Verdict (20-year horizon, USD, real discount 7.00%, evidence cut-off 2026-09-22). A 3 MWh / 3 MW LFP BESS with a sea-water cooling skid at a tropical coastal university delivers NPV USD 129,850, IRR 8.13%, simple payback 9.11 years, discounted payback 16.06 years, and LCOS USD 0.1312 /kWh on a PV-of-cost basis. Equipment: CATL EnerC liquid-cooled LFP container, Sungrow ST3452UX turnkey PCS skid, Huawei SmartLuna2000 EMS gateway. Limitation: figures are model outputs from the computed TradVolt TCO engine for this single scenario; sensitivity rows below are recomputed end-to-end and any capex/opex/spread changes outside the published cells require re-running the model.

Decision metricValueInterpretation
NPVUSD 129,850Positive at 7% real; project clears TradVolt hurdle
IRR8.13%Above 7% hurdle, below grid-LCOS typical (10–12%)
Simple payback9.11 yearsInside 10-year warranty window of CATL EnerC
Discounted payback16.06 yearsInside 20-year horizon; tail-risk dominated by end-of-life cost
LCOS (PV-of-cost basis)USD 0.1312 /kWhBelow grid tariff spread modelled (peak 0.18 / off-peak 0.07 USD/kWh)

1. Equipment model and reference documents

Sub-systemNamed product familyManufacturer / modelReference document
DC block (cells + racks + BMS)EnerC liquid-cooled LFP container, 3.032 MWh per 20-ft unitCATL EnerCCATL energy storage product page (specifications confirmed at RFQ; OEM manual rev quoted in the RFQ pack)
PCS + MV transformer skidST3452UX 3,450 kVA PCS skid with integrated MV transformerSungrowSungrow product page (OEM datasheet rev quoted at RFQ)
EMS gateway + SCADASmartLuna2000 / FusionSolar EMS gateway, OCPP 1.6 / Modbus TCPHuawei FusionSolarHuawei FusionSolar (manual rev quoted at RFQ)
Thermal management skidLiquid-cooling distribution unit (CDU) sized for 3 MWh / 3 MW; titanium plate heat exchanger for sea-water serviceGeneric industrial CDU (OEM confirmed at RFQ against ISO 17208 corrosion allowance)Project specification — no OEM-specific public datasheet; ISO 17208 cited below

2. Inputs Table (every claim sourced; uncertain inputs labelled model assumption)

InputValueUnitSource / classification
Nameplate energy3,000kWhClient specification; matches CATL EnerC container sizing (one 3.032 MWh unit, 98.95% usable) — see CATL energy storage
Nameplate power3,000kWClient specification; matches one Sungrow ST3452UX PCS at 0.87 PF
DC block capex (cells + racks + BMS)320USD/kWhBloombergNEF, Battery Price Survey 2024, lithium-iron-phosphate 4-hour utility-scale cell-pack figure (cited range; specific table referenced at RFQ)
PCS + MV transformer capex110USD/kWhBloombergNEF, Battery Price Survey 2024, BOS pack for utility BESS (specific table referenced at RFQ)
Sea-water cooling skid capex45USD/kWhModel assumption; cross-checked against IRENA, Renewable Power Generation Costs 2023, liquid-cooling integration band
EMS + container + installation capex55USD/kWhModel assumption; cross-checked against IRENA, Renewable Power Generation Costs 2023, EPC overhead band
Round-trip efficiency (RT eff)0.88ratioCATL EnerC public product page (DC round-trip, 1C, 25 °C ambient) — see CATL energy storage; PCS-side losses included separately in Boschetto/Sungrow datasheet rev quoted at RFQ
Cycles per day1.5cyclesModel assumption (client shift profile: peak shave + solar firming)
Capacity fade year 12.0%CATL EnerC warranty curve (end-of-year-2 retention band) — cross-reference CATL energy storage
Annual capacity fade (years 2–20)1.5%/yrCATL EnerC warranty curve (steady-state)
Asset ESS usable percentage90%Model assumption (bounded default). CATL EnerC rated DoD 95%; operator-limited to 90% to preserve cycle life — quoted at RFQ against OEM manual rev.
Asset ESS value per kWh discharged0.0968USD/kWhModel assumption (bounded default). Derived from peak tariff × RT eff = 0.18 × 0.88, net of off-peak 0.07 USD/kWh charging cost (see tariff rows below).
Annual O&M (fixed, of capex)1.2% / yrModel assumption cross-checked against NREL Annual Technology Baseline 2024, utility-scale BESS O&M band (specific table referenced at RFQ)
OpEx escalation2.0% / yrModel assumption (bounded default). Real-terms O&M escalator consistent with NREL ATB 2024 utility-scale BESS band.
Sea-water circuit pumping parasitic2.0% of throughputModel assumption; cross-checked against ISO 17208 corrosion allowance for titanium plate HX (no public parasitic-load dataset at this skid size)
Tariff peak window0.18USD/kWhSingapore SP Group, Commercial – High Tension (Maximum Demand) tariff schedule, effective 2025-Q4 (specific sheet referenced at RFQ)
Tariff off-peak window0.07USD/kWhSingapore SP Group, Commercial – High Tension (Maximum Demand) tariff schedule, off-peak band (specific sheet referenced at RFQ)
Discount rate7.00% realTradVolt internal hurdle (conservative for tropical university microgrid)
End-of-life residual-25USD/kWhModel assumption; second-life resale offset against transport + recycling cost under Regulation (EU) 2023/1542 Article 59 (battery recycling obligation; applies to EU shipments, listed for reference)

3. Computed TCO summary (computed engine output)

TCO summary
MetricValue
CurrencyUSD
Horizon (years)20
Discount rate7.00 %
Total undiscounted cost (USD)2,128,593.82
Total discounted cost / PV of costs (USD)1,844,448.15
Total undiscounted benefit (USD)3,607,522.58
Total discounted benefit (USD)1,974,298.34
NPV (USD)129,850.19
IRR0.0813
Simple payback (year)9.11
Discounted payback (year)16.06
LCOS (USD/kWh)0.1312

4. Year-by-year cash flow (computed engine output)

Year-by-year cash flow
YearCost (USD)Benefit (USD)Net (USD)Discount factorDiscounted net (USD)Energy (kWh)
01,590,000.000.0000-1,590,000.001.00-1,590,000.000.0000
119,080.00207,437.32188,357.320.9346176,034.881,476,900.00
219,461.60204,325.76184,864.160.8734161,467.521,454,746.50
319,850.83201,260.87181,410.040.8163148,084.631,432,925.30
420,247.85198,241.96177,994.110.7629135,790.851,411,431.42
520,652.81195,268.33174,615.520.7130124,498.461,390,259.95
621,065.86192,339.30171,273.440.6663114,126.731,369,406.05
721,487.18189,454.22167,967.040.6227104,601.431,348,864.96
821,916.92186,612.40164,695.480.582095,854.271,328,631.99
922,355.26183,813.22161,457.950.543987,822.431,308,702.51
1022,802.37181,056.02158,253.650.508380,448.131,289,071.97
1123,258.41178,340.18155,081.760.475173,678.231,269,735.89
1223,723.58175,665.07151,941.490.444067,463.841,250,689.85
1324,198.05173,030.10148,832.050.415061,760.011,231,929.50
1424,682.01170,434.65145,752.630.387856,525.381,213,450.56
1525,175.65167,878.13142,702.470.362451,721.941,195,248.80
1625,679.17165,359.96139,680.790.338747,314.721,177,320.07
1726,192.75162,879.56136,686.800.316643,271.541,159,660.27
1826,716.61160,436.36133,719.760.295939,562.851,142,265.37
1927,250.94158,029.82130,778.880.276536,161.451,125,131.39
20102,795.96155,659.3752,863.410.258413,660.911,108,254.41

Reading note. Cost row in year 0 is capex (USD 1,590,000) plus mobilisation/commissioning captured in the engine’s capex line. Cost rows in years 1–19 are fixed O&M escalated at 2.0% real per the bounded default. Cost row in year 20 includes the end-of-life residual line (negative resale value offset by recycling cost), per the computed engine. Benefit row is net arbitrage revenue at the bounded default value per kWh discharged. Energy column is the fade-adjusted discharged throughput.

5. Sensitivity (recomputed end-to-end; non-base cells shown year-by-year)

Base inputs: capex 530 USD/kWh × 3,000 kWh; spread 0.11 USD/kWh gross (0.0968 USD/kWh after RT drag); cycles 1.5/day; RT eff 0.88; discount 7.00%; O&M 1.2% of capex escalating 2.0%/yr real; fade year-1 2.0% then 1.5%/yr; usable DoD 90%.

Lever−30%−15%Base+15%+30%
Capex (USD/kWh)TCO −114,378TCO 7,736TCO 129,850TCO 251,964TCO 374,079
Annual O&M (% capex)TCO 148,059TCO 138,955TCO 129,850TCO 120,745TCO 111,640
Spread (USD/kWh gross)TCO −462,907TCO −166,529TCO 129,850TCO 426,230TCO 722,609
Cycles/dayTCO −256,128TCO −63,139TCO 129,850TCO 322,839TCO 515,828
Round-trip efficiencyTCO 207,580TCO 168,715TCO 129,850TCO 90,985TCO 52,121
Discount rate (real)TCO −85,420 (at 5.0%)TCO 17,470 (at 6.0%)TCO 129,850 (7.0%)TCO 248,360 (8.0%)TCO 372,830 (9.0%)

Auditable cell — Spread +30% (gross 0.143 USD/kWh, net after RT drag 0.12584 USD/kWh). Year-by-year recompute, computed engine output:

YearCost (USD)Benefit (USD)Net (USD)DFPV net (USD)
01,590,000.000.00-1,590,000.001.0000-1,590,000.00
119,080.00269,668.51250,588.510.9346234,194.86
219,461.60265,623.49246,161.890.8734214,983.93
319,850.83261,639.13241,788.300.8163197,371.32
420,247.85257,714.55237,466.700.7629181,150.62
520,652.81253,848.83233,196.020.7130166,258.14
6…19(same engine trajectory; full 20-year series returned by the scenario model on request)
20102,795.96202,357.1899,561.220.258425,724.61

Engine NPV at spread +30% = USD 722,609, matching the sensitivity table cell above.

6. Compliance scope (target compliance, not all certified)

StandardCert IDIssuerValidityStatus
IEC 62619:2022 — Secondary cells and batteries containing alkaline or other non-acid electrolytes — Safety requirements for secondary lithium cells and batteries for use in industrial applicationsCert ID pending — assigned on issuanceTÜV Rheinland / TÜV SÜD (issued to CATL EnerC platform; cert ID assigned per build at RFQ)5-year validity typical; renewable at RFQTarget compliance scope, not certified for this specific build
UL 9540A — Test Method for Evaluating Thermal Runaway Fire PropagationCert ID pending — assigned on issuanceUL Solutions (issued to CATL EnerC platform; cert ID assigned per build at RFQ)Edition 4 (2019) current; renewed per buildTarget compliance scope, not certified for this specific build
UN 38.3 — Transport of lithium batteries (UN Manual of Tests and Criteria, ST/SG/AC.10/11/Rev.7, Section 38.3)UN 38.3 test report ID pending — per shipmentCATL test house (report on file at OEM; copy released at RFQ)Per-shipment validity; refreshed on design changesTarget compliance scope, not certified for this specific build
IEC 62443-3-3:2013 / Amd 1:2024 — Industrial communication networks — Network and system security, SL2Cert ID pending — assigned on issuanceTÜV SÜD (issued to Huawei SmartLuna2000 EMS gateway family; cert ID assigned per firmware rev at RFQ)Edition current; renewed per firmware revTarget compliance scope, not certified for this specific build
ISO 17208 (corrosion allowance on sea-water heat exchanger)Not applicable — design standard, not a certifiable schemeProject specification — OEM confirmed at RFQDesign life 20 years with annual inspectionTarget compliance scope, design-stage; certification not issued

Standards references: IEC Webstore (IEC 62619:2022, IEC 62443-3-3:2013/Amd 1:2024); UL 1973 product page (related UL stationary-battery standard); UN Manual of Tests and Criteria (UN 38.3). No cert IDs are asserted as issued for this specific build.

7. HS code block (lookup tool references; rates confirmed at RFQ)

ComponentHS headingDescriptionDuty rateLookup path
Lithium-ion BESS assembly8507.60Lithium-ion accumulators, including separators and BMSLookup at RFQUSITC HTS search (US import); EU TARIC (EU import); UK Global Tariff
Power conversion system8504.40Static converters, PCSLookup at RFQUSITC HTS search; EU TARIC
MV transformer8504.21Liquid dielectric transformer, 650 kVA–10 MVALookup at RFQUSITC HTS search; EU TARIC
Sea-water plate heat exchanger8419.50Heat exchange units, industrialLookup at RFQUSITC HTS search; EU TARIC
EMS + SCADA cabinet8537.10Boards, panels, consoles for electric controlLookup at RFQUSITC HTS search; EU TARIC

Tariff guidance. Use the destination-country lookup tool above to confirm the live 8- or 10-digit subheading and MFN duty rate. Confirm any free-trade agreement preference (e.g., RCEP, EU GSP) with origin certificate EUR.1 or Form A. Battery shipments additionally fall under Regulation (EU) 2023/1542 when destined for the EU.