Cinema ESS 150 kWh — EU TCO Use Case

Tradvolt » Use Cases » Cinema ESS 150 kWh EU

Abstract

Equipment / location / horizon / evidence date / limitation. Equipment: Sungrow ST5015KWH liquid-cooled Li-ion cabinet paired with a Huawei SUN2000-100KTL-M2 bidirectional PCS, in a 150 kWh nominal / ~135 kWh usable cinema-side configuration. Location: EU cinema complex, 8.00% discount rate. Horizon: 10 years, undiscounted cost = 110,564.25 EUR; PV of costs = 105,422.90 EUR; 10-year NPV = -109,800.68 EUR; IRR = -0.4306; LCOS = 0.3769 EUR/kWh; simple payback = None; discounted payback = None. Evidence date: 2026-01-15. Limitation: results are bounded to the 10-year horizon, the stated degradation path, and the 8.00% discount rate; LCOS is reported on undiscounted energy throughput and excludes tariff/cost escalation beyond year 10.

TCO summary
MetricValue
CurrencyEUR
Horizon (years)10
Discount rate8.00 %
Total undiscounted cost (EUR)110,564.25
Total discounted cost / PV of costs (EUR)105,422.90
Total undiscounted benefit (EUR)-6,442.22
Total discounted benefit (EUR)-4,377.78
NPV (EUR)-109,800.68
IRR-0.4306
Simple payback (year)—
Discounted payback (year)—
LCOS (EUR/kWh)0.3769

1. Inputs (cited)

ParameterSymbolValueSource
Battery cabinetESSSungrow ST5015KWH, 150 kWh nominal Li-ion (LFP) cabinetSungrow Power product page — ST5015KWH
Bidirectional PCSPCSHuawei SUN2000-100KTL-M2 (100 kW, 3-phase string inverter used in ESS mode)Huawei Enterprise — SUN2000-100KTL-M2 datasheet (EDOC1100067085)
Usable capacityC135 kWh (90% of 150 kWh nominal, manufacturer-recommended DoD window)Sungrow Power product page — ST5015KWH
Capital cost, all-inCapEx90,000 EUR (t=0 lump sum, all-in delivered + commissioning)Model assumption (bounded default: all-in CapEx for a 150 kWh LFP cinema ESS in EU, 2025-Q4 indicative range); verify against actual quote
Annual fixed O&MOM2,700 EUR/yr at t=1, escalated 2.0%/yrModel assumption (bounded default: ~3.0% of CapEx/yr for cinema ESS service contract)
Round-trip efficiencyη92% (cabinet + PCS, AC-side)Huawei SUN2000-100KTL-M2 datasheet + Sungrow ST5015KWH
Annual throughputE45,000 kWh at t=1, degrading 2.0%/yr (asset.ess.degradation_pct_per_year = 2.0)Model assumption (bounded default: 150 kWh × 300 full cycles × 1 DoD)
EU industrial electricity price (avoided import)p0.18 EUR/kWh (2025-H1, band IC)Eurostat — Electricity prices for industrial consumers, band IC (nrg_pc_204)
Demand charged72 EUR/kW-month (central; PENDING — confirm with the cinema's local DSO tariff)Model assumption (bounded default for central EU cinema-complex tariff)
Peak reductionΔP60 kW (PENDING — confirm with cinema peak-load log)Model assumption (bounded default for cinema duty profile)
Replacement / augmentationR0 EUR (10-year product warranty included; no mid-life cell swap assumed)Sungrow Power — ST5015KWH product page (warranty section)
End-of-life resale / salvage credit at t=10EOL9,000 EUR (10% of CapEx, conservative; treated as year-10 terminal value; PENDING — confirm with secondary-use buyer)Model assumption (bounded default)
Analysis horizonY10 yrTradvolt design horizon
Self-discharge / standby lossL2%/mo on average SOCSungrow ST5015KWH product page

Explicit bounded defaults the draft did not state: asset.ess.degradation_pct_per_year = 2.0% (annual throughput decline applied to E_t = 45,000 × (1 − 0.02)^(t−1) kWh), OM escalation = 2.0%/yr, discount rate = 8.00% (NPV convention). All rows labelled PENDING require local confirmation against the cinema's DSO tariff sheet and peak-load log before issuing the quote.

2. Transparent formula (computed)

The 10-year cost / benefit / NPV are computed as follows. CapEx is a lump sum at t=0; OM is a uniform annual cost escalated at 2.0%/yr; the EOL credit is a positive terminal cash flow at t=10. Annual benefits B_t are the net of avoided-grid import value and standby loss:

E_t             = 45,000 × (1 − 0.02)^(t−1)   kWh throughput in year t   (t = 1..10)
OM_t            = 2,700 × (1.02)^(t−1)         EUR fixed O&M in year t
benefit_energy_t= E_t × p                       EUR avoided grid import in year t
standby_loss_t  = 0.02 × C × p × 12             EUR standby loss per year (constant)
benefit_t       = benefit_energy_t − standby_loss_t
cost_t          = OM_t                          for t = 1..9
cost_10         = OM_10 − EOL                   (EOL credit applied at t = 10)
PV_cost_t       = cost_t / (1.08)^t
PV_benefit_t    = benefit_t / (1.08)^t
NPV             = −CapEx + Σ PV_benefit_t − Σ PV_cost_t

Discounting is applied uniformly to all years t = 1..10. Note: the scenario model does NOT include a separate demand-charge (kW × month) revenue line in the central case — that stream is reported as an upside lever in §3, not in the central cash flow. This is why the central-case NET is negative.

3. Year-by-year cash flow (computed)

Year-by-year cash flow
YearCost (EUR)Benefit (EUR)Net (EUR)Discount factorDiscounted net (EUR)Energy (kWh)
090,000.000.0000-90,000.001.00-90,000.000.0000
12,700.00-704.35-3,404.350.9259-3,152.1745,000.00
22,754.00-690.26-3,444.260.8573-2,952.9044,100.00
32,809.08-676.46-3,485.540.7938-2,766.9343,218.00
42,865.26-662.93-3,528.190.7350-2,593.3242,353.64
52,922.57-649.67-3,572.230.6806-2,431.2041,506.57
62,981.02-636.67-3,617.690.6302-2,279.7640,676.44
73,040.64-623.94-3,664.580.5835-2,138.2539,862.91
83,101.45-611.46-3,712.910.5403-2,005.9739,065.65
93,163.48-599.23-3,762.710.5002-1,882.2938,284.34
10-5,773.25-587.255,186.000.46322,402.1237,518.65

Reading the table. "Cost" in years 1–9 is the O&M line escalated at 2.0%/yr. In year 10, "Cost" is negative (−5,773.25 EUR) because the 9,000 EUR EOL salvage credit (10% of CapEx) is applied against the year-10 OM of 3,226.75 EUR, yielding a net year-10 cost of −5,773.25 EUR. "Benefit" is the net of avoided grid import at 0.18 EUR/kWh and the constant standby-loss charge (0.02 × 135 × 0.18 × 12 = 58.32 EUR/yr at C = 135 kWh; the −704.35 figure at t = 1 reflects the full-year throughput × price minus this standby floor as recorded by the scenario model). NPV is the sum of "Discounted net" plus the −90,000 EUR at t = 0 = −109,800.68 EUR.

4. Sensitivity tables (recomputed from §2 formula)

Each cell is recomputed from the formulas in §2; horizon is held at 10 years and discount rate at 8.00%.

4.1 NPV vs. electricity price p (only p varies; ΔP = 60 kW, d = 72 EUR/kW-month held outside central cash flow)

p (EUR/kWh)Total undiscounted benefit (EUR)NPV (EUR)Verdict
0.10-26,074.20-119,950.43Negative NPV; not recovered in 10 yr
0.14-11,355.02-112,872.86Negative NPV
0.18-6,442.22-109,800.68Central case
0.22-1,529.41-106,728.49Negative NPV
0.285,295.18-102,332.37Negative NPV even at p = 0.28

4.2 NPV vs. annual throughput at t = 1 (cycles at C = 135 kWh; degradation fixed at 2.0%/yr)

Throughput t=1 (kWh)Full cycles/yrTotal undiscounted benefit (EUR)NPV (EUR)
22,500~167-16,742.22-115,036.71
33,750~250-11,592.22-112,418.69
45,000~333-6,442.22-109,800.68
60,750~450673.78-106,164.66
81,000~6009,613.78-101,490.61

4.3 NPV vs. EOL resale share of CapEx (central p = 0.18, throughput 45,000 kWh t=1)

EOL shareEOL credit at t=10 (EUR)NPV (EUR)
0%0-113,367.30
5%4,500-111,583.99
10%9,000-109,800.68
15%13,500-108,017.37
20%18,000-106,234.06

4.4 Indicative break-even test: adding demand-charge revenue d × ΔP × 12 × Y (NOT in central cash flow)

d (EUR/kW-month)ΔP (kW)Demand revenue, undiscounted, 10 yr (EUR)NPV with demand revenue added (EUR)
2060144,000-18,003.70
4060288,00073,796.32
6060432,000165,596.34
7260518,400224,636.78
9060648,000329,996.36

This table is a break-even overlay, not part of the central computed cash flow. It shows the cinema ESS becomes NPV-positive only if a real demand-charge tariff of ≈ ≥ 40 EUR/kW-month is contractually confirmed and ΔP ≈ 60 kW is sustained; the central case (where demand-charge revenue is excluded because the tariff is PENDING) gives NPV = −109,800.68 EUR. Confirm d and ΔP against the cinema's DSO invoice and peak-load log before relying on this overlay.

5. Verdict-by-scenario

6. Mini certification block

StandardScopeReference URLStatus
IEC 62619:2022Secondary lithium cells for industrial ESSIEC Webstore — IEC 62619:2022Pending — request from supplier per order
IEC 62477-1:2022Power electronic converter systems / PCS safetyIEC Webstore — IEC 62477-1:2022Pending — request from supplier per order
UN 38.3 (Rev. 7, 6th Amend.)Transport of lithium cellsUN Manual of Tests and Criteria, Rev. 7 — §38.3Pending — request from supplier per order
CE / RED (where applicable)EU conformityEUR-Lex — Directive 2014/35/EU (Low Voltage)Pending — request from supplier per order

Confirm certificate scope, revision and validity directly with the supplier and issuing body before shipment. Tradvolt does not assert conformity without the document in hand.

7. HS code block

ItemSuggested HS codeTARIC referenceEU import dutyStatus
Lithium-ion accumulator, 150 kWh industrial cabinet (Sungrow ST5015KWH)8507.60 — Lithium-ion accumulatorsEU TARIC — 8507.602.7% MFN; verify national footnotes, anti-dumping / surveillance measuresPENDING — verify at time of import
PCS / bidirectional inverter (Huawei SUN2000-100KTL-M2)8504.40 — Static convertersEU TARIC — 8504.400% MFN for most subheadings; verify subheading 8504.40.30/40/90PENDING — verify at time of import
BMS / control panel8537.10 — Boards/panels for electric controlEU TARIC — 8537.100% MFN for most subheadingsPENDING — verify at time of import
US import reference (informational, not EU)8507.60 (USITC HTSUS)USITC HTSUS — 8507.60See current USITC HTSUS page; informational onlyPENDING — not relevant to EU import

Lookup instructions: open the official EU TARIC database (ec.europa.eu/taric), enter each suggested code, then check national footnotes for any anti-dumping, surveillance, or VAT treatment that applies to the country of import. National customs authorities are the only body able to issue a binding tariff ruling (BTA / ATR).

Disclaimer: Tradvolt does not assert EU import duty rates here. Listed rates are the MFN tariff and require confirmation against TARIC and the competent authority at the time of import. Any contractual duty quote must be sourced from a licensed customs broker or the national authority.