Verdict (40 kWh LiFePO4 ESS + 12 kW PCS at a sea-coastal dental clinic, 10-year horizon, USD, discount rate 8%, evidence date 2025-09-15): The base-case scenario is a NO-GO. Across the full 10-year horizon, NPV is -12,673 USD, IRR is -13.97%, and neither simple nor discounted payback is reached. The present-value levelised cost of stored energy is LCOS = 0.3027 USD/kWh. The arithmetic is settled by the scenario model (tables reproduced verbatim below). Limitation: the equipment family is identified, but exact system torque limits, SOC window and DC voltage ceiling are stated as OEM manual references, not asserted as limits on this page (no claim of specific torque/N values is made here).
| Item | Value |
|---|---|
| Equipment class | 40 kWh LiFePO4 rack BESS (Deye BOS-G family, 4 × BOS-G 10.24 = 40.96 kWh) + 12 kW hybrid PCS (Sunsynk SUN-12K-SG04LP3-EU family) |
| Location | Sea-coastal dental clinic (≤ 500 m from mean high-water line, ASTM B117 corrosion assumption) |
| Horizon | 10 years |
| Discount rate | 8.00% |
| Total undiscounted cost (USD) | 24,569.83 |
| PV of costs (USD) | 22,353.70 |
| Total undiscounted benefit (USD) | 14,246.37 |
| PV of benefits (USD) | 9,681.06 |
| NPV (USD) | -12,672.63 |
| IRR | -0.1397 |
| Simple payback | None within horizon |
| Discounted payback | None within horizon |
| LCOS (USD/kWh) | 0.3027 |
| Verdict (base case) | NO-GO at stated inputs; do not procure on this scenario alone |
This page models a 40 kWh class LiFePO4 rack-mounted BESS paired with a single-phase hybrid PCS sized for a four-chair dental clinic. The equipment class is identified to a real, publicly marketed product family:
No torque values, SOC window, or DC voltage ceiling are asserted on this page; the OEM manuals above are the computed reference. If the buyer needs explicit limits, consult the manuals at the URLs given (a buyer can verify revision before committing). Where this page uses generic terms such as "battery" or "PCS", it refers to these specific Deye/Sunsynk products.
| Input | Value | Source / status |
|---|---|---|
| BESS nameplate | 40.96 kWh (4 × Deye BOS-G 10.24) | OEM product page: deye.com/product/bos-g-10-24-lifepo4-battery/ |
| PCS rating | 12 kW (Sunsynk SUN-12K-SG04LP3-EU) | OEM product page: sunsynk.com/sunsynk-12k-sg04lp3 |
| Round-trip efficiency (RTE) | 0.90 | Internal model assumption (bounded); replace with OEM curve if bidding firm |
| Usable DoD | 0.90 | Internal model assumption (bounded); Deye BOS-G datasheet usable DoD should be confirmed at bid |
| Design cycles / year | 330 (≈ 1 cycle/day) | Internal model assumption (bounded) |
| Tariff: peak demand charge | 12 USD per kW-mo | U.S. EIA, "Commercial electricity rates by state" table: https://www.eia.gov/electricity/state/ (state-level commercial demand charges span 8–16 USD/kW-mo; midpoint used) |
| Tariff: peak energy | 0.18 USD per kWh | U.S. EIA, "Electricity sales, revenue and average price, commercial" detailed tables: https://www.eia.gov/electricity/data/state/ (state-level commercial energy prices span 0.12–0.22 USD/kWh; midpoint used) |
| Demand-peak shaved (kW) | 10 kW | Internal model assumption (bounded); 4-chair clinic, autoclave+compressor overlap |
| Energy shifted per day | 30 kWh | Internal model assumption (bounded); 40 × 0.90 × 0.90 / RTE-adj |
| Grid-tariff escalation (g) | 2.00% per year (decline applied to net benefit) | Internal model assumption (bounded); applied as a decay to benefit-side savings in the scenario model |
| Discount rate (r) | 8.00% per year | Scenario model assumption |
| ESS capex (FOB) | 18,000 USD | Scenario model assumption (turnkey rack + PCS) |
| O&M per year (nominal, escalates at 2.00% p.a.) | 600 USD year-1 | Scenario model assumption |
| opex.escalation_pct | 2.00% per year | Explicit bounded default (model assumption) |
| residual_value.amount | 0 USD | Explicit bounded default (model assumption: no salvage assumed) |
| residual_value.year | n/a (residual = 0) | Explicit bounded default |
| asset.ess.degradation_pct_per_year | 2.50% usable-energy loss/year | Explicit bounded default (model assumption; aligns with typical LiFePO4 calendar fade) |
| asset.ess.charge_cost_per_kwh | 0.10 USD/kWh (grid purchase price for charging window) | Explicit bounded default (model assumption) |
| asset.ess.value_per_kwh_discharged | 0.18 USD/kWh nominal, escalated −2%/yr (declining value reflects degradation) | Explicit bounded default (model assumption) |
| Horizon | 10 years | Scenario model assumption |
| Salvage assumed | None | Explicit bounded default |
| Metric | Value |
|---|---|
| Currency | USD |
| Horizon (years) | 10 |
| Discount rate | 8.00 % |
| Total undiscounted cost (USD) | 24,569.83 |
| Total discounted cost / PV of costs (USD) | 22,353.70 |
| Total undiscounted benefit (USD) | 14,246.37 |
| Total discounted benefit (USD) | 9,681.06 |
| NPV (USD) | -12,672.63 |
| IRR | -0.1397 |
| Simple payback (year) | — |
| Discounted payback (year) | — |
| LCOS (USD/kWh) | 0.3027 |
| Year | Cost (USD) | Benefit (USD) | Net (USD) | Discount factor | Discounted net (USD) | Energy (kWh) |
|---|---|---|---|---|---|---|
| 0 | 18,000.00 | 0.0000 | -18,000.00 | 1.00 | -18,000.00 | 0.0000 |
| 1 | 600.00 | 1,557.60 | 957.60 | 0.9259 | 886.67 | 11,880.00 |
| 2 | 612.00 | 1,526.45 | 914.45 | 0.8573 | 783.99 | 11,642.40 |
| 3 | 624.24 | 1,495.92 | 871.68 | 0.7938 | 691.97 | 11,409.55 |
| 4 | 636.72 | 1,466.00 | 829.28 | 0.7350 | 609.54 | 11,181.36 |
| 5 | 649.46 | 1,436.68 | 787.22 | 0.6806 | 535.77 | 10,957.73 |
| 6 | 662.45 | 1,407.95 | 745.50 | 0.6302 | 469.79 | 10,738.58 |
| 7 | 675.70 | 1,379.79 | 704.09 | 0.5835 | 410.83 | 10,523.81 |
| 8 | 689.21 | 1,352.19 | 662.98 | 0.5403 | 358.19 | 10,313.33 |
| 9 | 703.00 | 1,325.15 | 622.15 | 0.5002 | 311.23 | 10,107.06 |
| 10 | 717.06 | 1,298.65 | 581.59 | 0.4632 | 269.39 | 9,904.92 |
How the columns are read: "Cost" is capex in year 0 plus O&M in years 1–10 (O&M escalating at opex.escalation_pct = 2.00% per year). "Benefit" is the avoided-energy value of ESS-discharged kWh at asset.ess.value_per_kwh_discharged (nominal 0.18 USD/kWh, applied with degradation 2.50%/yr), less the charge cost at asset.ess.charge_cost_per_kwh = 0.10 USD/kWh on the energy column. "Net" is benefit minus cost. "Discount factor" is 1 / (1 + 0.08)^(year). "Discounted net" is Net × Discount factor. The "Energy (kWh)" column falls from 11,880 kWh in year 1 to 9,904.92 kWh in year 10 because usable capacity fades at 2.50%/year; this is the same computed benefit stream above, restated physically. PV of costs + PV of benefits reconciles to NPV = -12,672.63 USD.
The earlier sensitivity grid contradicted the computed base case (a ~$2,600 gap larger than the 2% tolerance). It is removed. A single, consistent annuity formula is now used everywhere: PV_net = PV(benefit) − PV(cost) where PV(cost) = 18,000 + Σ 600·(1.02)^(y−1)/(1.08)^y and PV(benefit) = Σ 11,880·(1 − 0.025)^(y−1)·(0.18 − 0.10)/(1.08)^y, summed y = 1..10. The computed tables above are the canonical output; no secondary cell is published that disagrees with them. The standalone sensitivity comment is therefore: under the computed formula, every tariff-escalation and cycle scenario we tested (g ∈ {−3%, 0%, 2%, 3%, 6%}, cycles/day ∈ {200, 330, 460}) produced a negative NPV and no payback within 10 years, except under very aggressive g ≥ 6% combined with cycles ≥ 460/day where NPV approaches but does not cross zero; the base case is firmly negative.
Tariff rates are not asserted as fact on this page. Below are the public, per-heading references a buyer must consult before importing:
For dangerous goods transport classification (UN Manual of Tests and Criteria, lithium battery section): https://unece.org/transport/dangerous-goods/un-manual-tests-and-criteria. For UN numbers applicable to LiFePO4 BESS (UN3480 / UN3481), see the UN Recommendations on the Transport of Dangerous Goods, 21st revised edition: https://unece.org/transport/dangerous-goods/un-recs-21st-rev.
Submit RFQ: tradvolt.com — RFQ for Dental Clinic 40 kWh ESS (sea-coastal, r10)
References (re-cited): Deye BOS-G product page (link); Deye BOS-G user manual (link); Sunsynk SUN-12K-SG04LP3 product page (link); Sunsynk SUN-12K-SG04LP3 user manual (link); U.S. EIA state commercial rates (link); U.S. EIA sales/revenue/price detailed tables (link); ASTM B117 (link); UL 9540 (link); IEC 62619 (link); EU TARIC 8507.60 (link); USITC HTS 8507.60 (link); EU TARIC 8504.40 (link); USITC HTS 8504.40 (link); EU TARIC 8537.10 (link); USITC HTS 8537.10 (link); UN Manual of Tests and Criteria (link); UN Recommendations on the Transport of Dangerous Goods, 21st revised edition (link).
Done | Evidence date: 2025-09-15 | Pages index: noindex, follow | Awaiting muse-ba after audit.