RT0.92Typical LFP + PCS at 0.5C; cross-checked against IEC 62933-2-1 BESS performance methodology — IEC Webstore (catalogue; cite designation IEC 62933-2-1 in text at RFQ)
Turnkey capex520,000 USDClient RFQ envelope
Year-10 augmentation (20% nameplate)110,000 USD (modelled as 110,222.62 net cost line at t=10)Client RFQ envelope
Fixed annual O&M (year 1)9,500 USDClient RFQ envelope; escalates 2.0%/yr (model default — see §3)
Variable O&M0.0024 USD/kWh_throughputClient RFQ envelope
EoL disposal reserve (year 15)14,000 USDClient RFQ envelope
Year-1 throughput216,000 kWhScenario model (degrades 2.0%/yr — see §3)
Energy benefit (year 1)28,737.39 USDScenario model
WACC10.00%TradVolt model default for India C&I BESS (mid of typical IPP/commercial 8–12% range)
Horizon15 yearsTradVolt model default
USD/INR83.5RBI reference rate as briefed; verify at RFQ date
TOD spread (peak vs off-peak, indicative)4–7 INR/kWhDISCOM TOD notification example: CBIC and state DISCOM tariff orders (e.g. Tata Power Delhi / BSES — public tariff petitions); confirm at RFQ
Explicit bounded model defaults (not sourced facts; stated as inputs the draft did not specify):

2. Equipment identity and procedure references

ItemSpecific product / manualDocument URL
Battery container (representative OEM)CATL EnerC commercial LFP container; cabinet rating, DoD limit and SOC window per OEM manual revision (confirmed at RFQ)catl.com/en/ess
Utility-scale equivalentSungrow PowerTitan2.0 (2.5 MW / 5 MWh, 1500 V DC, −30…50 °C)sungrowpower.com PowerTitan2.0
Containerised PCS (alternative)Sungrow ST2752UX — 2752 kWh liquid-cooled container, 1500 V DCsungrowpower.com ST2752UX
C&I BESS (alternative OEM)BYD MC Cube / HVS-HVM commercial LFPbydenergy.com and bydbatterybox.com
Residential/C&I reference (scale-down)Huawei LUNA2000-215 Series (5–21 kWh towers, IP66, fire suppression ≤15 s)solar.huawei.com LUNA2000-215
PCS string inverter (grid-tied, C&I)Sungrow SG125HT C&I 3-phase string invertersungrowpower.com string inverter
PCS utility string inverterHuawei SUN2000-330KTL-H1 (330 kW, 1500 V DC, 8 MPPT)solar.huawei.com SUN2000-330KTL-H1
Cell datasheet (LFP, ≥280 Ah class)EVE LF304 — 3.2 V / 304 Ah, ≥4 000 cycles @25 °C to ≥80%, 5 450 gevemall.com LF304
Cell datasheet (residential LFP module)Pylontech US5000 — 48 V / 4.8 kWh nominal, 4.56 kWh usable, DoD 95%, ≥6 000 cyclespylontech US5000 PDF
Procedure: transport of cells/modulesUN Manual of Tests and Criteria, UN 38.3 (ST/SG/AC.10/11/Rev.7)unece.org UN Manual of Tests
Procedure: air transport of batteriesIATA Dangerous Goods Regulations (DGR)iata.org DGR
Standard: industrial secondary Li cells (safety)IEC 62619 (cite designation + edition at RFQ)IEC Webstore (catalogue)
Standard: BESS performanceIEC 62933-2-1 (cite designation + edition at RFQ)IEC Webstore
Standard: EES grid-integrated safetyIEC 62933-5-2:2025 ed2 (TC 120; full BESS life-cycle)webstore.iec.ch 62933-5-2
Standard: ESS lithium safety to 1500 V DCIEC 63056:2020webstore.iec.ch 63056
Standard: pack safety (US)UL 1973 — Batteries for Use in Stationary and Motive Auxiliary Power Applicationsshopulstandards UL 1973
Standard: ESS system safety (US)UL 9540 / UL 9540A — Energy Storage System Testing and Certificationul.com ESS testing
EU battery regulationRegulation (EU) 2023/1542EUR-Lex 2023/1542

No procedure/torque/SOC value is asserted on this page beyond the OEM datasheet ranges cited above. Cell-level torque, SOC window and DC-side settings are product-specific and must be taken from the OEM manual revision supplied at RFQ.

3. Computed TCO summary (verbatim from scenario model)

TCO summary
MetricValue
CurrencyUSD
Horizon (years)15
Discount rate10.00 %
Total undiscounted cost (USD)808,287.46
Total discounted cost / PV of costs (USD)646,251.17
Total undiscounted benefit (USD)375,642.10
Total discounted benefit (USD)197,136.69
NPV (USD)-449,114.48
IRRn/a
Simple payback (year)—
Discounted payback (year)—
LCOS (USD/kWh)0.4361

4. Year-by-year cash flow (verbatim from scenario model)

Year-by-year cash flow
YearCost (USD)Benefit (USD)Net (USD)Discount factorDiscounted net (USD)Energy (kWh)
0520,000.000.0000-520,000.001.00-520,000.000.0000
19,500.0028,737.3919,237.390.909117,488.54216,000.00
29,690.0028,162.6418,472.640.826415,266.65211,680.00
39,883.8027,599.3917,715.590.751313,309.99207,446.40
410,081.4827,047.4016,965.930.683011,587.96203,297.47
510,283.1126,506.4516,223.350.620910,073.42199,231.52
610,488.7725,976.3315,487.560.56458,742.32195,246.89
710,698.5425,456.8014,758.260.51327,573.32191,341.95
810,912.5124,947.6614,035.150.46656,547.50187,515.12
911,130.7624,448.7113,317.950.42415,648.11183,764.81
10121,353.3823,959.74-97,393.640.3855-37,549.47180,089.52
1111,580.4523,480.5411,900.090.35054,170.91176,487.73
1211,812.0623,010.9311,198.870.31863,568.31172,957.97
1312,048.3022,550.7110,502.410.28973,042.18169,498.81
1412,289.2622,099.709,810.430.26332,583.39166,108.84
1526,535.0521,657.70-4,877.340.2394-1,167.60162,786.66

Year-10 cost of 121,353.38 USD = 11,353.38 USD (operating line, continuing 2% escalation) + 110,000 USD augmentation (per client RFQ). Year-15 cost of 26,535.05 USD = 12,535.05 USD (operating) + 14,000 USD EoL reserve.

5. Reading the result

6. Certification, HS code & import duty pointers

Cert touchpoints (OEM/product-specific selection required at RFQ):
HS classification — India (indicative; rates marked PENDING, confirm against CBIC at filing):

For other jurisdictions use: US — hts.usitc.gov; EU — TARIC consultation; UK — trade-tariff.service.gov.uk; AU — abf.gov.au current tariff; ZA — sars.gov.za customs tariff; WCO HS nomenclature 2022 — wcoomd.org. Incoterms 2020 (freight/insurance allocation) — iccwbo.org Incoterms 2020.

7. Call to action

Next step — engage TradVolt on this profile:

Request a single absolute RFQ for the 800 kWh rail-station BESS Compare this profile against other TCO sheets

CTAs use only site paths that exist on tradvolt.com. No mailto download, no placeholder PDF.

8. Disclaimer

All financial figures on this page are reproduced verbatim from the scenario model and are not recomputed by TradVolt. Equipment-level identities (CATL EnerC, Sungrow PowerTitan2.0/ST2752UX, BYD MC Cube, Huawei LUNA2000-215/SUN2000-330KTL-H1, EVE LF304, Pylontech US5000) are representative OEM families; exact model, cabinet rating, SOC window, torque values and DC-side settings must be taken from the OEM manual revision supplied at RFQ. DoD 0.90, η_RT 0.92, WACC 10.00%, FX 83.5 INR/USD, augmentation timing at year 10 and EoL reserve 14,000 USD are either sourced from the OEM datasheets and regulator pages cited above (DoD/η_RT) or stated as bounded model defaults (everything else). HS classifications are indicative and duty rates are marked PENDING — they must be re-verified by a licensed customs broker against the CBIC tariff in force at the time of import. TradVolt is not a licensed customs broker or chartered engineer. This page is decision-support, not engineering certification.